Instrumentation Systems & Services MicroSpeed 196 User Manual Download Page 16

MESSAGE

COMMAND

TYPE TYPE

0 0
0 1
0 2
0 3

0 4
0 5
0 6
0 7
0 8

FUNCTION

Start
Stop

E-Stop

Set to factory defaults.
Change set point (immediate change).
Load master set point (wait for execute).
Execute loaded master set point.
Load follower set point (wait for execute).
Execute loaded follower set point.

Example: Command All MicroSpeed 196 units to Stop
Message Sent- stx00000l00000etx
Message Returned- stx00l00l00000etx

Command Message Type Definitions:

Start - 0 -

 Starts the specified MicroSpeed 196. If the front or back panel stop has been

enabled (with Var 30) and 

Stop 

is held, this command will be ignored.

Stop -1 - 

Stops the specified

 MicroSpeed  196.

E-stop - 2 -

 E-stops the specified MicroSpeed  196.

Set to Factory Defaults  

- 3 -

 Sets all variables, except Node Address (Var 19) and

Baud Rate (Var 20), to the default values.

Set Point Changes:

Only the active set point can be changed via commands 4 - 8. To change a nonselected
set point, use the write message type. The decimal location is fixed by Variable 02 in
the Master mode or Variable 23 in the Follower mode. You cannot write to the active
set point’s variable while running.

Change Set Point - 4 -

 Changes the presently selected set point to the value sent.

Load Master Set Point - 5 -

 Allows for a new speed set point to be loaded, but not

executed. The value will be stored in Variable 49.

Execute Master Set Point  

- 6 

-

 Moves the loaded speed set point into the active set

point (1 - 4), and ramps to the new value.

Load Follower Set Point  

- 7 -

 Allows for a new ratio set point to be loaded, but not

executed. The value will be stored in Variable 49.

Execute Follower Set Point  

- 8 -

 Moves the loaded ratio set point into the active set

point (1 - 4), and ramps to the new value.

Error Message  - 3 

-

 If the MicroSpeed  196 detects an error in a message, it will

respond with a 3 in the Character #4 position. The type of error will be specified in the
Character #6 position.

Error type Problem

Parity 

Error (Standard Definition)

2 Data Error (Data Outside of Range 1 - 9)
3 Global Read Error (Cannot Use the Address 00 During Read)
4 Etx Error (Etx Came Early, Late or Not At All)
5 Command Error (Reference Below)

Command Error

 -

 Any of the following conditions will give a command error:

.

Message type out of range (O-2).

.

Command type out of range (O-8).

.

Variable value out of range.

.

Write command sent to a protected variable while running.

.

Command or write sent while in local mode.

.

Load or execute new Master set point while in Follower mode.

.

Load or execute new Follower set point while in Master mode.

REMOTE VARIABLES:

The Following variables are only available over the RS422 serial port:

49 - New 

Set Point (Explained in Command, Changing Set Points - Monitor only)

50 

-

 Serial Status (Explained Below - Monitor Only)

51 

-

 Master or Follower Mode (O=Master, 

1

 =Follower)

52 

-

 Closed or Open Loop (O=Closed Loop, 1 =Open  Loop)

53 

-

 Forward or Reverse (O=Forward,  1 =Reverse)

54 

-

 Master Set Point 1 in User Units

55 

-

 Master Set Point 2 in User Units

56 

-

 Master Set Point 3 in User Units

57 

-

 Master Set Point 4 in User Units

58 

-

 Follower Set Point 1 in User Ratios

59 - Follower Set Point 2 in User Ratios
60 

-

 Follower Set Point 3 in User Ratios

61 

-

 Follower Set Point 4 in User Ratios

62 

-

 Display (Explained Below - Monitor Only)

63 - Alarm Status (Explained Below - Monitor Only)
64 

-

 Spare for Future Use

65-  Spare for Future Use

Serial Status: Variable 50 -

 Contains information on the present state of the

MicroSpeed  196. The data is returned in Characters 7 - 10.

Char 

#7 (1000’s)

Char #8 (100’s)

Operation status Local/Remote

Char #9 (10 ’s)
Active Set Point

0 =

 E-Stop 0 = Local

1 = set point 1

1 = Deceling 1 = Remote

2 = set point 2

2 = Stopping

3 = set point 3

3 = Acceling
4 = Running

4 = set point 4

5 = Ready Mode
7 = No Feedback

8 = Digital Speed Pot Mode (Diag #9)

29

30

Summary of Contents for MicroSpeed 196

Page 1: ...MSMAN32C MicroSpeed 196...

Page 2: ...is designed in sequential order from basics to the highest level of MicroSpeed 196 programming The deeper you read into each section the less relevent the options may be to your application If this is...

Page 3: ...d to the wiper of the speed potentiometer The isolated common terminal on the MicroSpeed 196 is connected to reference common on the drive Terminal locations are as follows TB2 2 Isolated Command Outp...

Page 4: ...ignal from a PLC The MicroSpeed 196 only reads this input while stopped in the Ready mode Wiring of the Master Follower input is as follows TB1 15 Master Follower to common Open Master Closed Follower...

Page 5: ...puts relays LEDs etc Power to the output circuits should be wired parallel with the Diode Protect TB2 20 terminal if inductive loads are driven to avoid damage to the output circuitry See Diagram 5 Wi...

Page 6: ...display will prompt for a variable number and the numeric display will indicate two zeros 00 which will reflect the variable number entered Enter the desired variable number and press ENTER If you are...

Page 7: ...FOLLOWER MODE The Microspeed 196 in the Follower mode mirrors a lead frequency input and can be scaled by the Ratio Set Point The lead frequency is typically generated from a digital transducer on ano...

Page 8: ...can be independently locked The section of the keypad that is locked is determined by placing a 1 one in the appropriate location Any section or combination of sections can be locked See chart below...

Page 9: ...ART MIN 56 PARTSIHR 57 Percent 58 RATIO 65 Customized 15 Diagnostic 0 Custom User Unit Labels If the choices presented in Variable 10 do not provide the display that is needed a Custom User Unit Label...

Page 10: ...ect the proper polarity of the Command Output Voltage using the Forward Reverse Input Open Positive Closed Negative 3 Access Diagnostic 9 Digital Potentiometer by pressing 2nd Function key then the 9...

Page 11: ...ters at the unstable speed 19 FOLLOWER MODE PID CONSIDERATIONS Variable 09 Max Lead Wind Up If you are speed matching and have very fast master speed changes or if you are bringing the Follower motor...

Page 12: ...ill decrease motor speed Variable 28 Auxiliary Input Delay Delays the start of the Auxiliary Trim function on startup Enter the number of 10 msec update cycles to wait When ENTER is pressed the MicroS...

Page 13: ...g inputs Closed Open Loop Master Follower Forward Reverse Keypad Unlocked Locked out Set Point 1 3 2 4 Set Point 3 4 Disabled Set Point 3 4 Enabled No Scroll Scroll Down No Scroll Scroll Up Left to ri...

Page 14: ...oSpeed 196 with node address 01 will be the only MicroSpeed 196 to answer the host computer but all MicroSpeed 196 s will respond to global commands Never duplicate an address on the same communicatio...

Page 15: ...ommunication Valid characters from the host are 0 command 1 read variable or 2 write variable The MicroSpeed 196 will echo the host in this character location unless the host communication message has...

Page 16: ...in a message it will respond with a 3 in the Character 4 position The type of error will be specified in the Character 6 position Error type Problem 1 Parity Error Standard Definition 2 Data Error Da...

Page 17: ...aximum Speed PPR Maximum Lead RPM Lead PPR User Unity Ratio Master Follower The active set point will only change with a Change Set Point command A write command to the active set point while running...

Page 18: ...mp Compete Zero Speed Deviation Drive Enable Operational Specifications Accuracy Respons Modes of Operation Preset Speeds Accel Decel Times Processor Speed Display Alphanumeric Display Function LEDs D...

Page 19: ......

Reviews: