7.2 i-meter® ModBus RTU Registers Mapping
The ModBus module has a plethora of registers that present the metering data, as well as diagnostic
information for the module itself. The bulk of the registers are available using the Read Holding Register
ModBus command, while the Read Input Registers provides direct read access to the non-volatile memory.
The system registers provide general information about the meter and the ModBus module. This
information is the identification data and it generally remains constant with the exception of the up time.
Configuration Parameters:
Modbus
Address
Name
Format
Access
Default
40003
Firmware Version
UINT16
41002
Address
UINT16
R/W
1
41003
Baud Rate
Enumated
R/W
3 = 9600 bps
Note
1.
Address - 41002
: Changes to the ModBus address takes effect
immediately. The next command must use the changed address,
otherwise the module will not respond.
2.
Baud Rate - 41003
: 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 =
57600 bps; 7 = 115200 bps. The Baud Rate takes effect after power
cycling.
3.
Firmware Version
: V4.64 (the same firmware as the i-45)
4.
Hardware Version
: 101-1357 REV-A