Intel
®
Server System SR870BH2
9
Quick Start Guide
protection by wearing an anti-static wrist strap attached to chassis ground of the
server when handling components (e.g., any unpainted metal surface).
CAUTION
Grounded outlet:
Make sure that the power service connection is through a
properly grounded outlet.
Temperature:
The range of temperatures in which the server operates when
installed in an equipment rack, must not go below 5 °C (41 °F) or rise above
35 °C (95 °F). Extreme fluctuations in temperature can cause a variety of
problems in your server.
Ventilation:
The equipment rack must provide sufficient airflow to the front
of the server to maintain proper cooling. The rack must also include
ventilation sufficient to exhaust a maximum of 650 Watts (or 2300 BTUs)
for each server. The rack selected and the ventilation provided must be
suitable to the environment in which the server will be used.
Checking Power Cords
WARNING
The Power button on the front control panel of the server does not
completely remove AC power. To completely remove AC power from
the server, you must unplug both AC power cords from the system or
from the wall outlet. Unplugging the cords removes the +12 Volt
standby power that is present when the server is powered down.
WARNING
Do not attempt to modify or use an AC power cord that is not the exact
type required. You must use a power cord that meets the following
criteria:
1. Rating: For U.S./Canada cords must be UL Listed/CSA Certified,
16/3, 75C type, VW-1, SJT/SVT, with NEMA 5-15P or
NEMA 6-15P attachment plug and IEC 320 C13 input power
connector rated 15 amps. For outside U.S./Canada cords must be
flexible harmonized (<HAR>) rated 250V, 1.0 mm minimum
conductor size with IEC 320 C13 input power connector and rated
for no less than 10 amps.
2. AC Attachment Connector, wall outlet end for outside U.S./Canada:
The AC wall attachment plug should be a three conductor grounding
type, rated at 125 V, 15 amps and must be for the configuration of
the specific region or country. The AC wall attachment plug must
bear at least an accepted safety agency certification mark for the
specific region or country.