background image

Scheduled PROGRAM is now complete.

Assume

A 30 min. INTERVAL override duration is desired for 
Load

1

.

Set 

Load slide switches to 

Enable 

Load

and 

Disable 2

Press

PROG

(completes programming for Saturday data)

INTVL, 3, 0, OK 

(sets user selectable interval duration 

to 30 minutes)
(Note a day or day group is not selected since Interval 
override is selected on demand by the building occupants.)

Interval override duration

selection is now complete. 

The interval override will not begin until called for by 
the user via the front panel pushbuttons, or by a switch 
connected to the remote override connector.

To complete programming, download all data into non-volatile
memory by sliding the 

SET/RUN

switch to 

RUN

. Note SAVE is

displayed momentarily and the current day of week and time 
appear in the display.

NOTE:

If you need more programming assistance, request form 

#158ET9311, Programming Examples, which contains step-by-  
step instructions for several complex programs.

BATTERY BACKUP

All programmed data is protected by non-volatile memory and can
only be changed or deleted by reprogramming, regardless of power
outage durations. A factory installed 8-year lithium battery backup
maintains accurate time and calendar information. See Special
Instructions for replacement.

owner wants to offset actual sunrise time by having lights 
switch off 30 min. late, press 

CLEAR

CLEAR

CLEAR

(deletes automatic center of zone calculation; display 
now shows --:--) and 

8, 0, 3, OK

(selects new offset 

sunrise time). The time switch now displays the 
calculated center of time zone sunset time of -5:13 P.M. 
Since the building owner wants to offset actual sunset 
time, press 

CLEAR

CLEAR

CLEAR

(deletes automatic

center of zone calculation; display now shows --:--);

4, 4, 3, OK

(selects new offset sunset time);

1, OK

(selects first Holiday schedule Ref. #  for 1997);  

7, 0, 4, 

OK, OK

(pressing 

OK

twice selects same start and stop 

date); 

2, OK 

(selects second Holiday schedule Ref. #);

1, 2, 2, 2, OK

(start date); 

1, 2, 3, 1 OK 

(stop date);

3, OK

(selects first Holiday schedule Ref. # for 1998);

1, 0, 1, OK 

(start date) and

1, 0, 5, OK 

(stop date).

SET UP is now complete.

Press

PROG

(to enter PROGRAM mode and exit SET UP)

Assume

• Programming for two loads: #1 indoor lighting, #2 

buzzer 

• Load

1

switches On 7:50 A.M. to 4:40 P.M. 

Monday thru Friday and 7:50 A.M. to 12:00 P.M. noon
Sat. only. 

• Load

operates the signal twice daily for 15 sec. at 

8:00 A.M. and 4:30 P.M. Monday thru Friday only.

Set

Load slide switches to 

Enable

Load

and 

Disable 2

Press

WKdy/8, OK

(selects weekdays only); 

7, 5, 0, AM, OK

(load On time); 

4, 4, 0, PM, OK

(load Off time)

Set

Load slide switches to 

Disable

Load

and 

Enable 2 

Press

8, 0, 0, AM, PULSE, 1, 5, OK

(selects 15 sec. load On 

at 8:00 A.M.); 

4, 3, 0, PM, PULSE, 1, 5, OK

(selects 15 

sec. load On at 4:30 P.M.)

Press

PROG

to select a new day or day group to program.

Set

Load slide switches to 

Enable 

Load

1

and 

Disable 2

Press

SAT/7, OK 

(selects Saturday only); 

7, 5, 0, AM, OK

(load On time); 

1, 2, 0, 0, PM, OK

(load Off time)

18

19

Next Generation 

Summary of Contents for ET70415CR

Page 1: ... Zones 24 25 Special Instructions 26 29 Typ Wiring Configurations 30 31 Troubleshooting 32 37 Error Messages 37 38 INSTRUCTIONS Pg CHARTS Pg REFERENCE Pg Next Generation Models ET70415CR ET70415CR24 Vol 4 Installation Date ______________________ Battery Replacement Recommended _______________________ 8 years after installation Intermatic Plaza Spring Grove Illinois 60081 9698 Printed in U S A Copy...

Page 2: ... categories shown on the front panel SET UP and PROGRAM 3 Next Generation INTRODUCTION This easy to program microprocessor based time switch provides flexible 24 hour 7 day or full year load control Its unique self prompting feature simplifies programming by leading you through with flashing prompts The 2 rows of LEDs on the left side flash and indicators in the digital display light while you are...

Page 3: ...SAT 7 WKDY 8 WKND 9 ALL 0 Next Generation SET UP is performed once during installation to set the internal CLOCK ASTRO sunrise sunset times and HOLIDAY references After entering and okaying the ASTRO Zone the timer will display calculated center of time zone times when prompting for sunrise and sunset entries You may OK these enter actual sunrise sunset times or enter offset times for early or lat...

Page 4: ...or pulse duration then press OK Remember INTVL or PULSE override is initiated on demand via the keypad and is not based on a day and time as is normal INTVL or PULSE To initiate an override interval or pulse first set the RUN SET switch to RUN and set the switch for the desired load to Enable then press the ON OFF key for the load you wish to override The green load indicator flashes during the in...

Page 5: ...DST is automatic see Special Instructions for override if DST adjustment is not required such as in Arizona Hawaii and parts of Indiana The clock time will be adjusted by 1 hour on the first Sunday of April and the last Sunday of October at 2 00 A M Due to un expected results it is recommended you do not attempt pro gramming from 12 00 midnight to 2 00 A M on these two days PROG Program and SET UP...

Page 6: ...actors adapted for two wire control The display will show the selected day followed by COPY Now key in the day you wish to copy to and press OK to confirm Select and OK additional copy to days as required Four rules need to be followed when using COPY 1 You cannot copy to a day that has already been programmed 2 You cannot copy from a day which has already been copied to 3 You cannot copy to or fr...

Page 7: ...s below for individual day day group review if any scheduled events need to be cleared 13 Next Generation INSTRUCTIONS FOR REVIEWING REVISING DATA REVIEW PROCEDURE Place the RUN SET switch in the SET position to review You must review Clock info day of week time date Astro and Holiday dates in SET UP mode You must review all load activity Fixed times Astro times Pulse operations Interval operation...

Page 8: ... press the day key SUN 1 through SAT 7 or the day group key wkDY 8 wkND 9 or ALL 0 to select the day or day group to review NOTE If you have entered data as a day group and attempt to review any of the days individually the message End of Review will be displayed This is because you must review data just as it was entered in this example as a day group Press REV at which point the colon will disap...

Page 9: ...ne The time switch now displays the calculated center of time zone sunrise time of 7 33 A M Since the building 17 Next Generation review You must revise the data by reviewing the appropriate individual day day group or copied from day During automatic review the OK key must be used to pause the display before the displayed data can be deleted After any program data is cleared review is terminated ...

Page 10: ...R CLEAR deletes automatic center of zone calculation display now shows and 8 0 3 OK selects new offset sunrise time The time switch now displays the calculated center of time zone sunset time of 5 13 P M Since the building owner wants to offset actual sunset time press CLEAR CLEAR CLEAR deletes automatic center of zone calculation display now shows 4 4 3 OK selects new offset sunset time 1 OK sele...

Page 11: ...AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM SWITCHING TIMES Day Day CIRCUITS SWITCH ON SWITCH OFF PULSE INTVL ASTRO Group 1 2 3 4 Override AM PM N O T I M E E N T R Y R E Q U I R E D Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec A...

Page 12: ...Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM NOTE Holidays not prog...

Page 13: ...imate sunrise and sunset times for the center of the time zone will be displayed Depending on your location relative to the center you may want to change offset this time Following are approximate offsets plus or minus for selected cities in 5 minute increments SUNRISE SUNSET Albuquerque 5 5 Atlanta 25 25 Baltimore 5 5 Bangor ME 35 35 Boston 30 30 Chicago 20 20 Cleveland 15 15 Dallas 15 15 Denver ...

Page 14: ...to remove the power module unless you want to change the input voltage If the change is required to meet your available voltage remove the power module before mounting the enclosure Mount the enclosure with 8 or 10 pan head or 6 or 8 hex head screws The cover can be removed by lifting upward off hinges for convenience in installation WARNING Disconnect all power at the service panel before removin...

Page 15: ...O NOT apply voltage to thess connections DO NOT apply voltage to thess connections Use solid or stranded copper wire Use solid or stranded copper wire 16 thru 24 AWG 16 thru 24 AWG 158ET9019 158ET9019 Upper Compartment for Override Wires Insulating Tubing REMOTE OVERRIDE WIRING 28 SPECIAL INSTRUCTIONS Changing Power Input Voltage Multi Volt Model ET70415CR This model can be powered by any industry...

Page 16: ...er powered by same source Signs Open Closed Bell Signal Horn Circuit 1 Circuit 2 24 VAC 60 Hz To Optional Remote Override Switches Equipment Ground Timer Power 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Circuit 3 Circuit 4 Example 2 Loads and timer each powered by different sources and voltages 277 VAC Indoor Lighting AC 24 VAC Thermostat 240 VAC Motor 120 VAC Signal Horn 30 WARNING If timer power supply vo...

Page 17: ...interval duration even if the load was not On before the start of the Off pulse or interval TROUBLESHOOTING Problem Solution s Display Does Make sure flat cable is properly plugged into the Not Light rear of the logic module Refer to Re installing logic module in Special Instructions If connec tor will not install easily check for bent pins On multi volt model make sure the voltage selector jumper...

Page 18: ...ulse features to eliminate if required NOTE ASTRO switching times change daily according to changing Sunrise and Sunset Consider fixed times with this in mind e g a fixed Off intended to end an Astro On would be ignored if sunset moves beyond the fixed Off time The fixed event should be scheduled to occur outside the range of the Astro event or an Astro Pulse should be considered NOTE Override int...

Page 19: ... entry the Switch Off Display On or Switch Off LED does not alternate Doesn t since most Pulse or Interval applications Alternate require only ON or OFF Press OK without a During time entry to alternate the Switch On Off Programming display if required Some All review should be done with only one circuit Switching enabled at a time If more than one is enabled Times Don t only events common to the ...

Page 20: ...icable ERR 0B Override entry not applicable ERR 0C PULSE entry not applicable ERR 0D INTERVAL entry not applicable ERR 0E Invalid or incomplete entry ERR 0F Unrecognized key or too many keys pressed ERR 1A No AM or PM selection ERR 1B Review entry not applicable ERR 1C One or more of the selected circuits has a program conflict ERR 1D The day of the week entry does not agree with the previously en...

Reviews: