background image

INSTALLATION INSTRUCTIONS

3-phase R-410A Split System Heat Pump

6

506 01 5102 00

transmission between the tubing and the foundation or
wall.

Along floor or ceiling joists, suspend refrigerant lines so
that they do not contact the building structure, water

pipes, or ductwork. Use insulated or suspension type
hangers. Metal straps must be at least 1” wide to avoid
cutting into the tube insulation. Keep the liquid and
suction lines separate. Refer to Figure 4.

Figure 4

Routing and Suspending Refrigerant Lines

INSULATION

SUCTION TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

SUCTION TUBE

INSULATION

CAULK

HANGER STRAP

(AROUND SUCTION

TUBE ONLY)

JOIST

1” MIN

THROUGH THE WALL

SUSPENSION

!

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in improp‐
er product operation.

Do not bury more than 36” of line set underground.
Refrigerant may migrate to cooler buried section
during extended periods of unit shut-down, caus‐
ing refrigerant slugging and possible compressor
damage at start-up.
If ANY section of the line set is buried under‐
ground, provide a minimum 6” vertical rise at the
service valve.

D. OUTDOOR UNIT HIGHER THAN INDOOR UNIT

Proper oil return to the compressor should be maintained
with suction gas velocity. If velocities drop below 1500
fpm (feet per minute), oil return will be decreased. To
maintain suction gas velocity, do not upsize vertical
suction risers.

NOTE:

 If there is more than 20 feet vertical separation

between outdoor and indoor units, refer to the Long Line
Application Guidline document for additional instructions.

E. LIQUID LINE FILTER-DRIER

Outdoor units are shipped with an appropriate filter-drier
for installation in the liquid line. Leave the plugs in the tube
ends until the filter-drier is installed. The optimal location
for the filter-drier is close to the indoor coil. Heat pump
filter-driers are “bi-flow” type. Either end can be pointed
towards indoor coil. Refer to Figure 5.

Figure 5

Liquid Line Filter-Drier

Installed at Indoor Coil

38-11-84

Filter-Drier

Summary of Contents for H4H3 Series

Page 1: ...rd CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Lab...

Page 2: ...oom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit away fro...

Page 3: ...lit System Heat Pump 506 01 5102 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service...

Page 4: ...on is not recommended on wood frame structures where low noise levels are required Supporting structure or platform for the unit must be level If installation is on a flat roof locate unit minimum 6 i...

Page 5: ...refer to the Long Line Application Guideline document for additional instructions NOTE Line set actual length must not exceed 200 feet NOTE A crankcase heater must be used when the refrigerant line le...

Page 6: ...d periods of unit shut down caus ing refrigerant slugging and possible compressor damage at start up If ANY section of the line set is buried under ground provide a minimum 6 vertical rise at the serv...

Page 7: ...e set tube ends with emery cloth or steel brush Remove any grit or debris Insert line set tube ends into service valve tube stubs Apply heat absorbing paste or heat sink product between service valve...

Page 8: ...TEM IF IT HOLDS DEEP VACUUM EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHARGE SYSTEM BREAK VACUUM WITH DRY NITROGEN EVACUATE WAIT I OPENING SERVICE VALVES Outdoor units are shipped with a r...

Page 9: ...two power wires to Contactor and one power wire to Blue lead wire use wire nut Connect ground wire to Ground Lug Refer to Wiring Diagram on unit and Figure 9 Figure 9 208 230 V and 460 V Electrical Su...

Page 10: ...INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE...

Page 11: ...tdoor fan motor lead from OF2 on control board refer to Figure 13 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in he...

Page 12: ...indoor temperature is between 70_ and 80_F S line set is less that 80 feet 1 Operate unit a minimum of 15 minutes before checking charge NOTE If outdoor unit has a 2 speed fan motor motor will operat...

Page 13: ...s indoor unit blower relay starting indoor blower motor When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipp...

Page 14: ...Stage Compressor Signal First Stage Compressor Signal 24 VAC for Thermostat Indicator 24 Volt Power 24 Volt Common 24 Volt Compressor Protection Function DC Compressor Solenoid ALERT LED TRIP LED DC...

Page 15: ...restriction 2 If high pressure switch present go to Flash Code 2 information 3 Intermittent thermostat demand signal 4 System or control board defective Yellow ALERT Flash Code 4 Locked Rotor LOCKOUT...

Page 16: ...nd signal is present If not R and C are reversed wired Verify voltage at contactor coil falls below 0 5VAC when off Review R 410A QUICK REFERENCE GUIDE R 410A refrigerant operates at 50 70 higher pres...

Reviews: