BATTERIES: RECHARGING 

 

This Inverter includes a powerful and modern battery charger powered by AC input 

 

Charger Configuration: 

Maximum recharging current can be configured in the LCD frontal panel. Maximum current must be configured according to the capacity 

of the battery bank. 

 

Maximum current must be between 10% and 20% of the total AH battery capacity.  

For example, for a small 9AH battery bank, the minimum current should be 0.1C (about 0.9A). In this case, charger should be configured 

as 1A.  

To get shorter recharging time current could be configured close to its maximum value 0.2C (1.8A). In this case, charger should be 

configured as 2A. 

 

Recharging Algorithm 

This Inverter battery charger uses a 3 steps algorithm to care batteries. 

 

1-

 

Constant Current  

During this stage charger injects a constant current meanwhile batteries increase their voltage. During this stage batteries 

recover up to 90% of their total capacity. This stage takes 60% of total recharging time. 

 

2-

 

Constant Voltage 

When first step is finished charger provides stable voltage meanwhile current decreases slowly. The charging voltage for 

VRLA/AGM batterie is close to 2.35Vdc per cell (14.1 VDC per battery). In this stage batteries recover 100% of their capacity. 

 

3-

 

Floating 

This is stage where batteries keep charged with 2.25VDC per cell (13.5VDC per battery) 

 

 

 

TEMPERATURE COMPENSATION 

 Batteries should be recharged with a room temperature under 30ºC. In case temperature rises above 30ºC, charger decreases charging 

voltage to protect batteries as follows: 

 

Over 30ºC: 

-5mV/ºC per cell (-30mV/ºC per battery) during constant voltage stage 

-3mV/ºC per cell (-18mV/ºC per battery) during floating stage 

 

 

 

Summary of Contents for Xmart LBU-ONL 1.5K

Page 1: ...n this manual is property of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or...

Page 2: ...PRODUCT DESCRIPTION 3 SAFETY QUALITY AND PERFORMANCE STANDARDS 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 Inverter CONFIGURATION 8 ERROR ALARMS CODES 9 TROUBLESHOOTING 10 SO...

Page 3: ...ect this Inverter to any of its own power outlets this could damage the unit permanently WARNING Do not connect AC motor based equipment without a careful sizing of the Inverter based on inrush curren...

Page 4: ...14001 2015 TRANSPORTATION IEC EN 60068 2 32 Drop Test IEC EN 60068 2 64 Vibration Test IEC EN 60068 2 27 Shock Test WARNING Modifications made on the product or the use of this product as a part of a...

Page 5: ...to drive maximum rated current For 3KVA Inverter in 120V wires must be minimum 12AWG for lengths shorter than 15m 50 feet Wiring gauge is conditioned to length temperature etc Wiring must be selected...

Page 6: ...ace Inverter module close to original XMART Batteries Array 2 If there are check all Battery DC switches are in OFF position 3 Connect Inverter to first Battery String by using original DC cable 4 In...

Page 7: ...ncludes 2 serial ports USB RS232 Additionally there is also a Smart Port to support different communication cards such as LAN SNMP card Dry Contacts card RS 485 card among others RS232 COMMUNICATION P...

Page 8: ...s mode is adopted in case ON button has not been activated as soon as Inverter detects a valid AC input on its terminals If bypass mode is not enabled Inverter will simply light its LCD Outputs will k...

Page 9: ...r output is generated by inverter BATTERY MODE A Input indicator at bottom left corner A shows Battery voltage since there is no valid AC input detected B Output indicator displays AC output generated...

Page 10: ...ll checking of systems and batteries OFF ENTER Inverter TURN OFF Press for 2 seconds to turn Inverter off ENTER When Inverter is in configuration mode this key operates as ENTER SELECT CHECK VALUES In...

Page 11: ...INFORMATION Displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also shows r...

Page 12: ...ammable output powered 5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area graphically displays the power supplied by the Inverter with a 4 s...

Page 13: ...ODE ON MUTE Used as key to navigate or changing parameters value OFF ENTER Used as ENTER key to confirm modifications SELECT Used as key to navigate or changing parameters value CONFIGURATION MENU For...

Page 14: ...c Set values with keys 06 BYPASS ENABLE DISABLE Enables or disables BYPASS function when Inverter is off ENA ENABLE DIS DISABLE Factory set DIS 07 BYPASS INPUT VOLTAGE RANGE Valid input VOLTAGE range...

Page 15: ...maximum recharging current in Amps 1 2 4 6 or 8 A Factory set 2 A 14 BOOSTING CHARGING VOLTAGE NO MODIFICATIONS RECOMMENDED ONLY FOR TECHNICIANS Charging voltage can be increased Adjustable Voltage 2...

Page 16: ...DESCRIPTION AO Active Open AC Active Close BAH Battery AH BAT Battery BR Battery Replacement CBV Charger Boost Voltage CFV Charger Float Voltage CF Frequency Converter Function CHA Charger current CH...

Page 17: ...nd codes with intermittent beeps Tipo de ALARMA SIMBOLO INTERMITENTE ALARMA SONORA OVERLOAD Inverter Load exceeds Inverter capacity 1 beep s LOW BATTERY 1 beep 2s BATTERY FAULT 1 beep 2s BATTERY REPLA...

Page 18: ...the Inverter FAILURE CODE ICON BUS START FAIL 01 BUS OVER 02 BUS UNDER 03 Inverter SOFT START FAIL 11 Inverter VOLTAGE HIGH 12 Inverter VOLTAGE LOW 13 Inverter OUTPUT SHORT 14 BATT VOLTAGE TOO HIGH 2...

Page 19: ...n EEPROM Failure Turn off and power off Inverter Restart Inverter If not solved call technical service ERROR CODES PROBABLE CAUSE SOLUCION 01 02 03 Turn off and power off Inverter Disconnect all equip...

Page 20: ...ating Inverter with higher room temperatures will short dramatically battery life IMPORTANT RECHARGING PLAN FOR LONG STORAGE If Inverter and batteries are going to be stored for long time it is mandat...

Page 21: ...charger uses a 3 steps algorithm to care batteries 1 Constant Current During this stage charger injects a constant current meanwhile batteries increase their voltage During this stage batteries recove...

Page 22: ...bution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is o...

Page 23: ...xmart Inverter com VER 2211 17 One ENG 23 14 REAR PANEL 1 Standard Inverter Outlets 2 Programmable Outlets 3 AC Input 4 Surge Protected RJ45 sockets 5 Emergency Power Off connector 6 USB RS232 7 Smart...

Page 24: ...USER MANUAL LBU ONL 1 5K 2 25K 3K 4 5K www xmart Inverter com VER 2211 17 One ENG 24 15 SPECIFICATIONS 1 2...

Page 25: ...emperatura Almacenaje UPS w o batteries 25 to 55 C UPS with batteries 20 to 50 C CEE Schuko 1 CEE Schuko 2 CEE Schuko 2 L5 30P NEMA5 20P CE IEC EN 62040 1 RoHS ISO9001 ISO14001 IEC EN 61000 2 2 IP21 F...

Page 26: ...n though this inverter can manage battery discharge until 10 5VDC per battery we recommend not using this feature up to the limit but using a higher cut off voltage instead This will give a shorter ba...

Page 27: ...100AH 100AH OF STRINGS 1 2 3 1 2 3 1 2 TOTAL CURRENT 45A 90A 135A 65A 130A 195A 100A 200A 100 550 1180 1768 790 1580 2372 1235 2470 200 225 552 858 374 795 1190 590 1290 300 128 345 575 250 535 825 38...

Page 28: ...2 3 4 1 2 3 1 2 TOTAL CURRENT 45A 90A 135A 180A 65A 130A 195A 100A 200A 150 430 970 1460 1950 655 1306 1960 1020 2040 300 194 490 765 1070 340 720 1075 523 1121 450 120 318 525 740 240 500 770 360 775...

Page 29: ...F STRINGS 1 2 3 1 2 3 1 2 TOTAL CURRENT 45A 90A 135A 65A 130A 195A 100A 200A 200 670 1 340 2 000 655 1 306 1 960 1050 2000 400 345 730 1 090 340 720 1 075 540 1140 600 240 510 760 240 500 770 360 780...

Page 30: ...100AH OF STRINGS 1 2 3 1 2 3 1 2 TOTAL CURRENT 45A 90A 135A 65A 130A 195A 100A 200A 300 450 1025 1500 690 1300 2000 1080 2100 600 200 500 780 350 740 1100 540 1150 900 122 325 540 245 520 800 365 790...