background image

7

 

 

P/N 1006-7201-00 • REV A • ISS 14MAR18                      ©2018 United Technologies Corporation

  

3. Troubleshooting Guide

Trouble Condition

Visual Indications

Audible Indications

Action:

Fault Mode/Fatal 

Error

One AMBER 

LED blink every 5 

seconds.

Alarm chirps 

every 30 seconds.

1. Push the Test/Hush button once to attempt to 

reset the alarm. 

The RED LED will blink out an Error Code 

(number of blinks) when the Test/Hush button 

is pushed/released once.Report the number of 

blinks to Customer Service, if needed.

2. Clean your alarm. See “Cleaning Your Alarm” 

for instructions. 

3. Remove alarm from service. If fatal error 

cannot be cleared, permanently discharge and 

decommission the alarm.

Network Error  

(if a alarm loses 

wireless interconnect 

connection due to 

loss of signal)

One AMBER 

LED blink every 5 

seconds.

Alarm chirps every 

30 seconds. (

NOTE:

 

chirps only occur if 

network includes more 

than 2 alarms.)

Remove device from mounting bracket, and try 

rotating and re-installing the device in a different 

orientation on the mounting bracket.  This might 

align the antenna in a better position.

1. Push the Test/Hush button once to silence the 

audible indication for 24 hours at a time. 

    The RED LED will blink out an Error Code 

(number of blinks) when the Test/Hush button 

is pushed/released once. Report the number of 

blinks to Customer Service, if needed.

2. Follow instructions in “Resetting an Alarm’s 

Wireless Interconnect Settings.”, then attempt 

to rejoin the network by following the instruc-

tions in ”Adding Alarms to an Existing Wireless 

Interconnected Network .”*If the error persists, 

remove, discharge, and replace the alarm as 

soon as possible.

Network Error due to 

loss of radio  

(CCI supervision)

One AMBER 

LED blink every 5 

seconds.

Alarm chirps every 30 

seconds, regardless of 

the number of  

alarms in the network.

1. Push the Test/Hush button once to silence the 

audible indication for 24 hours at a time.

The RED LED will blink out an Error Code (4 

blinks) when the Test/Hush button is pushed/

released once. Report the number of blinks to 

Customer Service, if needed.

2. Remove, discharge, and replace the alarm as 

soon as possible.

Summary of Contents for HDX-135Z-433

Page 1: ...ghly read this user guide which should be saved for future reference NOTE Leave this user guide with the home owner You do NOT need a home wi fi system to use these units Multiple wireless units create their own independent wireless alarm network HDX 135Z 433 Wireless Interconnected Heat Freeze sensor 433 63 User Guide ...

Page 2: ... wireless units create their own independent wireless alarm network Teach children how to respond to the alarm and that they should never play with the unit Your Interlogix heat alarm was designed for use in a residential environment It is not designed for use in a recreational vehicle RV or boat NOTE Please thoroughly read this user guide and save the document for future reference and to pass on ...

Page 3: ...ommended Locations For Heat Alarms 14 7 Locations To Avoid 17 8 Installation Activation Wireless 18 8 1 Set Up A Wireless Alarm Network Wireless Interconnect 19 8 2 Adding Alarms to an Existing Wireless Interconnected Network 21 8 3 Resetting an Alarm s Wireless Interconnect Settings 22 9 Operation and Testing 23 10 Recognizing Nuisance Alarms 25 11 Battery 26 12 Permanently Disable Alarm Discharg...

Page 4: ...r Instead use your alternate exit If the inside of the door is cool place your shoulder against it open it slightly and be ready to slam it shut if heat and smoke rush in If the escape route requires you to go through smoke stay close to the floor where the air is cleaner Crawl if necessary and breathe shallowly through a cloth wet if possible Once outside go to your selected meeting place and mak...

Page 5: ...ts trim plate otherwise flashing and chirping will continue while condition exists System Test Mode Rapidly flashing RED LED for 10 seconds duration 1 alarm chirp when magnet detected 2 alarm chirps when System Test mode enabled Hold magnet next to button for 4 seconds See Figure 5 Local Alarm Test button press when no alarm condition is present Flashes RED AMBER GREEN then current protocol Tempor...

Page 6: ...de Heat HUSH CONTROL Red LED blinks every 2 sec After button push Heat alarm pattern stops If the unit still detects a dangerous situation the alarm will sound again This feature is to be used only when a safe condition is known to exist Locate None After button push on non ini tiating unit only initiating unit continues alarm pattern Use this to quickly locate the alarm source and determine if al...

Page 7: ...ng the device in a different orientation on the mounting bracket This might align the antenna in a better position 1 Push the Test Hush button once to silence the audible indication for 24 hours at a time The RED LED will blink out an Error Code number of blinks when the Test Hush button is pushed released once Report the number of blinks to Customer Service if needed 2 Follow instructions in Rese...

Page 8: ...ery 30 seconds The RED LED will blink out an Error Code of 9 blinks Start of EOL will be delayed if Night Detect is active Hush for Network Error End of Life One AMBER LED blink every 5 seconds Chirp temporarily silenced for 24 hours Push the Test Hush button to initiate Hush for 24hrs Alarm Fault Number of RED LED Blinks short duration blinks Wireless Fault Number of RED LED Blinks long duration ...

Page 9: ...rms can be a part of the same interconnected network The HDX 135Z 433 uses 10 year sealed in lithium batteries ensuring continuous operation over the 10 year life of the alarm This eliminates worry about battery removal or unauthorized deactivation of the alarm The self activation feature activates the alarm when attached to the mounting bracket At the end of alarm life the unit will chirp indicat...

Page 10: ...ensor NTC Thermistor Battery life 10 years Alarm life 10 years Audible alarm Heat 85dB at 10 3 0 to 3 5 KHz pulsing alarm Temporal T3 pattern Single Unit Box Dimensions 142mmx149mm x 65mm W x L x H Product Dimensions Ø142 3 0 3mm x 59 0 1 0mm Gross Weight unit pkg etc 452 grams Net Product Weight 327 grams Product Features and Specifications ...

Page 11: ...5 F 29 4 C Fixed temperature heat detection 135 F 57 2 C Freeze warning 41 F 5 C 5 F 2 8 C Storage temperature 4 F 20 C to 140 F 60 C Operating environment Temperature Relative humidity 32 F to 100 F 0 C to 37 8 C 0 to 95 noncondensing Regulatory Listings UL539 3 year warranty Not a battery performance claim Product Features and Specifications ...

Page 12: ...12 P N 1006 7201 00 REV A ISS 14MAR18 2018 United Technologies Corporation Model Description HDX 135Z 433 Wireless Interconnected Heat Freeze sensor 433 63 UL539 Product Ordering ...

Page 13: ...f of the occupants in po tentially fatal fires Victims are often intimate with the fire too old or young or physically or mentally impaired such that they cannot escape even when warned early enough that escape should be pos sible For these people other strategies such as protection in place or assisted escape or rescue are necessary A battery powered alarm must have a battery of the specified typ...

Page 14: ...aked or cathedral ceilings at or within 3 ft 0 9m of the highest point measured horizontally NFPA 72 states Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft 3m in 2 4m horizontally shall be located on the high side of the room NFPA 72 states A row of alarms shall be spaced and located within 3 ft 0 9m of the peak of the ceiling measured horizontally see Figure 3 In rooms with op...

Page 15: ...the heat from reaching an alarm mounted on the ceiling In such units install the heat alarm on an inside wall with the top edge of the alarm at a minimum of 4 10 cm and a maxi mum of 12 30 5 cm below the ceiling see Figure 1 If you are not sure about the insulation in your mobile home or if you notice that the outer walls and ceiling are either hot or cold install the alarm on an inside wall WARNI...

Page 16: ...16 P N 1006 7201 00 REV A ISS 14MAR18 2018 United Technologies Corporation FIGURE 1 FIGURE 2 FIGURE 3 ...

Page 17: ...ance alarms Heat alarms are not to be used with alarm guards unless the combination alarm and guard have been evaluated and found suitable for that purpose In very humid areas above 95 RH non condensing Moisture or steam can cause nuisance alarms Alarms should not be installed within 3 ft 9m of the door to a bathroom containing a tub or shower forced air supply ducts used for heating or cooling ce...

Page 18: ...ate by rotating the alarm in a clockwise direction NOTE Installing the alarm on the mounting bracket trim plate will automatically activate the battery The power up sequence is indicated by the LED ring slowly glowing GREEN on off one time NOTE Alarms will emit a series of slow RED LED glowing on off as the alarm searches for a wireless network If you are intending to use the alarms without the wi...

Page 19: ...aken within 15 minutes of initial power up the wireless function will turn off The alarm will then perform as a single station alarm WIRELESS These models have wireless alarm interconnect capability When one interconnected alarm sounds an alarm all other compatible wireless alarms in the wireless alarm network will alarm A maximum of 24 compatible devices may be interconnected in a multiple statio...

Page 20: ...e network setup to timeout approximately 15 minutes OR to immediately close the network push the Test Hush button until two beeps are heard approximately 4 seconds and then release the button The network can be closed from any device enrolled in the network When the network has been closed each alarm s GREEN LED will change from glowing on off every second to flashing once every 60 seconds to indi...

Page 21: ...rim plate to activate the battery or by carefully turning the red activation wheel with a screwdriver See Figure 4 After initial GREEN LED on off sequence the new alarm s RED LED will fade on off every 3 sec onds as it searches for the network A fast GREEN LED flickering followed by a slow GREEN LED fading on off confirms the new alarm has found and joined the existing wireless interconnection net...

Page 22: ... the out of box mode 1 Place and hold a magnet for 4 seconds on the cover at the designated location per Figure 5 The alarm will chirp once when the magnet is detected then the alarm will chirp twice and the button will start flashing the RED LED rapidly to indicate System Test Mode has been entered 2 Press and hold the Test Hush button for approximately 8 seconds while the RED LED is rapidly flas...

Page 23: ...c or low volume sound or no sound coming from your alarm may indicate a defective alarm and it should be returned for service See Permanently Disable Alarm Discharge Battery section to determine how to prepare the unit for shipment or disposal To test all alarms connected in the same network start System Test mode by placing a magnet in the location shown in Figure 5 and holding it for four second...

Page 24: ...the next Day cycle you can temporarily silence End of Alarm Life or Network Error chirps by pressing the Test Hush button Low Battery chirps cannot be silenced If a valid Night Day cycle has not been established because the alarm is located in either a constantly dark or lighted location the chirps mentioned above will not be delayed at night Moving the alarm to a different location might allow th...

Page 25: ...an alarm that detects smoke or heat and initiates an alarm is called the initiating alarm unit Initiating alarm units will be flashing the Green LED every second during alarm interrupted by the T3 RED LED alarm pattern Depending on alarm loca tions and the location of the source of smoke or heat it is possible to have more than one initiating alarm If you suspect a nuisance alarm situation you can...

Page 26: ... THE BATTERY USED IN THIS DEVICE MAY PRESENT A FIRE OR CHEMICAL BURN HAZARD IF MISTREATED DO NOT RECHARGE DISASSEMBLE HEAT ABOVE 100 C 212 F OR DISPOSE OF IN FIRE Low battery This alarm is equipped with a low battery monitor circuit If the battery capacity can no longer provide ade quate power for all alarm functions the low battery condition will occur See Troubleshooting Guide The alarm battery ...

Page 27: ...or reactivated WARNING Failure to discharge alarm battery as instructed prior to disposal may create poten tial for lithium battery related fire or hazard CAUTION Do not disassemble and do not dispose of in fire To Permanently Disable Alarm Discharge Battery Rotate the alarm counterclockwise to remove it from the mounting plate Push in the dashed area with a screwdriver to break tab Figure 6 After...

Page 28: ...a Test Hush button push and the temporal test sequence the alarm may be in need of cleaning After cleaning press the Test Hush button If the fault does not clear the alarm needs to be replaced Never use detergent or other solvents to clean the alarm Avoid spraying air freshener hair spray or other aerosols near the alarm Do not paint the alarm Never attempt to disassemble the alarm to clean inside...

Page 29: ...d Install and maintain fire extinguishers on every level of the home and in the kitchen basement and garage Know how to use a fire extinguisher prior to an emergency Fire warning systems for dwelling units are capable of protecting about half of the occupants in potentially fatal fires Victims are often intimate with the fire too old or young or physically or mentally impaired such that they canno...

Page 30: ...EABLE The required number of smoke alarms might not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke alarms For this reason it is recom mended that the householder consider the use of additional smoke alarms for those areas for increased protection The additional areas include the basement bedrooms dining room furnace room...

Page 31: ... radio or television reception the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for he...

Page 32: ... ALL WARRANTIES AND REPRESENTATIONS WHETHER EXPRESS IMPLIED STATUTORY OR OTHERWISE INCLUDING BUT NOT LIMITED TO ANY WAR RANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THESE PRODUCTS AND ANY RELATED SOFTWARE MANUFACTURER FURTHER DISCLAIMS ANY OTHER IMPLIED WARRANTY UNDER THE UNIFORM COMPUTER INFOR MATION TRANSACTIONS ACT OR SIMILAR LAW AS ENACTED BY ANY STATE USA onl...

Reviews: