17. ESPECIFICACIONES (1KF / 2KF / 3KF) & (1KF-CN / 2KF-CN / 3KF-CN) (1/2)
INPUT / ENTRADA
Freq. Range / Rango Frecuencia
Slew Rate / Seguimiento de F.
Surge Immunity Level
Output Regulation / Rango de Salida
Freq. Conversion / Conversión Frec.
EPO /Apagado Emergencia
Progammable Outputs / Salidas Prog.
Eco Mode
AC Mode / Modo Normal
Output Shortcircuit / Cortocircuito en Salida
Battery Mode / Modo Batería
Type / Tipo
Cap. & Qty
Recharge Time / Recarga
Charging Voltage / Voltaje de Carga
Charging Amps / Corriente de Carga
EXT. BATT CABINETS (Optional) - BATERIAS EXTERNAS (opcionales)
Standard EXT-BATT pack
> 7KV (EN61000-4-5)
27.4Vdc
54.7Vdc
82.1Vdc
100%~110%: (warning-alarma) / 110%~130%: 30s: shutdown / >130% : 1s: shutdown
100%~110%: (warning-alarma) / 110%~130%: 1min: bypass / >130% : 1s: bypass
Full Protection for all outlets / Protección en todas las salidas
Sealed Lead Acid VRLA-AGM / Sellada de Libre Mantenimiento VRLA-AGM
4 Hours for 90% capacity / 4 Horas para recuperar el 90% de carga
UPS status, Load level, Battery, Input/Output voltage, Discharge timer, and Fault conditions
Estado del UPS, Consumo, Baterías, Voltaje Entrada/Salida, Autonomía, Diagnostico Fallas
Battery Mode, Low batt., Overload, UPS Failure / Modo Batería, Baja batería, Sobrecargas, Falla
N
N
N
N
> 86%
Model 120V: 80Vac-150Vac (@ 100% load)
Model 120V: 50Vac-150Vac (@ 50% load)
Model 220V: 160Vac-300Vac (@ 100% load)
Model 220V: 110Vac-300Vac (@ 50% load)
N
> 93%
> 89%
(*N3) 50 Hz +/- 0.25 Hz - 60Hz +/- 0.3 Hz
3:1 @ 100% load
N
12V/9AH x 2
> 89%
> 93%
> 93%
N
800W
12V/9AH x 4
1.0 A (Max.)
12V-9Ah x 8
40 Hz - 70Hz
Single phase with ground / 1 fase + Tierra
> 0.99 @ 100% load
2000VA
3000VA
2400W
(*N1) Model 120V: 110/115/120/127Vac - Model 220V: 208/220/230/240Vac
+/-1%
> 88%
< 3% @ Linear Load / Carga Lineal
<6% @ No Linear Load / Carga no Lineal
> 90%
> 89%
0 ms
1KF & 1KF-CN
2KF & 2KF-CN
Range / Rango - Vac (Models 220V):
Harmonic Distortion /
Dist. Armónica (THDv)
EFFICIENCY / EFICIENCIA
AC Mode / Modo AC
< 7% @ 100% load
1 Hz / s
3KF & 3KF-CN
1000VA
Voltage Output / Voltaje de Salida AC
Capacity / Capacidad (W)
Input THDi / THDi de Entrada
1600W
x
12V-9Ah x 12
12V/9AH x 6
Pure Sinewave / Sinusoidal Pura
N
N
OUTPUT / SALIDA
Phase / Fases
Power Factor / Factor de Potencia
ONLINE UPS (1/2)
Range / Rango - Vac (Models 120V):
Capacity / Capacidad (VA)
Frequency / Frecuencia (Batt. Mode)
AC to Inverter / Tiempo AC a Inversor
Waveform / Forma de Onda
BATTERIES / BATERIAS
LCD
OVERLOAD/ SOBRECARGA
Current Crest Ratio / Factor de Cresta
Battery Mode / Modo Batería
INDICATORS / INDICADORES
ALARM / ALARMAS
Alarm Beep / Alarma Sonora: