USER MANUAL - LBU-ONL 1.5K/2.25K/3K/4.5K
VER.2211.17-One (ENG)
14
03
CF: FREQUENCY OUTPUT VALUE
- If CF Mode is Disabled, PAR 02 shows BAT and Initial frequency at Battery mode
can be set to:
BAT 50 = 50Hz
BAT 60 = 60Hz
- If CF Mode is Enabled, PAR 02 shows CF and Output Frequency in ONLINE mode can
be set as:
CF 50 = 50Hz
CF 60 = 60Hz
04
ECO ENABLE / DISABLE:
ENA = ENABLE
DIS = DISABLE
Factory set: DIS
Check more details at operation modes section.
05
ECO
–
INPUT VOLTAGE RANGE (Vac)
- Valid input VOLTAGE range for ECO mode can be configured by setting high limit
and low limit (PAR 02):
HLS: High Limit Setting (in Vac)
220V Models: HLS from +7 to +24Vac of nominal voltage (Factory set: +12Vac)
120V Models: HLS from +3 to +12Vac of nominal voltage (Factory set: +6Vac)
LLS: Low Limit Setting (in Vac)
Models 220V: LLS from -7 to -24Vac of nominal voltage (Factory set: -12Vac)
Models 120V: LLS from -3 to -12Vac of nominal voltage (Factory set: -6Vac)
Set values with keys:
&
06
BYPASS: ENABLE / DISABLE:
- Enables or disables BYPASS function when Inverter is off.
ENA = ENABLE
DIS = DISABLE
Factory set: DIS
07
BYPASS: INPUT VOLTAGE RANGE
- Valid input VOLTAGE range for bypass mode can be configured by setting high limit
and low limit (PAR 02):
HLS: High Limit Setting (in Vac)
220V Models: HLS 230Vac
–
264Vac (Factory set as 264Vac)
120V Models: HLS 120Vac
–
140Vac (Factory set as 132Vac)
LLS: Low Limit Setting (in Vac)
220V Models: LLS 170Vac
–
220Vac (Factory set as 170Vac)
120V Models: LLS 85Vac
–
115Vac (Factory set as 85Vac)
Set values with keys:
&
08
BYPASS: INPUT FREQUENCY RANGE
- Valid input FREQUENCY range for bypass mode can be configured by setting high
limit and low limit (PAR 02):
HLS: High Limit Setting (in Vac)
50Hz Models: HLS 51Hz
–
55Hz (Factory set as 53Hz)
60Hz Models: HLS 61Hz
–
65Hz (Factory set as 63Hz)
LLS: Low Limit Setting (in Vac)
50Hz Models: LLS 45Hz
–
49Hz (Factory set as 47Hz)
60Hz Models: LLS 55Hz
–
59Hz (Factory set as 57Hz)
Set values with keys:
&
09
PROG-OUTPUT: ENABLE / DISABLE PROGRAMMABLE OUTPUTS:
Enables/disables programable output (check Parameter 10)
ENA : ENABLE
DIS : DISABLE
Factory set: DIS