5.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
VIN310C2V31 VIN310C2V31 OUTDOOR
3/8’’
(Ф9.52)
1/4’’
(Ф6.35)
7.5
10
25
15
VIN414C2V31 VIN414C2V31 OUTDOOR
1/2’’
(Ф12.7)
1/4’’
(Ф6.35)
7.5
10
25
15
VIN520C2V31 VIN520C2V31 OUTDOOR
1/2’’
(Ф12.7)
1/4’’
(Ф6.35)
7.5
20
30
15
VIN625C2V31 VIN625C2V31 OUTDOOR
5/8’’
(Ф15.9)
3/8’’
(Ф9.52)
7.5
20
30
30
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
14