INNOVAIR INVERTER VEXUS
SERVICE MANUAL
9.2.4 Fan speed has been out of control diagnosis and solution(E3)
Error Code
E3/F5
Malfunction decision
conditions
When indoor fan speed keeps too low (300RPM) for certain time,
the unit will stop and the LED will display the failure.
Supposed causes
●
Wiring mistake
●
Fan ass’y faulty
●
Fan motor faulty
●
PCB faulty
Trouble shooting:
Shut off the power supply
and turn it on 2 minutes
later. Is it still displaying
the error code?
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
The unit operates normally.
Find out the cause and
have it solved. For
example, check
whether the fan is
blocked or the bearing
is broken?
Check the wires of fan
motor. Are all the
connections good?
No
Yes
No
Correct the connections.
No
Check whether the main PCB is
normal through index 1?
Yes
Yes
Yes
Replace the fan motor.Is the error
extinguished?
No
Replace the main PCB
No
39
Summary of Contents for Vexus VIN310C2V31
Page 9: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL For VIN520C2V31 TIN520H2V33 For VIN625C2V31 7 ...
Page 13: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL For VIN625C2V31 11 ...
Page 22: ...INNOVAIR DC INVV ERTER QUANTUM SERVICE MANUAL w w w i n n o v a i r c o m VIN625C2V31 20 ...
Page 23: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL 6 2 Outdoor Unit VIN310C2V31 VIN414C2V31 21 ...
Page 24: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL w w w i n n o v a i r c o m VIN520C2V31 VIN625C2V31 22 ...
Page 48: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL w w w i n n o v a i r c o m P W N U 46 ...
Page 49: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL N V N W 47 ...