USER MANUAL - LBU-ONL 1.5K/2.25K/3K/4.5K
VER.2211.17-One (ENG)
15
10
PROG-OUTPUT: MAXIMUM RUNTIME FOR PROGRAMMABLE OUTLETS:
0-999: Time in minutes for programable outlets in Battery mode (if function 10 is
enable).
Factory set: 999 min.
This setting does not affect runtime for standard Inverter outlets.
11
MAXIMUM RUNTIME:
This function sets maximum time in Battery mode for standard outlets.
000 a 999: Max. Time in minutes.
DIS: Disable. Runtime will be limited by Battery charge level only.
Factory set: DIS
Set values with keys:
&
12
BATTERY CAPACITY IN AH:
This function must be adjusted only if external batteries are connected to the Inverter.
Adjusted value must describe total AH (in external) connected to Inverter.
For example, if Inverter has internal bank of 9AH and other external 9AH battery bank
is connected, the value to be set is 18AH.
0-999: value can be set 7AH to 999AH
13
BATTERY CHARGER CURRENT:
Sets maximum recharging current in Amps (1, 2, 4, 6 or 8 A)
Factory set: 2 A
14
BOOSTING CHARGING VOLTAGE:
** NO MODIFICATIONS RECOMMENDED
–
ONLY FOR TECHNICIANS **
Charging voltage can be increased
Adjustable Voltage: 2.25V per cell up to 2.40V per cell
6 cells per battery
Factory set: 2.36V/cell
→
2.36*6= 14.16V per battery
15
FLOATING CHARGING VOLTAGE:
** NO MODIFICATIONS RECOMMENDED
–
ONLY FOR TECHNICIANS **
Charging voltage can be increased
Adjustable Voltage: 2.20V per cell up to 2.33V per cell
6 cells per battery
Factory set: 2.28V/cell
→
2.28*6= 13.68V per battery
16
EPO LOGIC
** NO MODIFICATIONS RECOMMENDED
–
ONLY FOR TECHNICIANS **
AO: Active Open: If EPO switch is open Inverter will power-off outputs
AC: Active Closed: If External EPO switch is closed, Inverter will power-off their
outputs
Factory set: Active Open
17
ISOLATION TRANSFORMER (optional):
ENA: Allows connection of an output ISO transformer
DIS: Does not allow connection of an ISO transformer
Factory set: DIS
18
AUTONOMY TIME ON LCD:
EAT (Estimated Autonomy Time): LCD will show remaining runtime in battery mode
RAT (Running Autonomy Time): LCD will show running time in battery mode
Factory set: EAT