21
INS-500 & INS-1000 • 5403645 • REV A • 6/17
The Potter IntelliGen
™
Nitrogen Generator is designed to work specifically with the Potter IntelliPurge
®
Nitrogen Purge Valve.
Combining the two products creates a quick seamless experience when it comes to protecting and monitoring your sprinkler
system.
Use stranded 3 wire (22 AWG gauge) to run from the IntelliGen
™
Controller to the first INS-PV.
Maximum wire length for network is 6500 ft. Maximum number of INS-PV devices on network is 27. Maximum number of INS-
RA devices on network is 4.
The INS-PV’s devices must be addressed as slave devices. For addressing and programming the INS-PV see the INS-PV manual
#5401532.
The PLINK network is designed to be wired in series. See Fig. 21.
IntelliPurge
®
Wiring and Networking
Nitrogen
Generator
Fig. 21
Fig. 22
INS-PV-2
or
INS-RA
INS-PV-3
or
INS-RA
INS-PV-#
or
INS-RA
INS-PV-27
A
B
+
-
To
Next
Device
- 24V
DC +
- 24V
AC/DC +
INS-RA
INS-PV
Terminal Block
Normally Closed for Remote
BMS Monitoring