background image

5

53-22130A100

The Control Module operates the air conditioner compressors and fans via three relays with 12 VDC coils
supplied by the A/C manufacturer and mounted in their equipment.  The contacts on these relays are internally
wired by the A/C manufacturer to the 120 VAC supply line for each unit and connect the compressor and the
low or high speed taps on the fan motor to that supply line when operated.  The wiring between the Control
Module and these relays is low voltage (12 VDC) wiring.  The Control Module uses 

high side switching to

operate the corresponding relays.  One side of each of the relay coils is connected together. This "common"
lead is connected to ground through the Control Module and 

should not be grounded anywhere else.  The other

side of each of the coils is brought out to one of three separate leads.  These leads are connected to the Control
Module via a four pin connector - J2 for the front A/C unit, and J3 for the rear A/C unit.  The corresponding pigtail
connectors, PC2 and PC3, are supplied with the system.  PC3, the rear A/C connector, is marked in red in
order to differentiate it from PC2.  The following table indicates the connection and control states:

MODULE

PIGTAIL

 CONN

WIRE

FUNCTION

  “ON”

  “OFF”

  PIN

COLOR

VOLTAGE

VOLTAGE

  J2-1

BLU

COMMON

< 1 VDC

< 1 VDC

  J2-2

GRY

LOW FAN

+12 VDC

< 1  VDC

  J2-3

GRN

HIGH FAN

+12 VDC

< 1 VDC

  J2-4

YEL

COMPRESSOR

+12 VDC

< 1 VDC

  J3-1

BLU

COMMON

<1  VDC

< 1 VDC

  J3-2

GRY

LOW FAN

+12 VDC

< 1 VDC

  J3-3

GRN

HIGH FAN

+12 VDC

< 1 VDC

  J3-4

YEL

COMPRESSOR

+12 VDC

< 1 VDC

NOTE: The PC2 and PC3 pigtail wire colors are included for reference only to identify the functions of

the wires emanating from the Control Module.  The wire colors emanating from the front and rear
A/C units may or may not agree with these colors.  Always refer to the installation manual
supplied with the A/C unit, or see “Identifying control lead functions on the A/C unit”, in order to
match the wire color/functions with those on the Control Module.

TEST SWITCH:

The Control Module incorporates a three position test switch located between J2 and J3 to verify proper wiring
to each A/C unit relay.  Sliding the test switch towards the J2 operates the front compressor and high fan by
connecting  J2-3 and J2-4 to +12V.  Sliding the test switch towards the J3 operates the rear compressor and
high fan by connecting  J2-3 and J2-4 to +12V.   The test switch must be placed in the CENTER or OFF position
for normal operation.

SHORT INDICATOR:

The 12 volt wires feeding the air conditioners are protected from short circuits.  If any of these wires is shorted
to ground, the SHORT INDICATOR LED will be illuminated, indicating the short.  To help locate the short, the
plugs feeding the air conditioners should be unplugged, one at a time, to see which cable is at fault.  When the
shorted cable is unplugged, the SHORT INDICATOR will go out and the other air conditioner will operate
normally.  The individual wires of the shorted plug can be tested for shorts to find which one is at fault.

131 EISENHOWER LANE NORTH
LOMBARD, ILLINOIS 60148-5413
630-268-0010 / 1-800-251-2408

ELECTRONIC CLIMATE CONTROL

INTELLITEC

Summary of Contents for ECC

Page 1: ...nt temperature When in the AUTO mode the unit automatically controls the compressors and selects the appropriate air conditioner fan speed based on the difference between the set point temperature and...

Page 2: ...GND There are two identical sets of controls on the panel one for each of the front and rear systems The potenti ometers allow the user to select a desired temperature for each system in the range of...

Page 3: ...cator will be lit when the associated function switch is in any mode except the OFF mode and the system has not shed the associated air conditioner compressor or fan The red SHED indicator will be lit...

Page 4: ...ected to pins 1 and 2 of connector J4 and the contacts for the rear furnace are connected to pins 4 and 5 of the same connector They are electrically isolated from all other circuitry on the Control M...

Page 5: ...GH FAN 12 VDC 1 VDC J3 4 YEL COMPRESSOR 12 VDC 1 VDC NOTE The PC2 and PC3 pigtail wire colors are included for reference only to identify the functions of the wires emanating from the Control Module T...

Page 6: ...n by all of the 120 VAC operated equipment in the coach being fed through the main panel The Current Sensor is mounted in the main panel and supplies an input signal to the Control Module When enough...

Page 7: ...WHT 2 2 CURRENT SENSOR GND WHT J1 PC1A FUNCTION COLOR pin pin 3 1 KEYED NOT CONNECTED 4 2 12 VDC POWER RED 5 3 KEYED NOT CONNECTED 6 4 POWER GROUND BLK 7 5 IPXGND BRN 8 6 IPX SIG YEL THE ECC CURRENT S...

Page 8: ...INTELLITEC USE OF THE ECC WITH AUXILIARY GENERATOR SETS USE WITH 4KW GENERATOR In systems using 4KW generator sets the main system includes a manual or automatic change over which selects the 30 Amp...

Page 9: ...ront system to the generator s second output to utilize generator s full output capability In this situation the ECC load shedding features will remain unchanged but the Current Sensor will not measur...

Page 10: ...connections to the ECC Thermostat If OK 1 Measure the DC voltage between the IPX SIG and IPX GND lugs and measure the voltage between pins 7 and 8 of J1 on the Control Module The voltage should read g...

Page 11: ...ck the continuity of the Comp Relay lead between the Control Module and the front A C unit B Slide the test switch on the Control Module towards J3 Rear compressor and high fan should turn on If not 1...

Page 12: ...d rear A C unit V ON indicator is on but the furnace does not operate in HEAT mode at any thermostat setting A Check the fuse or circuit breaker feeding the furnace B Move the set point control up to...

Page 13: ...e following situations 1 Shore power is plugged in 2 Generator is started and shore power is not plugged in 3 The 12 volt power to the control module is first applied 4 The Control Module has shed an...

Page 14: ...14 53 22130A100 131 EISENHOWER LANE NORTH LOMBARD ILLINOIS 60148 5413 630 268 0010 1 800 251 2408 ELECTRONIC CLIMATE CONTROL INTELLITEC...

Page 15: ...ingle Furnace Thermostat 00 00597 100 F80 0026 Dual Furnace Thermostat 00 00597 000 F80 0025 Control Module 00 00591 100 F97 0051 11K 13 5K BTU air conditioner Control Module 00 00591 000 F97 0052 11K...

Reviews: