background image

GEFRAN SpA

Via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) ITALY

This  Quick  Start  Guide  provides  basic  information  on 
setting up the Gefran 1200 controller for the application 
referenced  above.  Additional  software  and  hardware 
configuration information can be found in the User’s Manual 
included with this controller or online at www.gefran.com

If needed, automatic tuning (Self-Tune) can be enabled 

with the following steps

•  Press and hold 

F

 until 

CFG

 appears

•  Press 

F

 once, 

S.Tu

 appears — 

ENTER

 

2

•  Press 

F

 once

•  Cycle power to the controller
•  LED 3 (

L3

) will flash during the tuning process

With the machine at ambient temperature and

the control setpoint (SV) set...

Self-Tune will automatically save new PID

values once complete

Note

Change all menu parameters by 
using the front panel buttons

GETTING STARTED

• Unpack Contents
• Verify model numberand application
• Power Controller
• Program for yourapplication

Program Your Gefran Controller

2

* Parameter may be left at default value for input types 0...37

Input Sensor

Sensor Type

Sensor Type

0 TC J °C

30 PT100 °C

1 TC J °F

31 PT100 °F

2 TC K °C

32 JPT100 °C

3 TC K °F

33 JPT100 °F

4 TC R °C

34 PTC °C

5 TC R °F

35 PTC °F

6 TC S °C

36 NTC °C

7 TC S °F

37 NTC °F

8 TC T °C

44 4...20 mA

9 TC T °F

46 0...10 V

Connect Your Controller

3

What’s Included

• 48x96 DIN 1200-RD00-00-0-x 
  Gefran Controller x2
• Mounting Bracket
• Panel Sealing Gasket
• Screw Terminal Cover
• Multi-Language Manual

1

•  Press and hold 

F

 until 

PAS

 appears — 

ENTER

 

99

•  Press 

F

 once, 

Pro

 appears — 

ENTER

 

128

•  Press 

F

 once, 

PAS

 appears — 

ENTER

 

99

•  Press and hold 

F

 until 

Hrd

 appears

•  Press 

F

 repeatedly until 

but

 appears — 

ENTER

 

1

•  Press and hold 

F

 until

1 nP

 appears

•  Press 

F

 twice, 

tYP

 appears — 

ENTER

 the Input Sensor number

  from the list
•  Press 

F

 repeatedly until 

Lo.S

* appears — 

ENTER

 the minimum Input Scale limit

•  Press 

F

 once, 

H i.S

* appears — 

ENTER

 the maximum Input Scale limit

•  Press 

F

 repeatedly until 

Lo.L

* appears — 

ENTER

 the minimum Alarm Scale limit

•  Press 

F

 once, 

H i.L

* appears — 

ENTER

 the maximum Alarm Scale limit

•  Press and hold 

F

 until you return to the main process display.  This is the display after 

PAS

 

and will be indicated by the Process Variable if an input sensor is connected, or 

Lo

H i

Sbr

Err

 if no input is connected.

•  Use the   and   buttons to adjust the control setpoint (SV) from the main display.

•  Press 

F

 once from the main display, 

AL.1

 appears to adjust the Alarm 1 setpoint.

•  Press the 

 button to switch between automatic and manual control modes from the 

main display.  LED 1(

L1

) will light while in manual mode.

POWER

Additional wiring

configurations 

are available 

in the User’s 

Manual and

General Setup 

Guide

Quick Start Guide

1200-RD00-00-0-x 

Programmable PID Controller

2

-

1

+

7

8

11

10

6

-

5

+

ALARM

Heat & Alarm

HEATER 

POWER CONTROL

THERMOCOUPLE

Summary of Contents for 1200-RD00-00-0 Series

Page 1: ...ncluded 48x96 DIN 1200 RD00 00 0 x Gefran Controller x2 Mounting Bracket Panel Sealing Gasket Screw Terminal Cover Multi Language Manual 1 Press and hold F until PAS appears ENTER 99 Press F once Pro appears ENTER 128 Press F once PAS appears ENTER 99 Press and hold F until Hrd appears Press F repeatedly until but appears ENTER 1 Press and hold F until1 nP appears Press F twice tYP appears ENTER t...

Page 2: ... minimum Alarm Scale limit Press F once H i L appears ENTER the maximum Alarm Scale limit Press and hold F until Out appears Press F three times rl 1 appears ENTER1 Press F twice rl 3 appears ENTER 2 Press and hold F until you return to the main process display This is the display after PAS and will be indicated by the Process Variable if an input sensor is connected or Lo H i Sbr Err if no input ...

Page 3: ...ppears ENTER the minimum Input Scale limit Press F once H i S appears ENTER the maximum Input Scale limit Press F repeatedly until Lo L appears ENTER the minimum Alarm Scale limit Press F once H i L appears ENTER the maximum Alarm Scale limit Press and hold F until Out appears Press F once rl 1 appears ENTER1 Press and hold F until you return to the main process display This is the display after P...

Page 4: ...hat s Included 48x96 DIN 1200 RR00 00 0 x Gefran Controller x2 Mounting Bracket Panel Sealing Gasket Screw Terminal Cover Multi Language Manual 1 Press and hold F until PAS appears ENTER 99 Press F once Pro appears ENTER 128 Press F once PAS appears ENTER 99 Press and hold F until Hrd appears Press F repeatedly until but appears ENTER 1 Press and hold F until1 nP appears Press F twice tYP appears ...

Page 5: ...ENTER the minimum Input Scale limit Press F once H i S appears ENTER the maximum Input Scale limit Press F repeatedly until Lo L appears ENTER the minimum Alarm Scale limit Press F once H i L appears ENTER the maximum Alarm Scale limit Press and hold F until Out appears Press F once rl 1 appears ENTER1 Press and hold F until you return to the main process display This is the display after PAS and ...

Page 6: ...m Alarm Scale limit Press F once H i L appears ENTER the maximum Alarm Scale limit Press and hold F until Out appears Press F three times rl 1 appears ENTER1 Press F twice rl 3 appears ENTER 2 Press and hold F until you return to the main process display This is the display after PAS and will be indicated by the Process Variable if an input sensor is connected or Lo H i Sbr Err if no input is conn...

Reviews: