background image

13

441 01 5003 01

Specifications are subject to change without notice

7. Masonry Chimney Venting

CARBON MONOXIDE POISONING, FIRE AND

EXPLOSION HAZARD.
Failure to properly vent this furnace could result in

personal injury, death and/or property damage.
Follow these installation instructions.

!

Chimney Inspection

All masonry chimney construction must conform to the Standard for

Chimneys, Fireplaces, Vents, and Solid Fuel--Burning Appliances

ANSI/NFPA 211--2006 and to any state or local codes applicable.

The chimney must be in good condition and a complete chimney

inspection must be conducted prior to furnace installation. If the

inspection reveals damage or abnormal conditions, make

necessary repairs or seek expert help. See “The Chimney

Inspection Chart”

Figure 9.

Measure inside area of tile--liner and

exact height of chimney from the top of the chimney to the highest

appliance flue collar or drafthood outlet.

Connector Type

To reduce flue gas heat loss and the chance of condensate

problems, the vent connector

must

be double--wall Type B vent.

Venting Restrictions for Chimney Types

Interior Chimney --

has no sides exposed to the outdoors below

the roofline. Venting is permitted into an interior masonry chimney

in accordance with Table 13.8 and section 13.2 of the National Fuel

Gas Code ANSI Z223.1/NFPA 54--2006, if the furnace is

common--vented with at least one draft hood--equipped water

heater or furnace.
These furnaces are NOT permitted to be vented into interior

masonry chimneys singly (not common--vented with a draft

hood--equipped water heater or furnace).

Exterior Chimney --

has one or more sides exposed to the

outdoors below the roof line. All installations with a 99% Winter

Design Temperature* below 17

°

F (--8

°

C) must be common vented

only with a draft hood equipped Category I appliance.

*

The 99.6% Winter Design Dry--Bulb (db) temperatures are

found in the 1997 or 2001 ASHRAE Climatic Design

Information chapter, Table 1A (United States) and 2B

(Canada), or the 2005 ASHRAE Fundamentals Handbook,

Climatic Design Information chapter, and the CD--ROM

included with the 2005 ASHRAE Fundamentals Handbook.

Chimneys shall conform to the Standard for Chimneys, Fireplaces,

Vents, and Solid Fuel Burning Appliances ANSI/NFPA 211--2006

and must be in good condition.
Refer to Sections 13.1.9 or 13.2.20 of the NFGC or the authority

having jurisdiction to determine whether relining is required.
If relining is required, use a properly sized listed metal liner or

Type--B vent to reline the chimney.
Inspections before the sale and at the time of installation will

determine the acceptability of the chimney or the need for repair

and/or (re)lining. Refer to the Chimney Inspection Chart to perform

a chimney inspection.
If the inspection of a previously used tile--lined chimney:

a. Shows signs of vent gas condensation, the chimney should

be relined in accordance with local codes and the authority

having jurisdiction. The chimney should be relined with a

listed metal liner or Type--B vent to reduce condensation. If a

condensate drain is required by local code, refer to the

NFGC, Section 12.1 for additional information on

condensate drains.

b. Indicates the chimney exceeds the maximum permissible

size in the tables, the chimney should be rebuilt or relined to

conform to the requirements of the appliances being installed

and the authority having jurisdiction.

A chimney without a clay tile liner, which is otherwise in good

condition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined

with a UL listed metal liner or UL listed Type--B vent. Relining with a

listed metal liner or Type--B vent is considered to be a

vent--in--a--chase.

If a metal liner or Type--B vent is used to line a chimney, no other

appliance shall be vented into the annular space between the

chimney and the metal liner.

APPLIANCE APPLICATION REQUIREMENTS

Appliance operation has a significant impact on the performance of

the venting system. If the appliances are sized, installed, adjusted,

and operated properly, the venting system and/or the appliances

should not suffer from condensation and corrosion. The venting

system and all appliances shall be installed in accordance with

applicable listings, standards, and codes.

The furnace should be sized to provide 100 percent of the design

heating load requirement plus any margin that occurs because of

furnace model size capacity increments. Heating load estimates

can be made using approved methods available from Air

Conditioning Contractors of America (Manual J); American Society

of Heating, Refrigerating, and Air--Conditioning Engineers; or other

approved engineering methods. Excessive oversizing of the

furnace could cause the furnace and/or vent to fail prematurely.

When a metal vent or metal liner is used, the vent or liner must be in

good condition and be installed in accordance with the vent or liner

manufacturer’s instructions.

To prevent condensation in the furnace and vent system, the

following precautions must be observed:
1. This furnace is designed for minimum continuous return--air

temperature of 60

°

F (155

°

C) db or intermittent operation down

to 55

°

F (13

°

C) db such as when used with a night setback

thermostat.

2. Adjust the gas input rate per the installation instructions. Low

gas input rate causes low vent gas temperatures, causing

condensation and corrosion in the furnace and/or venting

system. Derating is permitted only for altitudes above 2000

(610 m).

3. Adjust the air temperature rise to the midpoint of the rise range

or slightly above. Low air temperature rise can cause low vent

gas temperature and potential for condensation problems.

4. Set the thermostat heat anticipator or cycle rate to reduce short

cycling.

Air for combustion must not be contaminated by halogen

compounds, which include chlorides, fluorides, bromides, and

iodides.

These compounds are found in many common home products such

as detergent, paint, glue, aerosol spray, bleach, cleaning solvent,

salt, and air freshener, and can cause corrosion of furnaces and

vents. Avoid using such products in the combustion--air supply.

Furnace use during construction of the building could cause the

furnace to be exposed to halogen compounds, causing premature

failure of the furnace or venting system due to corrosion.

Vent dampers on any appliance connected to the common vent can

cause condensation and corrosion in the venting system. Do not

use vent dampers on appliances common vented with this furnace.

Summary of Contents for H8UH5050B12C2

Page 1: ...fy unsafe practices that may result in minor personal injury or product and property damage Note is used to highlight suggestions that will result in enhanced installation reliability or operation Ins...

Page 2: ...setting ____ Fan Time OFF Setting ___ Manual Gas Shut Off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Calculated Firing Rate See Checks and Adjus...

Page 3: ...air shall also be handled by a duct s sealed to the furnace casing and terminating outside the space containing the furnace A gas fired furnace for installation in a residential garage must be instal...

Page 4: ...ne fluorine or any other damaging chemicals which could harm the furnace and vent system and permit spillage of combustion products into an occupied space Refer to Combustion Ventilation Air section C...

Page 5: ...16 49 183 4 476 J Installation Positions This furnace can be installed in an upflow horizontal either left or right airflow position DO NOT install this furnace on its back For the upflow position the...

Page 6: ...e with sheet metal screws and to the rafters or joists with bolts The preferred method is to use an angle iron frame bolted to the rafters or joists If the furnace is to be installed at ground level i...

Page 7: ...installation is complete check that all appliances have adequate combustion air and are venting properly See Venting And Combustion Air Check in Gas Vent Installation Section in this manual Contamina...

Page 8: ...ow and b Outdoor openings located as required in the Outdoor Combustion Air Method above and c Outdoor openings sized as follows 1 Calculate the Ratio of all Indoor Space volume divided by required vo...

Page 9: ...lowing equations from the National Fuel Gas Code ANSI Z223 1 NFPA 54 2006 9 3 2 2 1 For other than fan assisted appliances such as a draft hood equipped water heater 1000 Btu hr 21 ft3 I other Volume...

Page 10: ...ry built chimney or vent complying with a recognized standard or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction Venting into an unlined maso...

Page 11: ...permitted as outlined in the NFGC venting tables Follow all safe venting requirements Note See section Masonry Chimney Venting 6 Horizontal Venting Category I Furnaces With External Power Venters In...

Page 12: ...w vent terminal of the furnace to a dryer or water heater vent or other appliance s direct vent intake or exhaust N Clearance from a plumbing vent stack 3 91 cm 3 91 cm O Clearance above a paved sidew...

Page 13: ...formation on condensate drains b Indicates the chimney exceeds the maximum permissible size in the tables the chimney should be rebuilt or relined to conform to the requirements of the appliances bein...

Page 14: ...anufacturer s installation instructions CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code NFPA 54 ANSI Z223 1 2006 and ANSI NFPA 211 2006 Chimneys Fire places Ve...

Page 15: ...ring disconnected 4 Remove the four 4 screws holding the manifold and gas valve to the manifold supports Do Not discard any screws 5 Carefully remove the manifold assembly 6 Remove the Natural gas bra...

Page 16: ...ing and Adding Propane Low Pressure Switch Propane Low Pressure Switch Detail Alterative installation Figure 13 Right pipe entry O N O F F 25 25 51 Left Hand gas pipe entry detail 25 25 53 Drip Leg Un...

Page 17: ...may vary in appearance 4 Gas supply line then can be run directly into opening of elbow Piping with Close Nipples and Standard Elbows 1 Assemble elbows and nipples similar to street elbows shown in Fi...

Page 18: ...pacity can be determined by using the NEC or CEC Furnace must be installed so the electrical components are protected from water and connected to its own separate circuit Junction Box J Box Relocation...

Page 19: ...arning could result in personal injury or death Do NOT draw return air from inside a closet or utility room where furnace is located Return air duct MUST be sealed to furnace casing FIRE HAZARD Failur...

Page 20: ...ening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sa...

Page 21: ...cated from sheet metal Figure 24 Insert filter into side clips first and push filter back until it is fully engaged into back clip Figure 23 Bottom Mounted Filter 25 24 18 1 9 23 cm Center clip side t...

Page 22: ...his furnace it must be installed on the discharge side of the furnace to avoid condensation in the heat exchanger All furnaces are designed with a break away duct flange on the supply air side of the...

Page 23: ...ain burner orifices Refer to Table 5 Table 6 Table 7 or Table 8 for correct orifice size and manifold pressure for a given heating value and specific gravity for natural and propane gas Operation Abov...

Page 24: ...ATION FEET ABOVE SEA LEVEL 0 to 2000 2001 to 3000 3001 to 4000 4001 to 5000 5001 to 6000 6001 to 7000 7001 to 8000 2500 10 0 10 0 9 0 10 0 9 4 8 5 10 0 Orifice Size 54 54 54 55 55 55 56 Conversion 1 i...

Page 25: ...nt door exposing the burner compartment 2 Disconnect gas line from gas valve so manifold can be removed 3 Disconnect wiring at gas valve Be sure to note the proper location of all electrical wiring be...

Page 26: ...eed Chart Wire Color Motor Speed Black High Orange Med High Blue Med Low Red Low Med High speed may not be provided on all models 2 Change the heat or cool blower motor speed by removing the motor spe...

Page 27: ...s warning could result in personal injury death and or property damage It is recommended that the furnace be inspected and serviced on an annual basis before the heating season by a qualified service...

Page 28: ...s from furnace control Fan demands from furnace control for heat cool or G will override hard wired speed tap NOTE 3 EAC is NOT active for hard wired mode but IS active for fan demands from furnace co...

Page 29: ...32 OFF 24VAC or 220VAC is off fuse is open Heartbeat Normal operation or no previous Diagnostic Code ON SOLID Soft Lockout Furnace Control Error 1 hr delay If code repeats immediately following power...

Page 30: ...2 H8UH5100F14C2 H8UH5125J20C2 H8UH5140J20C2 MUF050W3C2 MUF075W3C2 MUF100W3C2 MUF125W5C2 MUF140W5C2 HL12H3TRC2 HL18H3TRC2 HL25H3TRC2 HL31H4TRC2 HL34H5TRC2 Save This Manual For Future Reference Internat...

Page 31: ...e Series Hot Surface Combustion Flue Outlet Size Inches 4 4 4 4 4 Limits Controls Thermal Sensor F Limit Control 300 See Parts List 300 See Parts List 300 See Parts List 300 See Parts List 300 See Par...

Page 32: ...7 587 224 1 236 293 392 552 249 0 204 266 362 523 NOTE 1 Data based on Bottom Only return 2 Data based on Both Sides or Bottom Plus One Side 3 Reduce Airflow by 5 if Bottom ONLY return 4 Gray area is...

Page 33: ...Bottom Only return 2 Data based on Both Sides or Bottom Plus One Side 3 Reduce Airflow by 5 if Bottom ONLY return 4 Gray area is above maximum temperature rise range Filter Size CFM L S 14 X 25 1400...

Page 34: ...34 441 01 5003 01 Specifications are subject to change without notice Wiring Diagram H8UH5 MUF HL...

Page 35: ...to change without notice Parts for H8UH5 MUF HL 25 23 49a 1 S 14 15 W 10 U V 16 L 16 17 N 5 4 3 9 B C A 2 1 BB AA 18 Y X CC M D T S P Z F E G F U 12 11 7 D GG FF EE HH 8 7 J 13 19 Representative draw...

Page 36: ...8 Furnace Control 1172550 1 1 1 1 1 9 Switch Interlock 1171981 1 1 1 1 1 10 Burner Assembly 1172884 1172965 1172966 1172967 1172968 1 1 1 1 1 11 Flame Sensor 1172827 1 1 1 1 1 12 Ignitor 1172533 1 1 1...

Page 37: ...Cover Junction box 1012350 1 1 1 1 1 D Partition Blower 1014009 1014010 1014011 1014013 1 1 1 1 1 E Housing Blower 1172885 1172969 1172970 1 1 1 1 1 F Hanger Blower 1012328 2 2 2 2 2 G Panel Blower C...

Page 38: ...0 1 1 1 1 1 Z Gasket Combustion Blower 1014385 1 1 1 1 1 AA Partition Front Ht Exchanger 1013543 1013521 1013546 1013548 1013549 1 1 1 1 1 BB Gaskets Heat Exchanger 1013991 1013992 1013993 1013994 101...

Reviews: