10 of 22

496332 Issue 1

Programming

Initial Start Up

Check that all LIM box tampers are closed. Make sure that the Bell and
Strobe is not connected to the main 9500 PCB. Link out any circuits that are
nnot used.

When powering up the panel for the first time:

1.

Close the control panel lid and connect the mains supply.

The display shows:

<SYSTEM RESET>
12:00 16 OCT 90

Alternating with:

12:00 16 OCT 90
Status : Alarm

2.

Key in 4567 + Enter.

The display shows:

Display

customer log?

3.

Press No.

The display shows:

<SYSTEM RESET>
12:00 16 OCT 90

Alternating with:

16 OCT 12:00:00
CALL ENGINEER

4.

Key in 7890 + Enter.

The display shows:

Ver 4.20
14 FEB 1991

Followed by:

Do you want
engineer reset?

Note: Whenever you enter engineer mode, the software version number and its date

will be displayed. Make a note of this number, as it will be useful when contact-
ing the Scantronic Product Support Department with any queries.

5.

Press No.

The display shows:

Do you want
test functions?

6.

Press No.

The display shows:

Do you want
reports?

7.

Press No.

The display shows:

Do you want to
program the system?

8.

Open the control panel lid.

9500

Summary of Contents for 9500

Page 1: ...uide Compatible Equipment 9525 Remote Keypad 9505 LIM 9507 LIM PSU 9508 Shunt LIM 4 zones 9509 Shunt LIM Controller 9510 EOL LIM 3 Zones 9585 Engineers Printer Centronics 9589 Printer lead Centronics 9590 Hardware Mimic System 9597 Computer Mimic System ...

Page 2: ...our main data high ways or branches from the main control panel Each branch comprises a minimum 4 core cable 6 core where keypads are included in branch which may be up to 2km 2000 metres in length and may accommodate a combi nation of up to 16 Line Interface Modules LIMs Remote Keypads and Isolation LIMs Figure 1 System Configuration Each Line Interface Module has five double pole circuits which ...

Page 3: ...LIM BS 4737 Full Specification Log 450 events Date andTime Panel Siren No Internal Siren 9040 4 max Dimensions Panel h x w x d 290 x 400 x 10mm Dimensions Keypad h x w x d 180 x 110 x 40mm Weight Panel 4 6 Kg Keypad 500g Battery 6 Ah Communicator Output Plug on STU 9058 9056 by using the 9578 Signalling Conversion Interface Plug on Interface 9576 9576 01 Outputs Bell relay contacts Strobe relay co...

Page 4: ...4 of 22 496332 Issue 1 Wiring Figure 2 Main PCB Layout Figure 3 Main PCB Connections 9500 ...

Page 5: ...496332 Issue 1 5 of 22 Figure 4 Standard LIM PCB Figure 5 Connection of Shunt LIM as Single Shunt 9500 Wiring ...

Page 6: ...6 of 22 496332 Issue 1 Figure 6 Connection of Shunt LIM as Multiple Shunt Figure 7 Connection of End of Line Resistor LIM Wiring 9500 ...

Page 7: ...496332 Issue 1 7 of 22 Figure 8 Remote PSU LIM Layout and Connections Figure 9 Remote Keypad Connections 9500 Wiring ...

Page 8: ...8 of 22 496332 Issue 1 Figure 10 Wiring the Remote Keypad s to the Branch Loops Figure 11 9558 Communicator Layout and Connections Wiring 9500 ...

Page 9: ...496332 Issue 1 9 of 22 Figure 12 9576 Interface Layout Figure 13 9576 01 Interface Board Layout 9500 Wiring ...

Page 10: ...Display customer log 3 Press No The display shows SYSTEM RESET 12 00 16 OCT 90 Alternating with 16 OCT 12 00 00 CALL ENGINEER 4 Key in 7890 Enter The display shows Ver 4 20 14 FEB 1991 Followed by Do you want engineer reset Note Whenever you enter engineer mode the software version number and its date will be displayed Make a note of this number as it will be useful when contact ing the Scantronic...

Page 11: ... controls 3 Change engineer access code 4 Review communications 5 Change site location number 6 Do you want to set the clock 7 Do you want test functions 8 Do you want reports 9 Do you want engineer reset When programming the system for the first time no circuits are allocated to specific functions On entering a function the system asks for a circuit number Each circuit has a unique four digit ide...

Page 12: ...12 of 22 496332 Issue 1 Engineering Program Commands 9500 ...

Page 13: ...496332 Issue 1 13 of 22 9500 Engineering Program Commands ...

Page 14: ...14 of 22 496332 Issue 1 Engineering Program Commands 9500 ...

Page 15: ...is connected and all lids are closed on LIMs keypads and main control panel If your system is fitted with remote signalling check that it is programmed for Engineer Reset and proceed as follows The display shows Do you want to engineer reset 1 Press Yes The display shows Branch 1 No of LIMs 5 Followed by Branch 2 No of LIMs 7 Followed by Branch 3 No of Lims 8 9500 Leaving Engineering Mode ...

Page 16: ...are now in customer day mode Re entering Engineering Mode 1 Key in 7890 Enter The display shows Ver 4 20 14 FEB 1991 Followed by Do you want engineer reset 2 Press No The display shows Do you want test functions 3 Press No The display shows Do you want reports 4 Press No The display shows Do you want to program the system 5 Open the control panel lid 6 Press Yes You are now in Engineering Mode Not...

Page 17: ... Replace the chip and Power up the control panel Reset the system and continue to re programme as required 9500 LOG EVENTS Access engineer Tamp panel keys Excess key presses Fault tel line Telephone line fault line missing Fault tel comm Telephone communication failure e g no reply Fault mains A C Power failure Fault battery Fault aux supply Aux 12v DC fuse blown Fault all power Total power failur...

Page 18: ...elctd Reset branches Viewed CST log Tamper panel Tamper bell Printed codes Access codes Manager modified or printed access codes Groups isolated Always followed by a list of groups isolated Exit fault Date time change date time is old time New Date time date time is new time Personal attack Tamp alarm represents a circuit number 24 hr alarm Alarm PA Tech alarm Tamp FE Omit 24 hr tamp Tamper LIM Om...

Page 19: ...T LkSt Walk test engineer walk test only printer only WT LIM tmp Walk test engineer walk test only printer only WT circuit Walk test R circuit Restore circuit R tamper Restore tamper R PA cct Restore personal attack circuit R PA tmp Restore personal attack tamper R FE cct Restore final exit circuit R FE tamp Restore final exit tamper R Tech cct Restore technical alarm circuit R Tech tamp Restore t...

Page 20: ...M Walk test of a LIM engineer walk test Entry alarm keys Entry alarm following entry initiated at panel keypad Part Set System part set Omit 24hr grp Omission of 24 hour groups Access manager Tamper branch Failure of branch communications or branch wiring fault Alarm entry Entry alarm following entry at final entry circuit Invalid log code Invalid entry found in log Open Return from full set statu...

Page 21: ...appear in the log Fault checksum High security data has been corrupted Defaults have been loaded SYSTEM RESET The system has reset and is running on default parameters User Commands ACCESS CODE SPECIFICATION 1 Master manager code manager number 1 49 Manager codes manager numbers 2 to 50 49 Operator codes operators 1 to 49 1 Cleaner code operator number 0 1 Duress code operator 99 in log events mem...

Page 22: ...r manager codes It can also change and delete both manager and operator codes and PRINT OUT actual access codes The normal manager codes can change operator codes and print the engi neer log Along with the master manager they have control of the group isolation facility The duress code when entered will disarm the system and trigger a silent personal attack signal to the alarm company central stat...

Reviews: