5. CONFIGURATION

 

 

      

 

Any configuration modification must be applied with UPS connected to AC line but in OFF or STAND-BY mode. 
This UPS can be configured to work under some different modes. Some important functions can also be configured in CONFIGURATION 
MODE: 
 

a)

 

Normal Mode: Also known as AC MODE. Under this mode UPS works as ONLINE UPS. UPS outlets are supplied by AC power 
generated by UPS inverter circuit offering a clean power to your devices. 

 

b)

 

ECO Mode: Under this mode UPS works as OFF-LINE UPS. UPS outlets are supplied by AC input source. UPS supervises input 
source to switch to ONLINE mode only when input source is out of range This is not a recommendable mode for those critical 
applications that require ONLINE UPS. 
Default mode set as factory is NORMAL MODE (Online UPS).  

 

c)

 

Output Voltage: It can be configured to any of 4 available values: 

 

In 120Vac Models: 110Vac, 115Vac, 120Vac, 127Vac,  

 

In 220Vac Models: 208Vac, 220Vac, 230Vac ó 240Vac 

 

d)

 

Output Frequency: It can be selected to 50Hz or 60Hz. Default configuration allows auto-selection to match with frequency of 
input AC source. NOTE: When conversion frequency mode is activated UPS power capacity could be reduced 

 

e) Programmable Outputs: There are 2 groups of outlets: 
 

 

Standard Outlets: They work as expected in any UPS. This kind of outlets under battery keep powered until batteries reach very low 

level or up to UPS receives power off command from software. 

 

Programmable Outlets: If programmable outlets function is configured, programmable outlets can be powered off by internal timer 
before UPS detects very low battery level. Most common application for programmable outlets is for connecting non critical devices 

to them so that backup time can be longer for those critical devices connected in standard outlets. 

 
 
 

6. OPERATION

 

 

      

 
This is UPS is ONLINE DOUBLE CONVERSION type and it has been designed to offer the most clear power without switching transitions or 
dead times. In that way your hardware but also your valuable data will be safe when your PC related equipment is connected to EPRO 
series UPS. 

Power output is sine-wave type same as supplied by AC main source. 
Depending of AC input source, this UPS can work under one of two following modes: 
 
Stand-By Mode:  UPS  goes  to  Stand-By  mode  when  it  is  just  connected  to  AC  input  source.  BYPASS  mode  must  not  be  previously 
activated. If BYPASS is activated, UPS will go to BYPASS mode just after UPS is connected to input source. 

 
Normal AC Mode (Online) : It is the default mode when AC input source is OK and ON button is selected.  If ON button is not selected, UPS 
will remain in stand-by mode or bypass (if bypass has been configured as ENABLE) 
Under normal online  mode, power output is generated by UPS inverter. Inverter takes power from AC/DC converter feed by AC input 
source. AC input source is only used under this mode to recharging batteries when necessary. 

 
Battery Mode: Also known as Inverter Mode. It is the mode when AC input source is out of range or black-out is detected by the UPS. 
Under this mode power output is generated by UPS inverter that takes power from batteries. 
There is no dead time (transition time is ZERO ms) related to switching from normal mode to battery mode since load is always powered 
from inverter. This is main characteristic of an ONLINE UPS. 

 
BYPASS Mode: Bypass is a working state where UPS supply outlets directly from input AC source. In this mode Inverter does not supply 
outlets from inverter. 
Bypass mode can be forced by user from Online mode by selecting ON & SELECT buttons at same time during 5 minutes. It can be also 
activated by configuring BYPASS as enable in configuration menu and connecting UPS to AC source without activating ON button. 
Bypass mode can be also forced in automatic way by UPS in case it detects external overload or internal failure. 

 
ECO Mode: This UPS also offer a third operation mode name ECO MODE. Under this mode (selectable by LCD configuration menu) UPS 
works as OFF-LINE UPS. Load is powered from AC input and UPS only switch to battery mode when input is out of range or in black-out 
status. Transition time from ECO mode to Battery mode is not zero. Typically is about 4ms that is why ECO Mode is not recommended for 
critical applications. 

 

 

Summary of Contents for EPRO 1.5K

Page 1: ...DOUBLE CONVERSION UPS Technical information on this manual is property of INTEGRA This manual Information cannot be copied or distributed totally or partially without written approval of INTEGRA INTEG...

Page 2: ...Inverter Technology Full Bridge isolated neutral Main Features of Full Brdige UPS Output Neutral is not connected to Input Neutral in normal Online mode That generates a floating voltage between outpu...

Page 3: ...with care Do not block UPS ventilation WARNING Make sure to connect this unit to proper power line according to selected model The UPS Technical Specs sticker shows power rating information DO NOT co...

Page 4: ...ient burst immunity IEC EN 61000 4 4 Level 4 Surge immunity IEC EN 61000 4 5 Level 4 Conducted Immunity IEC EN 61000 4 6 Power frequency magnetic field immunity IEC EN 61000 4 8 Voltage Dips Short Int...

Page 5: ...cording to the model In terms of communication you have a wide range of alternatives like RS 232 USB Ethernet LAN or AS 400 interface some of them are optional Please follow carefully this manual duri...

Page 6: ...PS This kind of damage is not covered by warranty FIG 1 For all full bridge models 1KF 3KF 1KF CN to 3KF CN it is not allowed to connect output Neutral to system Ground This practice will generate int...

Page 7: ...trongly affected by length and temperature Input wire must be selected and installed by qualified personnel according to local regulations 2 First time leave UPS recharging batteries during 6 hours be...

Page 8: ...must be sure about the kind of EXBATT to be connected to UPS In case of doubts we recommend to revise product label and instructions of this manual MODELO VOLTAJE DC MODELO VOLTAJE DC MODELO VOLTAJE...

Page 9: ...sitions or dead times In that way your hardware but also your valuable data will be safe when your PC related equipment is connected to EPRO series UPS Power output is sine wave type same as supplied...

Page 10: ...ency as selected BATTERY MODE When AC input source is out of range Ups goes to battery mode to supply output from taking energy from batteries BYPASS If UPS is overloaded by big consuming load connect...

Page 11: ...abnormal battery situation 2 Indicates UPS time under battery mode H hours M minutes S seconds 3 Alert triangle symbol indicates alarm or error Two 2 digits code indicates error alarm code 4 This symb...

Page 12: ...NT FUNCTIONS AND OPTIONS CONFIGURATION MENU BY MODEL FUNCTION EPRO 1K 1 5K 2K 3K EPRO F 1KF 2KF 3KF EPRO F CN 1KFCN 2KFCN 3KFCN 00 ESC screen ESC screen ESC screen 01 Output Voltage Setting Output Vol...

Page 13: ...____________________________________________________________________________________________ www integra ups com 1305 EPRO 1K 3K 13 MODEL EPRO F CN 1KF CN 2KF CN 3KF CN Screens for 230V models 120V mo...

Page 14: ...__________________________________________________________________________________________________ www integra ups com 1305 EPRO 1K 3K 14 MODEL EPRO F 1KF 2KF 3KF Screens for 230V models 120V models h...

Page 15: ...__________________________________________________________________________________________________ www integra ups com 1305 EPRO 1K 3K 15 MODEL EPRO 1K 1 5K 2K 3K Screens for 230V models 120V models h...

Page 16: ...re 41 x Overload UPS power output capacity has been exceeded Inverter cannot supply output 43 11 ALARMS ON LCD ALARM Description ICON on LCD Beep Alarm Low battery 1 s Overload hi power consumption de...

Page 17: ...re Batteries and charger must be inspected by qualified personnel Code 28 Active Continuous beep Very low voltage at batteries or charger failure Batteries and charger must be inspected by qualified p...

Page 18: ...ftware CD inside the box For others software downloading is available from our website Download always software user manual and follow it carefully during software installation 14 BATTERIES MAINTENANC...

Page 19: ...whichever is longer 5 INTEGRA or their distribution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons...

Page 20: ...UPS Outlets 9 SNMP Smart Port 3 AC Input 10 External Battery Connector EXBATT 4 Input Breaker 11 AC Output Terminal Block 5 RJ45 Surge Protected Sockets 12 Output Breaker 6 Emergency Power Off Connec...

Page 21: ...do del UPS Consumo Bater as Voltaje Entrada Salida Autonom a Diagnostico Fallas INDICATORS INDICADORES LCD ALARM ALARMAS Alarm Beep Alarma Sonora 1 0 A Max x 12V 9Ah x 12 12V 9Ah x 12 x Battery Mode L...

Page 22: ...n Frequency converter mode is activated When the output voltage is adjusted to 208VAC in 220Vac models output capacity derates to 80 La capacidad en VA Watts se degrada y baja hasta el 60 en modo Conv...

Page 23: ...r and Fault conditions Estado del UPS Consumo Bater as Voltaje Entrada Salida Autonom a Diagnostico Fallas Battery Mode Low batt Overload UPS Failure Modo Bater a Baja bater a Sobrecargas Falla N N N...

Page 24: ...ada se mantenga entre 40 y 70 Hz Derate capacity to 60 of total capacity when Frequency converter mode is activated When the output voltage is adjusted to 208VAC in 220Vac models output capacity derat...