5.

 

OPERATION MODES 

 

This  is  a  True  Online  Double  Conversion  Inverter,  and  it  is  designed  to  offer  clean,  bump-less,  and  highest  quality  power  to  your 

computer related equipment protecting also your valuable data. Power delivered by Inverter is 100% sine wave as main line. 

 

According to AC main service, and how Inverter has been configured, it may operate in following modes: 

 

ONLINE NORMAL Mode

: When Inverter is off by selecting ON push button in front panel Inverter enters ONLINE NORMAL mode if AC 

main service is inside acceptable input range. Under this mode 

Unit’s internal

 inverter powers outputs and the energy is taken from DC 

voltage coming from AC/DC converter. Batteries are charged by AC Line if required. 

 

BATTERY Mode: 

If in ONLINE NORMAL mode Inverter detects a problem in AC input Line, it enters in battery mode. Under this mode 

Inverter takes energy from batteries to feed inverter that generates power for the output. There are no transfers neither micro-cut on 

Inverter  output  as  inverter  was  already  working.  The  only  difference  is  that  energy  is  now  coming  from  batteries  instead  of  rectifier 

output. Transfer time is actually Zero (0ms). Inverter also can enter in battery mode when it is turned on without an acceptable AC input. 
 

STATIC BYPASS (INTERNAL BYPASS):

 This mode can be adopted if Inverter configuration allows BYPASS mode and any of 3 below 

conditions is present: 

Under bypass mode, Inverter AC output is feed from Inverter AC input. When Inverter is in bypass mode, in case AC input is interrupted, 

output will be interrupted also, and Inverter will power off. No battery mode can be adopted from bypass mode. 

Bypass mode can be caused by any of below conditions: 

1-

 

Bypass  mode  is  adopted,  in  case  ON  button  has  not  been  activated  as  soon  as  Inverter  detects  a  valid  AC  input  on  its 

terminals. (If bypass mode is not enabled, Inverter will simply light its LCD. Outputs will keep powered off)  

2-

 

Bypass mode is adopted as soon as a problem is detected in its internal circuitries. 

3-

 

Bypass  mode  is  also  activated  in  case  an  external  overload  is  detected  in  Inverter  output.  It  happens  when  equipment 

connected to Inverter output requires a power higher than max. power of the Inverter 

 

Additionally, this Inverter can adopt other operation modes under operator demand as described: 

 

FREQUENCY CONVERSION:

 

 

 

 

      

 

 

 

This  Inverter  offers  a  very  sophisticated  function  named  frequency  conversion  (CF)  that  allows  Inverter  to  generate  power  output  at 

determined frequency value (50Hz or 60Hz) no matter input frequency value. Inverter will be able to generate output at 50Hz even input 

source is at 60Hz or generate 60Hz even if connected to 50Hz source. 

This function can be configured and activated by LCD. Check configuration section of this manual. 

 

IMPORTANT NOTES: 

1.- Under CF mode, Inverter will disable BYPASS mode. Since  Inverter has been configured to generate output with frequency value 

different to input frequency, BYPASS mode is disabled to avoid a not acceptable frequency value at output. 

2.- When CF function is activated, maximum power output is de-rated to 60% of maximum nominal capacity. For example, for a 3K 

model, when CF is activated, maximum output is decreased to 1.8K. 

 

ECO:

  

Under this mode, Inverter powers outputs from the AC input. This is a kind of supervised BYPASS mode. As soon as AC input is out of 

acceptable input range for ECO mode (as defined on LCD configuration menus), Inverter switch Inverter from ECO to ONLINE mode or 

battery mode. Online mode is adopted if input range is acceptable for ONLINE mode. Switching from ECO to other mode takes about 

4ms to10ms. 

ECO mode must be activated on LCD according to configuration section of this manual. 
 

 

 

Summary of Contents for Xmart LBU-ONL 1.5K

Page 1: ...n this manual is property of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or...

Page 2: ...PRODUCT DESCRIPTION 3 SAFETY QUALITY AND PERFORMANCE STANDARDS 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 Inverter CONFIGURATION 8 ERROR ALARMS CODES 9 TROUBLESHOOTING 10 SO...

Page 3: ...ect this Inverter to any of its own power outlets this could damage the unit permanently WARNING Do not connect AC motor based equipment without a careful sizing of the Inverter based on inrush curren...

Page 4: ...14001 2015 TRANSPORTATION IEC EN 60068 2 32 Drop Test IEC EN 60068 2 64 Vibration Test IEC EN 60068 2 27 Shock Test WARNING Modifications made on the product or the use of this product as a part of a...

Page 5: ...to drive maximum rated current For 3KVA Inverter in 120V wires must be minimum 12AWG for lengths shorter than 15m 50 feet Wiring gauge is conditioned to length temperature etc Wiring must be selected...

Page 6: ...ace Inverter module close to original XMART Batteries Array 2 If there are check all Battery DC switches are in OFF position 3 Connect Inverter to first Battery String by using original DC cable 4 In...

Page 7: ...ncludes 2 serial ports USB RS232 Additionally there is also a Smart Port to support different communication cards such as LAN SNMP card Dry Contacts card RS 485 card among others RS232 COMMUNICATION P...

Page 8: ...s mode is adopted in case ON button has not been activated as soon as Inverter detects a valid AC input on its terminals If bypass mode is not enabled Inverter will simply light its LCD Outputs will k...

Page 9: ...r output is generated by inverter BATTERY MODE A Input indicator at bottom left corner A shows Battery voltage since there is no valid AC input detected B Output indicator displays AC output generated...

Page 10: ...ll checking of systems and batteries OFF ENTER Inverter TURN OFF Press for 2 seconds to turn Inverter off ENTER When Inverter is in configuration mode this key operates as ENTER SELECT CHECK VALUES In...

Page 11: ...INFORMATION Displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also shows r...

Page 12: ...ammable output powered 5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area graphically displays the power supplied by the Inverter with a 4 s...

Page 13: ...ODE ON MUTE Used as key to navigate or changing parameters value OFF ENTER Used as ENTER key to confirm modifications SELECT Used as key to navigate or changing parameters value CONFIGURATION MENU For...

Page 14: ...c Set values with keys 06 BYPASS ENABLE DISABLE Enables or disables BYPASS function when Inverter is off ENA ENABLE DIS DISABLE Factory set DIS 07 BYPASS INPUT VOLTAGE RANGE Valid input VOLTAGE range...

Page 15: ...maximum recharging current in Amps 1 2 4 6 or 8 A Factory set 2 A 14 BOOSTING CHARGING VOLTAGE NO MODIFICATIONS RECOMMENDED ONLY FOR TECHNICIANS Charging voltage can be increased Adjustable Voltage 2...

Page 16: ...DESCRIPTION AO Active Open AC Active Close BAH Battery AH BAT Battery BR Battery Replacement CBV Charger Boost Voltage CFV Charger Float Voltage CF Frequency Converter Function CHA Charger current CH...

Page 17: ...nd codes with intermittent beeps Tipo de ALARMA SIMBOLO INTERMITENTE ALARMA SONORA OVERLOAD Inverter Load exceeds Inverter capacity 1 beep s LOW BATTERY 1 beep 2s BATTERY FAULT 1 beep 2s BATTERY REPLA...

Page 18: ...the Inverter FAILURE CODE ICON BUS START FAIL 01 BUS OVER 02 BUS UNDER 03 Inverter SOFT START FAIL 11 Inverter VOLTAGE HIGH 12 Inverter VOLTAGE LOW 13 Inverter OUTPUT SHORT 14 BATT VOLTAGE TOO HIGH 2...

Page 19: ...n EEPROM Failure Turn off and power off Inverter Restart Inverter If not solved call technical service ERROR CODES PROBABLE CAUSE SOLUCION 01 02 03 Turn off and power off Inverter Disconnect all equip...

Page 20: ...ating Inverter with higher room temperatures will short dramatically battery life IMPORTANT RECHARGING PLAN FOR LONG STORAGE If Inverter and batteries are going to be stored for long time it is mandat...

Page 21: ...charger uses a 3 steps algorithm to care batteries 1 Constant Current During this stage charger injects a constant current meanwhile batteries increase their voltage During this stage batteries recove...

Page 22: ...bution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is o...

Page 23: ...xmart Inverter com VER 2211 17 One ENG 23 14 REAR PANEL 1 Standard Inverter Outlets 2 Programmable Outlets 3 AC Input 4 Surge Protected RJ45 sockets 5 Emergency Power Off connector 6 USB RS232 7 Smart...

Page 24: ...USER MANUAL LBU ONL 1 5K 2 25K 3K 4 5K www xmart Inverter com VER 2211 17 One ENG 24 15 SPECIFICATIONS 1 2...

Page 25: ...emperatura Almacenaje UPS w o batteries 25 to 55 C UPS with batteries 20 to 50 C CEE Schuko 1 CEE Schuko 2 CEE Schuko 2 L5 30P NEMA5 20P CE IEC EN 62040 1 RoHS ISO9001 ISO14001 IEC EN 61000 2 2 IP21 F...

Page 26: ...n though this inverter can manage battery discharge until 10 5VDC per battery we recommend not using this feature up to the limit but using a higher cut off voltage instead This will give a shorter ba...

Page 27: ...100AH 100AH OF STRINGS 1 2 3 1 2 3 1 2 TOTAL CURRENT 45A 90A 135A 65A 130A 195A 100A 200A 100 550 1180 1768 790 1580 2372 1235 2470 200 225 552 858 374 795 1190 590 1290 300 128 345 575 250 535 825 38...

Page 28: ...2 3 4 1 2 3 1 2 TOTAL CURRENT 45A 90A 135A 180A 65A 130A 195A 100A 200A 150 430 970 1460 1950 655 1306 1960 1020 2040 300 194 490 765 1070 340 720 1075 523 1121 450 120 318 525 740 240 500 770 360 775...

Page 29: ...F STRINGS 1 2 3 1 2 3 1 2 TOTAL CURRENT 45A 90A 135A 65A 130A 195A 100A 200A 200 670 1 340 2 000 655 1 306 1 960 1050 2000 400 345 730 1 090 340 720 1 075 540 1140 600 240 510 760 240 500 770 360 780...

Page 30: ...100AH OF STRINGS 1 2 3 1 2 3 1 2 TOTAL CURRENT 45A 90A 135A 65A 130A 195A 100A 200A 300 450 1025 1500 690 1300 2000 1080 2100 600 200 500 780 350 740 1100 540 1150 900 122 325 540 245 520 800 365 790...

Page 31: ...USA Miami FL 33196 USA sales xmart Inverter com EUROPE Sabadell Barcelona 08202 Spain sales xmart Inverter com LATAM Santiago de Chile Chile sales xmart Inverter com...

Reviews: