background image

14.26-4 

2300-MULTI Specifications. 

RTD Inputs: 

 

-Input Points 

 

 

 

-RTD Configuration 

2 or 3 Wire 

   -Resolution 

 0.1°C 

   -Drift 

 100ppm/°C 

Typ.

 

 

 

 

-Line resistance effect  < 0.1°C balanced 

 

 

-Max. line resistance  100ohms

 

   -Isolation 

 1500Vrms 

between 

field 

and 

logic

 

RTD Type:  

 

-Number 

 Type 

  Range 

 Accuracy

 

   -1 

 PT100 

  -200 

to 

850°C 

± 

0.3°CIEC 

751:1983

 

   -2 

 Ni120 

  -80 

to 

320°C 

± 

0.3°C

 

   -3 

 PT1000 

  -200 

to 

850°C 

± 

0.3°C

 

   -4 

 Ni1000-DIN  -200 

to 

850°C 

± 

0.3°C

 

   -5 

 Ni1000-Landys&Gyr 

 -200 

to 

850°C 

± 

0.3°C

 

   -6 

 Ohms 

  10 

400 

ohms 

± 

0.05%

 

   -7 

 Ohms 

  100-4000ohms 

± 

0.05%

 

Current Inputs:

 

 -Input 

Points 

  -Input 

Current 

0(4)~20 

mA

 

   -Input 

Resistance 

250ohms 

  -Drift 

 100ppm/°C

 

   -Input 

Type 

 Range 

 Resolution

 

   -1 

 0 

– 

4095 

 12 

bits

 

   -2 

 4~20.000mA 

1uA

 

   -3 

 +/-20.000mA 

1uA

 

   -Accuracy 

 0.2% 

of 

span 

 -Isolation 

 1000Vrms 

between 

field 

and 

logic

 

Factory Option : Voltage Inputs:

 

 

 

 

-Input Voltage 

0~1 Vdc or 0~10 Vdc   

-Input Resistance 

190kohms

 

   -Input 

Type 

 Range 

 Resolution

 

   -4 

 0 

– 

4095 

 12 

bits

 

   -5 

 0 

– 

10.000 

1mV

 

   -6 

 +/- 

 

10.000 

1mV

 

   -7 

 0 

– 

1.0000 

0.1mV

 

   -8 

 +/- 

 

1.0000 

0.1mV

 

   -Drift 

 100ppm/°C 

  -Accuracy 

 0.2% 

of 

span

 

   -Isolation 

 1000Vrms 

between 

field 

and 

logic

 

Current Output:

 

 -Output 

Points 

  -Output 

Current 

0(4)~20 

mA 

   -Output 

Type 

Range 

 Resolution

 

   -1 

 0 

– 

4095 

 12 

bits

 

   -Drift 

 100ppm/°C 

  -Accuracy 

 0.05% 

of 

span

 

 

 

 

-Compliance 

1000 ohms max. @ 24Vdc 

500 ohms max. @ 12Vdc

 

Factory Option : Voltage Output:

 

   -Output 

Voltage 

0(2)~10 

V

 

   -Output 

Type 

Range 

 Resolution

 

   -2 

 0 

– 

4095 

 12 

bits

 

   -Drift 

 100ppm/°C 

  -Accuracy 

 0.05% 

of 

span

 

   -Compliance 

2000 

ohms 

min. 

Load

 

Digital Inputs:

 

 

-Input Points 

 

 

-Input Voltage Range  10~26 Vdc 

 

 

 

-Input Current per input 

4mA@12Vdc / 8mA @24Vdc

 

Counters: 

  -Inputs 

 1 

to 

  -Resolution 

 32 

Bits 

   -Frequency 

 50 

Hz 

 

(max) 

 -Pulse 

Width 

20 

ms 

(min)

 

Digital Outputs:

 

 -Output 

Points 

  -Maximum 

Voltage 

36 

Vdc

 

 

 

 

-Maximum Current 

100 mA per output 

 

-Vceon 

 

1.1V  Max.

 

Isolation: 

 

 

-Between field and logic 

1500Vrms between field and logic 

Connectors:

 

 

-Logic Power and Comms 

4 Pin plug-in connector on side of station 

   -Inputs 

  18 

Way 

screw 

plug-in 

connector 

on 

top 

of 

station

 

Comms:

 

  -Protocols 

 RS485, 

Modbus 

RTU. 

   -Baud 

Rate 

 9600.

 

 

 

 

-Format 

 

8 bit, No Parity, 1 Stop.

 

Power Supply:

 

 

-Logic Supply Voltage  12~24 Vdc 

 

 

 

-Logic Supply Current  87mA @ 12V / 45mA @ 24V

 

Safety and EMC Compliances: 

EMC Compliance 

89/336/EEC and Low Voltage Equipment Directive 73/23/EEC. 

   Safety 

Compliance 

IEC 

950. 

General Specifications: 

(Unless otherwise stated in other input specifications.) 

Operating Temperature 

-10~50˚C. 

    Storage 

Temperature 

 

-40~85˚C. 

Operating Humidity 

 

Up to 95% non condensing. 

Housing 

  -Dimensions L=97.5, 

W=22.6, 

H=109mm. -Mounting 

 

35mm 

Symmetrical Mounting Rail. 

Note 1. 

Contact INTECH INSTRUMENTS for more detailed programming information.

 

Product Liability. 

This information describes our products. It does not constitute guaranteed properties and is not intended to affirm the  

suitability of a product for a particular application. Due to ongoing research and development, designs, specifications, and documentation are 
subject to change without notification. Regrettably, omissions and exceptions cannot be completely ruled out. No liability will be  
accepted for errors, omissions or amendments to this specification. Technical data are always specified by their average values and are based 
on Standard Calibration Units at 25C, unless otherwise specified. Each product is subject to the ‘Conditions of Sale’. 

Warning: These products are not designed for use in, and should not be used for patient connected applications. In any critical  
installation an independent fail-safe back-up system must always be implemented. 

Summary of Contents for 2300-MULTI

Page 1: ...ons Communications between the computer running MicroScan V5 and the 2300 series stations is RS485 1 pair cable multi drop as standard with an option for TCP A 32bit ARM CPU is used in the 2300 series stations to provide high speed data processing and fast communications turn around times All 2300 series stations have been equipped with status led s which are used to indicate the status of the Inp...

Page 2: ... 70 71 70 71 2300 I O Remote Station 2300 I O Remote Station 2300 I O Remote Station COM TX TX 74 71 USB USB 70 COM TX TX 74 71 70 2100 IS NS RS485 Converter Isolator MicroScan V5 RS232 RS232 2300 I O Remote Station 70 71 RS485 DATA HI WAY CABLE POLARITY MUST BE OBSERVED RS485 DATA HI WAY CABLE POLARITY MUST BE OBSERVED Resistor 1k End of Data Hi way Junction Box IMPORTANT i All cables must be scr...

Page 3: ...he 2300 MULTI has no user serviceable parts Protective enclosure only to be opened by qualified personnel Remove ALL power sources before removing protective cover 1 1 Factory Configurations The Intech Micro 2300 series I O Remote Stations are factory configured to connect directly to MicroScan V5 software Only the Station number station ID needs to be set via the easily accessible dip switches No...

Page 4: ...ut Points 2 Maximum Voltage 36 Vdc Maximum Current 100 mA per output Vceon 1 1V Max Isolation Between field and logic 1500Vrms between field and logic Connectors Logic Power and Comms 4 Pin plug in connector on side of station Inputs 18 Way screw plug in connector on top of station Comms Protocols RS485 Modbus RTU Baud Rate 9600 Format 8 bit No Parity 1 Stop Power Supply Logic Supply Voltage 12 24...

Page 5: ...N OFF ON OFF 44 OFF OFF ON ON OFF ON OFF 45 ON OFF ON ON OFF ON OFF 46 OFF ON ON ON OFF ON OFF 47 ON ON ON ON OFF ON OFF 48 OFF OFF OFF OFF ON ON OFF 49 ON OFF OFF OFF ON ON OFF 50 OFF ON OFF OFF ON ON OFF STATION ID DIP SWITCH SETTINGS SW1 SW2 SW3 SW4 SW5 SW6 SW7 51 ON ON OFF OFF ON ON OFF 52 OFF OFF ON OFF ON ON OFF 53 ON OFF ON OFF ON ON OFF 54 OFF ON ON OFF ON ON OFF 55 ON ON ON OFF ON ON OFF ...

Page 6: ...ON OFF OFF ON ON ON ON 122 OFF ON OFF ON ON ON ON 123 ON ON OFF ON ON ON ON 124 OFF OFF ON ON ON ON ON 125 ON OFF ON ON ON ON ON 126 OFF ON ON ON ON ON ON 127 ON ON ON ON ON ON ON RS485 Tx RS485 Rx Power Switch 1 Switch 10 2300 MULTI Dimensions The 2300 MULTI enclosure is shown below The station clips directly onto an industry standard DIN rail Field wiring is on the top of the station via a separ...

Page 7: ... where MODBUS is required please refer to the 2300 MULTI MODBUS supplementary manual which is available for download from the Intech website www intech co nz 2300 1 3 4 2 12Vdc 115mA Pin Connection 24Vdc 58mA Comms RS485 70 71 81 82 Notes 1 Logic power input terminals 17 18 range 12 24Vdc The logic power supply input must be isolated and completely separate to the power supply that powers the 2300...

Page 8: ... between wires of a pair 50 F m Capacitance between each wire to all others bunched together 95 F m Cross talk between pairs 1kHz 100kHz 90dB 100m 50dB 100m Characteristic Impedance 100kHz 135 Attenuation of a pair 1kHz 10kHz 100kHz 50kHz 1MHz 1 5MHz 0 15dB 100m 0 42dB 100m 0 8dB 100m 0 9dB 100m 1 9dB 100m 2 4dB 100m NOTE All cables are to be subject during manufacture to in process spark testing ...