3. OPERATION AND TROUBLE SHOOTING  
 

3.1 Metering Rules 

 

1.

 

Current Transformers (CTs) are directional. 

2.

 

Voltage references must be in phase with the load being metered and from the same source. 

 

Rule #1: 

 

 

If the CTs are mounted in the opposite direction, the polarity of the CT will be opposite. 

 

The arrow on the CT indicates the direction from LINE to LOAD. 

 

 

 

Similarly, the 

“H1”

 is on the LINE SIDE. 

 
All Intellimeter milli-Amp current transformers 100:0.8A, 200:0.1A, 400:0.1A and 600:0.1A have 
self-shorting protection built into the device. They can safely be open circuited while under load. 

 

 

External Current Transformers (CTs)

 

Twisted Pair #18-14 stranded colour code

 

#1

 

Intellimeter CTs 

100A (ICI30CT108-B) 

White (+) 

Black (-) 

#2

 

Intellimeter CTs 

200A (ICI30CT21) 

White (+) 

Black (-) 

#3

 

Intellimeter CTs 

400A (ICI30CT41) 

White (+) 

Black (-) 

#4

 

Intellimeter CTs 

600A (ICI30CT61) 

White (+) 

Black (-) 

#5

 

Instrument CTs 

X000:5A + 20 Turn CTs 

White (+) 

Black (-) 

 

 

The maximum length the CT leads can be extended is 30metres.  

 

1 twisted pair wire only for each CT. 

Summary of Contents for i -meter MF3

Page 1: ...Page 1 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2020 MF Series Manual I METER MF SERIES INSTALLATION AND USER MANUAL...

Page 2: ...TENTS 1 PRODUCT DESCRIPTION 4 1 1 Applications 4 1 2 Specifications 5 2 INSTALLATION 6 3 OPERATION AND TROUBLE SHOOTING 7 3 1 Metering Rules 7 4 STEPS TO OPERATE THE METER 9 5 CONFIGURATION 11 6 i met...

Page 3: ...a return material authorization RMA number should be obtained from ICI STATEMENT OF CALIBRATION The accuracy and calibration of our instruments are traceable to Measurement Canada a division of Indust...

Page 4: ...There are two models i meter MF3 1 3 meter with optional neutral current measurement i meter MF6 2 3 meters with optional neutral current measurement Measurement Canada California CTEP and CSA approve...

Page 5: ...ing Rated VA 4 VA Service Type 1 2W 1 3W 2 3W 3 4W wye 3 3W Delta Current Transformers 80 100 mA output Self Shorting Protection Current Range 0 08 80mA 1 100mA Instrument Transformers Interface Yes P...

Page 6: ...actor has to wire to the meter board and use the wire terminals spade connectors provided Terminate the voltage reference chain to the designated 15Amp breaker and ensure the proper phasing retained a...

Page 7: ...rom LINE to LOAD Similarly the H1 is on the LINE SIDE All Intellimeter milli Amp current transformers 100 0 8A 200 0 1A 400 0 1A and 600 0 1A have self shorting protection built into the device They c...

Page 8: ...e sequence Usually Line 1 Red or A phase Line 2 Black or B phase Line 3 Blue or C phase Neutral White Note Colour sequence may vary depending on the country and region Rule 3 When the metering system...

Page 9: ...ON L1W 3T9 Tel 905 839 9199 Copyright 2020 MF Series Manual 4 STEPS TO OPERATE THE METER Step 1 Connect three phase voltage to Voltage Inputs terminals Step 2 Connect all CTs to CT Inputs according to...

Page 10: ...Page 10 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2020 MF Series Manual i meter MF6 series wiring diagram...

Page 11: ...factory 6 i meter MF SERIES DISPLAY The i meter MF3 and the i meter MF6 have a three line LCD that shows both energy consumption and real time measurements Three line LCD 3x9 character i meter MF3 is...

Page 12: ...i_meter 123456 1 2 1 4 0 9 5 V Pf L1 1 2 3 6 0 9 2 V Pf L2 1 2 4 8 0 9 8 V Pf L3 Line 1 Phase A Voltage Power Factor Line 2 Phase B Voltage Power Factor Line 3 Phase C Voltage Power Factor Screen 3 I...

Page 13: ...e 3 Neutral Current 7 i meter MF SERIES COMMUNICATION The i meter MF series ModBus module enables the meter to communicate on a ModBus system It presents real time measurements such as voltage current...

Page 14: ...eral information about the meter and the ModBus module This information is the identification data and it generally remains constant with the exception of the up time Configuration Parameters Modbus A...

Page 15: ...NT32 x0 001A 41109 Current B UINT32 x0 001A 41111 Current C UINT32 x0 001A 41113 Watts A INT32 W 41115 Watts B INT32 W 41117 Watts C INT32 W 41119 Volt Amp A INT32 VA 41121 Volt Amp B INT32 VA 41123 V...

Page 16: ...NT32 x0 001A 41209 Current B UINT32 x0 001A 41211 Current C UINT32 x0 001A 41213 Watts A INT32 W 41215 Watts B INT32 W 41217 Watts C INT32 W 41219 Volt Amp A INT32 VA 41221 Volt Amp B INT32 VA 41223 V...

Page 17: ...s Name Format Unit Default 47001 THD IA Meter 1 UINT16 0 01 47021 THD IB Meter 1 UINT16 0 01 47041 THD IC Meter 1 UINT16 0 01 47061 THD IA Meter 2 UINT16 0 01 47081 THD IB Meter 2 UINT16 0 01 47101 TH...

Page 18: ...3T9 Tel 905 839 9199 Copyright 2020 MF Series Manual Thank you for giving us the opportunity to serve you We appreciate your business and the confidence you have placed in us Please visit us https in...

Reviews: