Open the valves on the charging cylinder and the
charge set. Purge the air by loosening the flare
nut on the 2-way valve approximately 45’ for 3
seconds then closing it for 1 minute; repeat 3
times.
After purging the air, use a torque wrench to
tighten the flare nut on the 2-way valve.
4). Check the gas leakage.
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and
discharge the refrigerant by loosening the flare
nut on the 2-way valve approximately 45’ until the
gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging
cylinder, and set the 2-way and 3-way valves to
the open position.
Be sure to use a hexagonal wrench to operate the
valve stems.
7). Mount the valve stems nuts and the service
port cap.
Be sure to use a torque wrench to tighten the
service port cap to a torque 18N·m.
Be sure to check the gas leakage.
5.5 Adding the refrigerant after running
the system for many years
Procedure:
1). Connect the charge hose to the 3-way service
port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the
bottom of the cylinder. If the refrigerant is
R410A, make the cylinder bottom up to ensure
liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air (be careful of the liquid
refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4) Operate the air conditioner at the cooling
mode.
5) Open the valves (Low side) on the charge set
and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper
weight (refer to the gauge and the pressure of the
low side), disconnect the charge hose from the
3-way valve’s service port immediately and turn
off the air conditioner before disconnecting the
hose.
7). Mount the valve stem caps and the service
port
Use torque wrench to tighten the service port
cap to a torque of 18N.m.
Be sure to check for gas leakage.
5.6 Re-installation while the indoor unit
need to be repaired
1. Collecting the refrigerant into the outdoor
unit
Procedure
1). Confirm that both the 2-way and 3-way valves
are set to the opened position
Remove the valve stem caps and confirm that the
valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the
valve stems.
16
Summary of Contents for Vexus VIN310C2V31
Page 9: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL For VIN520C2V31 TIN520H2V33 For VIN625C2V31 7 ...
Page 13: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL For VIN625C2V31 11 ...
Page 22: ...INNOVAIR DC INVV ERTER QUANTUM SERVICE MANUAL w w w i n n o v a i r c o m VIN625C2V31 20 ...
Page 23: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL 6 2 Outdoor Unit VIN310C2V31 VIN414C2V31 21 ...
Page 24: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL w w w i n n o v a i r c o m VIN520C2V31 VIN625C2V31 22 ...
Page 48: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL w w w i n n o v a i r c o m P W N U 46 ...
Page 49: ...INNOVAIR INVERTER VEXUS SERVICE MANUAL N V N W 47 ...