SPECIAL INSTRUCTIONS

Battery Replacement

The 8 yr. lithium battery is located on

the back of the circuit board under the metal battery terminal
clips. Replace with Panasonic or Rayovac BR2325 (or equivalent).

Re-installing Logic Module 

Carefully plug the 10 wire cable

straight into the connector on the rear of the logic module. The
sawtooth shape on both connectors must line up to allow the cable
connector to be seated. Engage the cut-aways on the right side of
the logic module with the guides in the plastic terminal block and
snap the left hand side in place. It may be necessary to use a small
screwdriver to push the left hand retaining tab slightly to the left
to allow the module to snap in place.

Removing Power Module
(required to change input
voltage or to access rear
power input terminals on 24
volt model) 

Remove the logic

module. Remove the (3) screws that
secure the power module to the
enclosure. Use the logic board
retaining tab to lift the power
module out of the enclosure.

27

Next Generation 

Ground Wire
Connect To Case
Ground Below

Power Module 
Installed In 
Enclosure

POWER MODULE

(front view)

SPECIAL INSTRUCTIONS

Enclosure Mounting

The top mounting hole on the enclosure

bracket is slotted; it is not necessary to remove the power module
unless you want to change the input voltage. If the change is
required to meet your available voltage, remove the power module
before mounting the enclosure. Mount the enclosure with #8 or
10 pan head or #6 or 8 hex head screws. The cover can be
removed by lifting upward off hinges for convenience in
installation.

WARNING:

Disconnect all power at the service panel before

removing the logic module. 

Removing Logic Module

(required for wiring). Pull the

retaining tab to the left and lift logic module away on the left side.

STOP:

Disconnect cable from rear of logic module by pulling

straight back on the cable.

Opening the Logic Module

To remove the metal logic module
cover, remove the screws on the
back and lift off, exposing the circuit
board. Reverse steps to replace cover.
The following three procedures
require cover removal.

Converting to 24 Hour
Display Mode

The time switch is

shipped with 12 hr. 

AM/PM

timekeeping; 24 hr. is available by
removing the jumper from the pin
connector on the circuit board. The jumper(s) may be stored for
later use by reinstalling on the outer pins only.

Daylight Saving Time Override 

Override the automatic

DST adjustment (in Arizona, Hawaii and parts of Indiana) by
removing the jumper on the circuit board.

26

Pull

Swing Up

SUN

1

MON

2

TUE

3

WED

4

THU

5

FRI

6

SAT

7

WK

DY

8

WK

ND

9

ALL

0

AM

PM

PULSE

INTVL

ASTRO

PROG

REV

SET UP

HLDY

CLEAR

COPY

HELP

OK

ON/OFF

ON/OFF

ON/OFF

ON/OFF

Summary of Contents for ET70415CR

Page 1: ... Zones 24 25 Special Instructions 26 29 Typ Wiring Configurations 30 31 Troubleshooting 32 37 Error Messages 37 38 INSTRUCTIONS Pg CHARTS Pg REFERENCE Pg Next Generation Models ET70415CR ET70415CR24 Vol 4 Installation Date ______________________ Battery Replacement Recommended _______________________ 8 years after installation Intermatic Plaza Spring Grove Illinois 60081 9698 Printed in U S A Copy...

Page 2: ... categories shown on the front panel SET UP and PROGRAM 3 Next Generation INTRODUCTION This easy to program microprocessor based time switch provides flexible 24 hour 7 day or full year load control Its unique self prompting feature simplifies programming by leading you through with flashing prompts The 2 rows of LEDs on the left side flash and indicators in the digital display light while you are...

Page 3: ...SAT 7 WKDY 8 WKND 9 ALL 0 Next Generation SET UP is performed once during installation to set the internal CLOCK ASTRO sunrise sunset times and HOLIDAY references After entering and okaying the ASTRO Zone the timer will display calculated center of time zone times when prompting for sunrise and sunset entries You may OK these enter actual sunrise sunset times or enter offset times for early or lat...

Page 4: ...or pulse duration then press OK Remember INTVL or PULSE override is initiated on demand via the keypad and is not based on a day and time as is normal INTVL or PULSE To initiate an override interval or pulse first set the RUN SET switch to RUN and set the switch for the desired load to Enable then press the ON OFF key for the load you wish to override The green load indicator flashes during the in...

Page 5: ...DST is automatic see Special Instructions for override if DST adjustment is not required such as in Arizona Hawaii and parts of Indiana The clock time will be adjusted by 1 hour on the first Sunday of April and the last Sunday of October at 2 00 A M Due to un expected results it is recommended you do not attempt pro gramming from 12 00 midnight to 2 00 A M on these two days PROG Program and SET UP...

Page 6: ...actors adapted for two wire control The display will show the selected day followed by COPY Now key in the day you wish to copy to and press OK to confirm Select and OK additional copy to days as required Four rules need to be followed when using COPY 1 You cannot copy to a day that has already been programmed 2 You cannot copy from a day which has already been copied to 3 You cannot copy to or fr...

Page 7: ...s below for individual day day group review if any scheduled events need to be cleared 13 Next Generation INSTRUCTIONS FOR REVIEWING REVISING DATA REVIEW PROCEDURE Place the RUN SET switch in the SET position to review You must review Clock info day of week time date Astro and Holiday dates in SET UP mode You must review all load activity Fixed times Astro times Pulse operations Interval operation...

Page 8: ... press the day key SUN 1 through SAT 7 or the day group key wkDY 8 wkND 9 or ALL 0 to select the day or day group to review NOTE If you have entered data as a day group and attempt to review any of the days individually the message End of Review will be displayed This is because you must review data just as it was entered in this example as a day group Press REV at which point the colon will disap...

Page 9: ...ne The time switch now displays the calculated center of time zone sunrise time of 7 33 A M Since the building 17 Next Generation review You must revise the data by reviewing the appropriate individual day day group or copied from day During automatic review the OK key must be used to pause the display before the displayed data can be deleted After any program data is cleared review is terminated ...

Page 10: ...R CLEAR deletes automatic center of zone calculation display now shows and 8 0 3 OK selects new offset sunrise time The time switch now displays the calculated center of time zone sunset time of 5 13 P M Since the building owner wants to offset actual sunset time press CLEAR CLEAR CLEAR deletes automatic center of zone calculation display now shows 4 4 3 OK selects new offset sunset time 1 OK sele...

Page 11: ...AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM SWITCHING TIMES Day Day CIRCUITS SWITCH ON SWITCH OFF PULSE INTVL ASTRO Group 1 2 3 4 Override AM PM N O T I M E E N T R Y R E Q U I R E D Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec A...

Page 12: ...Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM NOTE Holidays not prog...

Page 13: ...imate sunrise and sunset times for the center of the time zone will be displayed Depending on your location relative to the center you may want to change offset this time Following are approximate offsets plus or minus for selected cities in 5 minute increments SUNRISE SUNSET Albuquerque 5 5 Atlanta 25 25 Baltimore 5 5 Bangor ME 35 35 Boston 30 30 Chicago 20 20 Cleveland 15 15 Dallas 15 15 Denver ...

Page 14: ...to remove the power module unless you want to change the input voltage If the change is required to meet your available voltage remove the power module before mounting the enclosure Mount the enclosure with 8 or 10 pan head or 6 or 8 hex head screws The cover can be removed by lifting upward off hinges for convenience in installation WARNING Disconnect all power at the service panel before removin...

Page 15: ...O NOT apply voltage to thess connections DO NOT apply voltage to thess connections Use solid or stranded copper wire Use solid or stranded copper wire 16 thru 24 AWG 16 thru 24 AWG 158ET9019 158ET9019 Upper Compartment for Override Wires Insulating Tubing REMOTE OVERRIDE WIRING 28 SPECIAL INSTRUCTIONS Changing Power Input Voltage Multi Volt Model ET70415CR This model can be powered by any industry...

Page 16: ...er powered by same source Signs Open Closed Bell Signal Horn Circuit 1 Circuit 2 24 VAC 60 Hz To Optional Remote Override Switches Equipment Ground Timer Power 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Circuit 3 Circuit 4 Example 2 Loads and timer each powered by different sources and voltages 277 VAC Indoor Lighting AC 24 VAC Thermostat 240 VAC Motor 120 VAC Signal Horn 30 WARNING If timer power supply vo...

Page 17: ...interval duration even if the load was not On before the start of the Off pulse or interval TROUBLESHOOTING Problem Solution s Display Does Make sure flat cable is properly plugged into the Not Light rear of the logic module Refer to Re installing logic module in Special Instructions If connec tor will not install easily check for bent pins On multi volt model make sure the voltage selector jumper...

Page 18: ...ulse features to eliminate if required NOTE ASTRO switching times change daily according to changing Sunrise and Sunset Consider fixed times with this in mind e g a fixed Off intended to end an Astro On would be ignored if sunset moves beyond the fixed Off time The fixed event should be scheduled to occur outside the range of the Astro event or an Astro Pulse should be considered NOTE Override int...

Page 19: ... entry the Switch Off Display On or Switch Off LED does not alternate Doesn t since most Pulse or Interval applications Alternate require only ON or OFF Press OK without a During time entry to alternate the Switch On Off Programming display if required Some All review should be done with only one circuit Switching enabled at a time If more than one is enabled Times Don t only events common to the ...

Page 20: ...icable ERR 0B Override entry not applicable ERR 0C PULSE entry not applicable ERR 0D INTERVAL entry not applicable ERR 0E Invalid or incomplete entry ERR 0F Unrecognized key or too many keys pressed ERR 1A No AM or PM selection ERR 1B Review entry not applicable ERR 1C One or more of the selected circuits has a program conflict ERR 1D The day of the week entry does not agree with the previously en...

Reviews: