27 iN199 Air Intake Inlet and Exhaust Gas Outlet Pipe Connections
November 2021 - Revision 00
7.10 Recommended Exhaust-Gas Outlet Pipe
Transitions
3X DIA. MIN
45°
Do not direct exhaust gas from opposite directions. Use a 45 degree
transition, as shown.
Do not transition into a reducer or use a t-fitting. Transitions should always
be directed into a straight run of pipe.
Do not use 90 degree transition into a reducer or a straight pipe.
1/4" Rise Per
Foot Run
Condensate
Drain
Condensate
Drain
1/4" Rise Per
Foot Run
Do not use reducers in a straight run of pipe.