![intensity IPRC2414KC-3 Installation Instructions Manual Download Page 14](http://html1.mh-extra.com/html/intensity/iprc2414kc-3/iprc2414kc-3_installation-instructions-manual_2075139014.webp)
14
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per Standard UL 1995.
3. Fuse or HACR circuit breaker size in stalled at factory or field installed.
Table 6-1: 14 SEER Heat Pump W/Without Electric Heat
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
Model
kW
Stages
Amps
024
(2.0)
036
(3.0)
048
(4.0)
060
(5.0)
208/240-1-60
208/240-1-60
208/240-1-60
208/240-1-60
13.5A 58A 21.0A
41.2A
134A
26.4A
34.0A
117A
21.8A
26.0A
79A
16.7A
0.57A
1.08A
1.74A
1.74A
1.73A
2.45A
3.54A
3.92A
None
-
-
19.3
None
3.8/5
18.1/20.8 41.9/45.3
5.6/7.5
27.1/31.3 53.2/58.4
7.5/10
36.1/41.7 64.4/71.4
None
-
-
24.5
None
None
-
-
32.6
None
3.8/5
18.1/20.8 47.1/50.5
5.6/7.5
27.1/31.3 58.3/63.6
7.5/10
36.1/41.7 69.6/76.6
11.3/15
54.2/62.5 92.2/102.6
3.8/5
18.1/20.8 55.2/58.6
5.6/7.5
27.1/31.3 66.5/71.7
7.5/10
36.1/41.7 77.7/84.7
11.3/15
54.2/62.5 100.3/110.7
None
-
-
38.7
None
3.8/5
18.1/20.8 61.3/64.7
5.6/7.5
27.1/31.3 72.6/77.8
7.5/10
36.1/41.7 83.8/90.8
11.3/15
54.2/62.5 106.5/116.8
15/20
72.2/83.3 129.0/142.8
30
50/50
60/60
70/80
40
50/60
60/70
70/80
100/110
15/20
72.2/83.3
1
1
1
1
1
1
2
1
1
1
2
1
1
1
2
2
2
122.8/136.7
50
70/70
80/80
90/90
110/125
150/150
60
80/80
90/90
100/100
110/125
150/150
EHK-05C
EHK-08C
EHK-10C
EHK-05C
EHK-08C
EHK-10C
EHK-15C
EHK-05C
EHK-08C
EHK-10C
EHK-15C
EHK-20C
EHK-05C
EHK-08C
EHK-10C
EHK-15C
EHK-20C