background image

User’s Information Manual

5

441 02 2011 00

B.

Match goes out or flame wavers away from draft hood.

This

indicates spillage and that appliance is not getting enough air

for combustion.

CARBON MONOXIDE POISONING HAZARD.
Carbon monoxide poisoning could result in death

from asphyxiation or serious personal injury.
Draft hood spillage means there is not enough air

for proper combustion and carbon monoxide may

be present.
Keep a window open (a minimum of 2

²²²²

) near the

appliance until a permanent combustion air duct is

installed. Contact a qualified service agency.

!

WARNING

If draft hood spillage is indicated:

1. Check for plugged vent connectors and chimneys. Repair

stoppage and test again.

2. If you have a fireplace, open a window or door near the fire-

place and then check for spillage.
If spillage stops, do not use the fireplace until you can supply

fresh air by a permanent duct.

3. If you have kitchen and bathroom exhaust fans, turn them

OFF

and check for spillage.

If spillage stops, do not use exhaust fans until you can supply

fresh air by a permanent duct. Circuit breakers for fans

should be turned off and marked as to why they are off.

4. Spillage means air starvation and that an outdoor air duct or

air intake must be installed to provide air directly to the area

around the furnace. This duct or intake MUST comply with lo-

cal and state building codes or in their absence with the Na-

tional Fuel Gas Code NFPA 54/ANSI Z223.1--2002 in the

U.S., or the National Standard of Canada, Natural Gas and

Propane Installation Code CSA B--149.1--00 in Canada.

Indoor Humidity (Your Comfort)

Relative humidity is important to your health. Proper humidification

helps cut down incidences of respiratory illness. Air that is too wet

may damage the building structure. Air that is too dry is uncomfort-

able. A quick way to test for proper humidity is as follows:

1. Look for frequent fogging or excessive condensation on the

inside of windows. This indicates the indoor humidity level is

too high for outdoor weather conditions.

2. Drop three ice cubes into a glass of water and stir. If, within

three minutes, moisture does not form on the glass, the air is

too dry and a humidifier would be beneficial. (Do not perform

this test in the kitchen, cooking vapors may produce inaccu-

rate results.)

A good relative humidity is one just high enough to barely start con-

densation along the lower edges or lower corners of the windows,

when it is cold outside. More than that can be damaging.

If the humidity is too high, try these suggestions to lower the humid-

ity:

1. Reduce setting or discontinue use of humidifier.
2. Use range and bathroom exhaust fans while cooking and

bathing. Open a door or window for a few minutes to bring in

cool drier air.

3. Cook with pans covered.
4. Take shorter baths or showers with cooler water.

5. Install a fresh air intake duct. Cold, dry air brought in from out-

side to the furnace area lowers the indoor humidity level.

6. Have appliances checked. A malfunctioning appliance can

contribute water vapor to the structure.

7. If the problem continues, consult a heating contractor about

adding a heat recovery ventilator or air--to--air heat exchang-

er.

About Your Furnace

Figure 3

or

Figure 4

shows the location of the components in the

furnace.

Circulating Air Blower

The blower circulates room air through the furnace, air ducts, and

into the rooms of the structure. The blower can be set at the thermo-

stat for automatic or manual operation. In manual mode the blower

operates continuously. In automatic, the blower does not come on

until a preset time after the gas valve is energized. When the struc-

ture reaches the temperature set on the thermostat, the furnace will

shut off. The blower will continue to run until the furnace cools down.

Thermostat

There are many types and styles of thermostats. Most thermostats

control both heating and cooling functions and have a Fan Switch

with

AUTO

and

ON

settings. On

AUTO

, the Circulating Air Blower

will cycle on/off with the furnace on the heating speed unless a call

for cooling is initiated. Blower speed will correspond to the mode of

operation of the furnace. If the Fan Switch is positioned to

ON

the

blower will run continuously.

In addition some thermostats are programmable with multiple set

backs. The set backs can be pre--programmed to lower or raise the

temperature automatically.

Be sure to become familiar with your thermostat.

Rating Plate

The rating plate contains important information for the service tech-

nician and lists the complete model, manufacturing and serial num-

bers. You should always provide all these numbers when

requesting parts or if you need service. See

Figure 3, Figure 4

or

Figure 5

for rating plate location.

Door Interlock Switch

All the electrical power for the furnace goes through the door inter-

lock switch. The interlock switch interrupts electrical power to the

furnace when the blower door is removed. The furnace will not oper-

ate until the blower door is reinstalled.

Furnace Control

The furnace control provides power to the circulating air blower to

keep it on until the furnace cools down.

The fan off--delay setting can be adjusted if the fan remains on long

enough that cool drafts are felt in the room after the furnace shuts

off.

The off--delay is set by moving a set of switches (2--stage) or jumper

(1--stage) on the control. The Wiring Diagram located on the inside

of the blower door shows the various delay combinations. Refer to

Figure 3

or

Figure 4

for location of the control.

If you are unsure how to set the Off--delay Control, contact a Quali-

fied Service Agency.

Summary of Contents for *8MPN/L

Page 1: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or...

Page 2: ...nal injury or product or property damage NOTE is used to highlight suggestions which will result in en hanced installation reliability or operation Signal Words in Manuals The signal word WARNING is u...

Page 3: ...d safe operation of the furnace for com bustion and ventilation of flue gases See the Combustion Air Your Safety section of this manual 5 Familiarize yourself with the possible air starvation sig nals...

Page 4: ...for ventilation and or combustion WARNING New materials and methods are being used in construction and re modeling which resultin lowerenergy costs forheating and cooling It may also mean your applia...

Page 5: ...ow for a few minutes to bring in cool drier air 3 Cook with pans covered 4 Take shorter baths or showers with cooler water 5 Install a fresh airintake duct Cold dry air broughtin fromout side to the f...

Page 6: ...e Panel on Some Models Diagnostic Light Ignitor Flame Sensor not shown 25 24 78 1 Pressure Switch Some models have one Component Locations for 80 Furnaces 4 Position Figure 4 25 24 79 1 Heat Exchanger...

Page 7: ...if equipped with a System Select Switch 2 Turn OFF all electric power to the furnace at the disconnect switch or circuit breaker 3 Remove the burner compartment door by removing the two 2 screws secur...

Page 8: ...3 1 Disconnectthe 1 2 I D rubberhose fromthe vent drain fitting ortee thatis locateddownstreamofthe combustionblower Insert a funnel into the hose and pour four 4 ounces of sani tary type RV antifree...

Page 9: ...sized for the furnace s airflow rate Replacement filters must be of equivalent type size and rating except as described below Disposable low velocity filters may be used to replace washable high velo...

Page 10: ...u See Figure 8 4 Inspect the filter s and replace or clean washable types If filter is aluminum mesh it should be recoated with filter coating spray 5 Replace blower door 6 Turn on electric power to f...

Page 11: ...nal components such as exterior panels refractory combustion chambers oil nozzles refrigerant refrigerant inspection and refrigerant reclaiming freight and or handling charges associated with any repa...

Page 12: ...or 20 years from the date of original installation ADDITIONAL TERMS FOR OIL FURNACE APPLICATIONS ONLY 1 OIL BURNERS A replacement for 5 years from date of original installation for Oil Burner Parts 2...

Reviews: