INSTALLATION INSTRUCTIONS

R-22 Split System Heat Pump

8

428 01 5001 00

!

CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product
damage.

Braze with Sil-Fos or Phos-copper alloy on cop‐
per-to-copper joints and wrap a wet cloth around
rear of fitting to prevent damage to TXV.

I. EVACUATING LINE SET AND INDOOR COIL

The unit is shipped with a factory refrigerant charge. The
liquid line and suction line service valves have been
closed after final testing at the factory. Do not disturb
these valves until the line set and indoor coil have been
evacuated and leak checked, or the charge in the unit
may be lost.

NOTE:

 Do not use any portion of the factory charge for

purging or leak testing. The factory charge is for filling the
system only after a complete evacuation and leak check
has been performed.

!

CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product
damage.

Never use the outdoor unit compressor as a vacu‐
um pump. Doing so may damage the compressor.

Line set and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. If
deep vacuum equipment is not available, the alternate
triple evacuation method may be used by following the
specified procedure.

If vacuum must be interrupted during the evacuation
procedure, always break vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump
capable of pulling a vacuum to 500 microns and a vacuum
gauge capable of accurately measuring this vacuum
level. The deep vacuum method is the most positive way
of assuring a system is free of air and water.

Watch the vacuum gauge as the system is pulling down.
The response of the gauge is an indicator of the condition
of the system (refer to Figure 7).

With no leaks in the system, allow the vacuum pump to
run for 30 minutes minimum at the deep vacuum level.

Figure 7

Deep Vacuum Gauge Response

and System Conditions

500

MINUTES

0

1

2

4

6

1000

1500

LEAK IN
SYSTEM

VACUUM TIGHT
TOO WET

TIGHT
DRY SYSTEM

2000

M

ICRONS

2500

3000

3500

4000

4500

5000

3

7

5

Triple Evacuation Method

The triple evacuation method should only be used when
system does not contain any water in liquid form and
vacuum pump is only capable of pulling down to 28 inches
of mercury. Refer to Fig. 8 and proceed is as follows:

1.

Pull system down to 28 inches of mercury and
allow pump to continue operating for an additional
15 minutes.

2.

Close manifold valves or valve at vacuum pump
and shut off vacuum pump.

3.

Connect a nitrogen cylinder and regulator to
system and fill with nitrogen until system pressure
is 2 psig.

4.

Close nitrogen valve and allow system to stand for
1 hour. During this time, dry nitrogen will diffuse
throughout the system absorbing moisture.

5.

Repeat this procedure as indicated in Figure 8.

6.

After the final evacuate sequence, confirm there
are no leaks in the system. If a leak is found, repeat
the entire process after repair is made.

Figure 8

Triple Evacuation Sequence

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHARGE SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

Summary of Contents for C2H3

Page 1: ...ing manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product l...

Page 2: ...so that water runoff will not enter the unit Locate unit away from areas where heat lint or exhaust fumes will be discharged onto unit as from dryer vents Locate unit away from recessed or confined a...

Page 3: ...ystem Heat Pump 428 01 5001 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service 24 S...

Page 4: ...rm for the unit must be level If installation is on a flat roof locate unit minimum 6 inches above roof level Place the unit over one or more load bearing walls If there are several units mount them o...

Page 5: ...Specifications and Long Line Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet NOTE A crankcase heater must be used when the refrigerant line length exceed...

Page 6: ...efrigerant Lines INSULATION SUCTION TUBE LIQUID TUBE OUTDOOR WALL INDOOR WALL LIQUID TUBE SUCTION TUBE INSULATION CAULK HANGER STRAP AROUND SUCTION TUBE ONLY JOIST 1 MIN THROUGH THE WALL SUSPENSION CA...

Page 7: ...ice valve 2 Check that piston size stamped on side of piston matches with number listed on unit rating plate Return piston to piston body of liquid service valve either direction Return retainer to pi...

Page 8: ...e capable of accurately measuring this vacuum level The deep vacuum method is the most positive way of assuring a system is free of air and water Watch the vacuum gauge as the system is pulling down T...

Page 9: ...main remote electrical disconnect device There may be more than one disconnect device Supply voltage must be 208 230 volts 197 volt minimum to 253 volts maximum 60 Hz single phase Outdoor units are ap...

Page 10: ...LLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE THERM...

Page 11: ...fan motor lead from OF2 on control board refer to Figure 12 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in heating...

Page 12: ...will default to high speed fan for servicing Reconnect wire after servicing 2 Measure liquid service valve pressure by attaching an accurate gauge to service port 3 Measure liquid line temperature by...

Page 13: ...OUBLESHOOTING Some models are factory equipped with the Comfort Alertt Diagnostics device in the control box refer to Figure 14 Comfort Alert provides around the clock monitoring for common electrical...

Page 14: ...tch present go to Flash Code 1 information Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refri...