Page 15
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 MF Series Manual
Meter 1 Information:
Modbus
Address
Name
Format
Unit
Default
41100 Active Phases
Bit map
x1
41101 Voltage A
UINT32
x0.001V
41103 Voltage B
UINT32
x0.001V
41105 Voltage C
UINT32
x0.001V
41107 Current A
UINT32
x0.001A
41109 Current B
UINT32
x0.001A
41111 Current C
UINT32
x0.001A
41113 Watts A
INT32
W
41115 Watts B
INT32
W
41117 Watts C
INT32
W
41119 Volt-Amp A
INT32
VA
41121 Volt-Amp B
INT32
VA
41123 Volt-Amp C
INT32
VA
41131 Power Factor A
INT32
0.001 Units
41133 Power Factor B
INT32
0.001 Units
41135 Power Factor C
INT32
0.001 Units
41143 kWh
UINT32
X0.001kWh
41145 kVAh
UINT32
X0.001kVAh
41149 Frequency
UINT32
0.01 Hz
Note
1.
Active Phases - 41100
: 0x0001 - Meter uses phase A; 0x0002 -
Meter uses phase B; 0x0004 - Meter uses phase C.