13. SOFTWARE
Our control software offers huge capabilities to monitor your UPS and configure key shutdown parameters. Also event and data log are
available in software options.
Main software features are:
•
Friendly human interface to UPS.
•
Controlled files saving and OS shutdown when blackout is detected.
•
Configurable scheduled shutdown and Auto-tests
Some UPS models include software CD inside the box. For others software downloading is available from our website.
Download always software user manual and follow it carefully during software installation.
14. BATTERIES: MAINTENANCE AND CARE
When battery backup time is noticeable shorter it is time to replace batteries. To get longer lifetime we recommend applying a deep
discharge every 3 months. Operation temperature should be below 25ºC.
IMPORTANT: RECHARGING PLAN DURING LONG STORAGE
When UPS is storage periodic recharge must be performed as indicated in below table.
Long storage without recharging will damage batteries. This kind of problem is not covered by original product warranty.
Storage Temperature
Recharge Frequency
Recharge Time
-25°C to +30°C
3 months
6 hours
+30°C to +45°C
2 months
6 hours