Remote Connection Checking
In order to verify that the modem is correctly operating when the modem is remotely
located, please follow the below steps:
1.
In serial modem mode with CSD connection, dial into the modem data number:
a.
If the response is ‘BUSY’ then the SIM card is not correctly provisioned.
b.
If the response is ‘NO CARRIER’ immediately then the SIM card is offline
and not registered.
c.
If the response is ‘NO CARRIER’ after some time, then the modem auto
answer is not working correctly but the SIM card is registered.
d.
If you are able to connect to the modem (response is ‘CONNECT’, then
you can remotely check the settings on the modem by changing to an
IP mode and making a connection to the modem using the
configuration GUI.
2.
In IP Stack modes:
Open the GUI with an IP connection to the modem and log in.
i.
Check that the settings are correct for the equipment that you
are wanting to connect to, including the serial baud rate, etc.
ii.
Check that the signal strength is of a good level, better than -81
dBm.
3.
In either mode, send diagnostic SMS commands to the modem as below:
a.
Check RSSI: By sending INTELIMAX.PARK.RSSI to the modem, the modem
will respond with the RSSI which should be better than -81 dBm.
b.
Check APN and WAN connection using: INTELIMAX.PARK.WANIP. The
response
is:
“IP:<IP.IP.IP.IP>,APN:<APN>,ID:<ID>,PW:<PW>,Auth:<PAP,
CHAP,BOTH>,Reg:<0,1>,Sig:<CSQ>”
c.
If neither command work, then reboot the modem using:
INTELIMAX.PARK.REBOOT