Station ID Table. 

The following table assists with the setting up of DIP switches for the required Station ID (Station number). 

STATION 

ID 

DIP SWITCH SETTINGS 

  

 

 

SW1 SW2 SW3 SW4 SW5 SW6 SW7 

OFF OFF OFF OFF OFF OFF OFF 

ON  OFF OFF OFF OFF OFF OFF 

OFF  ON  OFF OFF OFF OFF OFF 

ON  ON  OFF OFF OFF OFF OFF 

OFF OFF  ON  OFF OFF OFF OFF 

ON OFF ON OFF OFF OFF OFF 

OFF  ON  ON  OFF OFF OFF OFF 

ON ON ON OFF 

OFF 

OFF 

OFF 

OFF OFF OFF  ON  OFF OFF OFF 

ON OFF OFF ON OFF OFF OFF 

10  OFF ON OFF ON OFF OFF OFF 

11 

ON  ON OFF ON OFF OFF OFF 

12 

OFF OFF  ON  ON  OFF OFF OFF 

13 

ON OFF ON  ON OFF OFF OFF 

14  OFF ON ON ON OFF 

OFF 

OFF 

15  ON ON ON ON OFF 

OFF 

OFF 

16 

OFF OFF OFF OFF  ON  OFF OFF 

17 

ON  OFF OFF OFF  ON  OFF OFF 

18  OFF ON OFF OFF ON OFF OFF 

19 

ON  ON OFF OFF ON OFF OFF 

20  OFF OFF ON OFF ON OFF OFF 

21 

ON OFF ON OFF ON OFF OFF 

22  OFF ON  ON OFF ON OFF OFF 

23  ON ON ON OFF ON OFF 

OFF 

24 

OFF OFF OFF  ON  ON  OFF OFF 

25 

ON OFF OFF ON  ON OFF OFF 

26  OFF ON OFF ON  ON OFF OFF 

27  ON ON OFF ON ON OFF 

OFF 

28  OFF 

OFF ON ON ON OFF 

OFF 

29  ON OFF ON ON ON OFF 

OFF 

30  OFF ON ON ON ON OFF 

OFF 

31  ON ON ON ON ON OFF 

OFF 

32 

OFF OFF OFF OFF OFF  ON  OFF 

33 

ON  OFF OFF OFF OFF  ON  OFF 

34 

OFF  ON  OFF OFF OFF  ON  OFF 

35 

ON  ON  OFF OFF OFF  ON  OFF 

36 

OFF OFF  ON  OFF OFF  ON  OFF 

37 

ON OFF ON OFF OFF ON OFF 

38  OFF ON  ON OFF OFF ON OFF 

39  ON ON ON OFF 

OFF ON OFF 

40 

OFF OFF OFF  ON  OFF  ON  OFF 

41 

ON OFF OFF ON OFF ON OFF 

42  OFF ON OFF ON OFF ON OFF 

43 

ON  ON OFF ON OFF ON OFF 

44  OFF OFF ON  ON OFF ON OFF 

45 

ON OFF ON  ON OFF ON OFF 

46  OFF ON ON ON OFF ON OFF 

47  ON ON ON ON OFF ON OFF 

48 

OFF OFF OFF OFF  ON  ON  OFF 

49 

ON  OFF OFF OFF  ON  ON  OFF 

50  OFF ON OFF OFF ON  ON OFF 

STATION 

ID 

DIP SWITCH SETTINGS 

  

 

 

SW1 SW2 SW3 SW4 SW5 SW6 SW7 

51  ON ON OFF 

OFF ON ON OFF 

52 

OFF OFF ON OFF ON  ON OFF 

53 

ON OFF ON OFF ON  ON OFF 

54 

OFF ON  ON OFF ON  ON OFF 

55  ON ON ON OFF ON ON OFF 

56 

OFF OFF OFF  ON  ON  ON  OFF 

57  ON OFF 

OFF ON ON ON OFF 

58  OFF ON OFF ON ON ON OFF 

59  ON ON OFF ON ON ON OFF 

60  OFF 

OFF ON ON ON ON OFF 

61  ON OFF ON ON ON ON OFF 

62  OFF ON ON ON ON ON OFF 

63  ON ON ON ON ON ON OFF 

64 

OFF OFF OFF OFF OFF OFF  ON 

65 

ON  OFF OFF OFF OFF OFF  ON 

66 

OFF  ON  OFF OFF OFF OFF  ON 

67 

ON  ON  OFF OFF OFF OFF  ON 

68 

OFF OFF  ON  OFF OFF OFF  ON 

69 

ON OFF ON OFF OFF OFF ON 

70 

OFF ON  ON OFF OFF OFF ON 

71  ON ON ON OFF 

OFF 

OFF ON 

72 

OFF OFF OFF  ON  OFF OFF  ON 

73 

ON OFF OFF ON OFF OFF ON 

74 

OFF ON OFF ON OFF OFF ON 

75 

ON  ON OFF ON OFF OFF ON 

76 

OFF OFF  ON  ON  OFF OFF  ON 

77 

ON OFF ON  ON OFF OFF ON 

78 OFF 

ON 

ON 

ON 

OFF 

OFF 

ON 

79  ON ON ON ON OFF 

OFF ON 

80 

OFF OFF OFF OFF  ON  OFF  ON 

81 

ON OFF OFF OFF ON OFF ON 

82 

OFF ON OFF OFF ON OFF ON 

83 

ON  ON OFF OFF ON OFF ON 

84 

OFF OFF ON OFF ON OFF ON 

85 

ON OFF ON OFF ON OFF ON 

86 

OFF ON  ON OFF ON OFF ON 

87  ON ON ON OFF ON OFF ON 

88 

OFF OFF OFF  ON  ON  OFF  ON 

89 

ON OFF OFF ON  ON OFF ON 

90  OFF ON OFF ON  ON OFF ON 

91  ON ON OFF ON ON OFF ON 

92 OFF 

OFF 

ON 

ON 

ON 

OFF 

ON 

93 

ON OFF ON  ON  ON OFF ON 

94  OFF ON ON ON ON OFF ON 

95  ON ON ON ON ON OFF ON 

96 

OFF OFF OFF OFF OFF  ON  ON 

97 

ON  OFF OFF OFF OFF  ON  ON 

98 

OFF ON OFF OFF OFF ON  ON 

99 ON 

ON 

OFF 

OFF 

OFF 

ON 

ON 

100  OFF OFF ON OFF OFF ON  ON 

Summary of Contents for 2300-MULTI

Page 1: ...ons Communications between the computer running MicroScan V5 and the 2300 series stations is RS485 1 pair cable multi drop as standard with an option for TCP A 32bit ARM CPU is used in the 2300 series stations to provide high speed data processing and fast communications turn around times All 2300 series stations have been equipped with status led s which are used to indicate the status of the Inp...

Page 2: ... 70 71 70 71 2300 I O Remote Station 2300 I O Remote Station 2300 I O Remote Station COM TX TX 74 71 USB USB 70 COM TX TX 74 71 70 2100 IS NS RS485 Converter Isolator MicroScan V5 RS232 RS232 2300 I O Remote Station 70 71 RS485 DATA HI WAY CABLE POLARITY MUST BE OBSERVED RS485 DATA HI WAY CABLE POLARITY MUST BE OBSERVED Resistor 1k End of Data Hi way Junction Box IMPORTANT i All cables must be scr...

Page 3: ...he 2300 MULTI has no user serviceable parts Protective enclosure only to be opened by qualified personnel Remove ALL power sources before removing protective cover 1 1 Factory Configurations The Intech Micro 2300 series I O Remote Stations are factory configured to connect directly to MicroScan V5 software Only the Station number station ID needs to be set via the easily accessible dip switches No...

Page 4: ...ut Points 2 Maximum Voltage 36 Vdc Maximum Current 100 mA per output Vceon 1 1V Max Isolation Between field and logic 1500Vrms between field and logic Connectors Logic Power and Comms 4 Pin plug in connector on side of station Inputs 18 Way screw plug in connector on top of station Comms Protocols RS485 Modbus RTU Baud Rate 9600 Format 8 bit No Parity 1 Stop Power Supply Logic Supply Voltage 12 24...

Page 5: ...N OFF ON OFF 44 OFF OFF ON ON OFF ON OFF 45 ON OFF ON ON OFF ON OFF 46 OFF ON ON ON OFF ON OFF 47 ON ON ON ON OFF ON OFF 48 OFF OFF OFF OFF ON ON OFF 49 ON OFF OFF OFF ON ON OFF 50 OFF ON OFF OFF ON ON OFF STATION ID DIP SWITCH SETTINGS SW1 SW2 SW3 SW4 SW5 SW6 SW7 51 ON ON OFF OFF ON ON OFF 52 OFF OFF ON OFF ON ON OFF 53 ON OFF ON OFF ON ON OFF 54 OFF ON ON OFF ON ON OFF 55 ON ON ON OFF ON ON OFF ...

Page 6: ...ON OFF OFF ON ON ON ON 122 OFF ON OFF ON ON ON ON 123 ON ON OFF ON ON ON ON 124 OFF OFF ON ON ON ON ON 125 ON OFF ON ON ON ON ON 126 OFF ON ON ON ON ON ON 127 ON ON ON ON ON ON ON RS485 Tx RS485 Rx Power Switch 1 Switch 10 2300 MULTI Dimensions The 2300 MULTI enclosure is shown below The station clips directly onto an industry standard DIN rail Field wiring is on the top of the station via a separ...

Page 7: ... where MODBUS is required please refer to the 2300 MULTI MODBUS supplementary manual which is available for download from the Intech website www intech co nz 2300 1 3 4 2 12Vdc 115mA Pin Connection 24Vdc 58mA Comms RS485 70 71 81 82 Notes 1 Logic power input terminals 17 18 range 12 24Vdc The logic power supply input must be isolated and completely separate to the power supply that powers the 2300...

Page 8: ... between wires of a pair 50 F m Capacitance between each wire to all others bunched together 95 F m Cross talk between pairs 1kHz 100kHz 90dB 100m 50dB 100m Characteristic Impedance 100kHz 135 Attenuation of a pair 1kHz 10kHz 100kHz 50kHz 1MHz 1 5MHz 0 15dB 100m 0 42dB 100m 0 8dB 100m 0 9dB 100m 1 9dB 100m 2 4dB 100m NOTE All cables are to be subject during manufacture to in process spark testing ...