background image

INSTALLATION INSTRUCTIONS

3-phase R-410A Split System Heat Pump

506 01 5102 00

11

DEFROST SYSTEM

A. DEFROST THERMOSTAT

The defrost thermostat is factory installed on a short tube
stub extending from the coil end plate. Refer to Figure 12
and confirm that the thermostat is securely fastened in
place on the tube stub.

Figure 12

Defrost Thermostat

FEEDER TUBE

TUBE STUB

DEFROST
THERMOSTAT

COIL

B. DEFROST CONTROL BOARD

The defrost board is a time/temperature control which
includes a field-selectable time period between defrost
cycles of 30, 60, or 90 minutes (quick-connects located
at board edge, factory set at 90 minutes).

Defrost mode is identical to cooling mode except that
outdoor-fan motor stops and second-stage heat is
turned on to continue warming conditioned space.

Initially, the defrost cycle timer starts when the contactor
is energized and a 24 VAC signal is present on the T1
terminal. Then the defrost cycle begins when the defrost
thermostat is closed and the cycle timer times out (30, 60,
90 or minutes).

To initiate a forced defrost cycle, the defrost thermostat
must be closed. This can be accomplished as follows:

1.

Turn off power to outdoor unit.

2.

Disconnect outdoor fan-motor lead from OF2 on
control board (refer to Figure 13). Tape lead to
prevent grounding.

3.

Restart unit in heating mode, allowing frost to
accumulate on outdoor coil.

4.

After a few minutes in heating mode, liquid line
temperature should drop below closing point of
defrost thermostat (approximately 32 

°

F).

5.

Short between speed-up terminals with a
flat-bladed screwdriver (refer to Figure 13). This
reduces the timing sequence to 7, 14, or 21
seconds (30, 60, or 90 minute defrost selection,
respectively).

6.

When you hear reversing valve change position,
remove screwdriver immediately; otherwise,
control will terminate normal 10-minute defrost
cycle in approximately 2 seconds.

NOTE:

 Length of defrost cycle is dependent upon length

of time it takes to remove screwdriver from test pins after
reversing valve has shifted.

7.

Unit will remain in defrost for remainder of
defrost-cycle time or until defrost thermostat
reopens at approximately 65 

°

F coil temperature of

liquid line.

8.

Turn off power to outdoor unit and reconnect
fan-motor lead to OF2 on control board (refer to
Figure 13).

Figure 13

Defrost Control Board

R8

OF1

K1

O1

R21

C2

R6

H9C1

C         US

®

R14

R13

D13

R7

C4

C10

JW2

JW1

D3

C16

C7

R28

D6

JW3

C13

R4

R1

R2

R3

R1

1

R5

R26

D1

D2

D10

A29

R9

D4

C19

C9

C1

OF2

CEBD430524-01A

 5501A

P2

1

Y

T1 C C  O

DFT

SPEEDUP

P1
1

J1

1

P3

1

J2

30 60 90

W1

R20

1

HK32EA001

C17

U1

1

U3

O
R

W

2

Y
C

Summary of Contents for H4H3 Series

Page 1: ...rd CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Lab...

Page 2: ...oom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit away fro...

Page 3: ...lit System Heat Pump 506 01 5102 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service...

Page 4: ...on is not recommended on wood frame structures where low noise levels are required Supporting structure or platform for the unit must be level If installation is on a flat roof locate unit minimum 6 i...

Page 5: ...refer to the Long Line Application Guideline document for additional instructions NOTE Line set actual length must not exceed 200 feet NOTE A crankcase heater must be used when the refrigerant line le...

Page 6: ...d periods of unit shut down caus ing refrigerant slugging and possible compressor damage at start up If ANY section of the line set is buried under ground provide a minimum 6 vertical rise at the serv...

Page 7: ...e set tube ends with emery cloth or steel brush Remove any grit or debris Insert line set tube ends into service valve tube stubs Apply heat absorbing paste or heat sink product between service valve...

Page 8: ...TEM IF IT HOLDS DEEP VACUUM EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHARGE SYSTEM BREAK VACUUM WITH DRY NITROGEN EVACUATE WAIT I OPENING SERVICE VALVES Outdoor units are shipped with a r...

Page 9: ...two power wires to Contactor and one power wire to Blue lead wire use wire nut Connect ground wire to Ground Lug Refer to Wiring Diagram on unit and Figure 9 Figure 9 208 230 V and 460 V Electrical Su...

Page 10: ...INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE...

Page 11: ...tdoor fan motor lead from OF2 on control board refer to Figure 13 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in he...

Page 12: ...indoor temperature is between 70_ and 80_F S line set is less that 80 feet 1 Operate unit a minimum of 15 minutes before checking charge NOTE If outdoor unit has a 2 speed fan motor motor will operat...

Page 13: ...s indoor unit blower relay starting indoor blower motor When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipp...

Page 14: ...Stage Compressor Signal First Stage Compressor Signal 24 VAC for Thermostat Indicator 24 Volt Power 24 Volt Common 24 Volt Compressor Protection Function DC Compressor Solenoid ALERT LED TRIP LED DC...

Page 15: ...restriction 2 If high pressure switch present go to Flash Code 2 information 3 Intermittent thermostat demand signal 4 System or control board defective Yellow ALERT Flash Code 4 Locked Rotor LOCKOUT...

Page 16: ...nd signal is present If not R and C are reversed wired Verify voltage at contactor coil falls below 0 5VAC when off Review R 410A QUICK REFERENCE GUIDE R 410A refrigerant operates at 50 70 higher pres...

Reviews: