4 Intended Use
Terminals of the IF-80x series are designed for controlling access as well as for controlling and monitoring
locking devices. Any other use is not in accordance with the intended purpose and is therefore not permitted.
5 Shielded Cables
To guarantee trouble-free operation, we recommend the use of shielded cables.
Operation, however, is also possible with unshielded cables. Data transfer problems must be examined on a
case-by-case basis. Where necessary, a shielded cable must be used for the corresponding devices.
6 Assembly and Installation
Please carry out all of the following steps in sequence:
Install all cables.
Mount the IF-80x terminal.
Make the electrical connections and switch on the power.
Adjust the reader.
Set the hardware address.
Start initial operation and test.
6.1 Laying the Cables
1
Power supply to mounting rail power supply unit
(41-10106)
4 Ethernet data cable from switch to IF-4070 controller or
IF-5735 terminal. Cable length maximum 100 m. Power
is supplied to the master terminal shown here via PoE
or from an external power supply unit.
2
Power supply to I/O controller board
5 Data cable from the I/O controller board to the IF-80x
terminal
3
Patch cable from PC to switch or hub
6 RS485 data cable from an IF-4070 controller to an I/O
controller board
Please refer to the table "
Function of Cables and Cable Types
" for detailed information on the cable
lengths, cable types and their diameters.