background image

For more details visit www.MrCool.com

The design and specifications are subject to change without prior notice.

. Consult with the sales agency or manufacturer for details.

CS260I-BP11D(QF)

   202000192602

     20130319

P

Please read this manual carefully before installation and keep it for future reference.

ROOM AIR CONDITIONER

 

INVERTER SPLIT  TYPE

®

DIY Series

For more details visit www.MrCool.com

13

Test running

Perform  test operation after completing gas leak check at the flare nut connections and 

electrical safety check.

    Check that all tubing and wiring have been properly connected.

    Check that the gas and liquid side service valves are fully open.

1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.

2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions

     works well. 

3. When the am

     the remote controller to run at cooling mode, manual operation can be taken. Manual 

     operation is used

     Hold the panel sides and lift the panel up to an angle until it remains fixed

     with a clicking sound.

     Press the Manual control button to select the AUTO or COOL, the unit will

     operate under Forced AUTO or COOL mode(see User Manual for details).

4.  The test operation should last about 30 minutes.

Connect the cable to the indoor unit 

Connect the cable to the outdoor unit 

,

                  Before performing any electrical 

work, turn off the power to the system.

1. The inside and outside connecting cable 

     can be connected without removing the 

     front grille.

2. The indoor power cord type is H05VV-F 

    or H05V2V2-F, the outdoor power cord 

    and interconnected cord type is H07RN-F.

3. Lift the indoor unit panel up, remove the 

    electrical box cover by loosening the screw.

4. Ensure the color of wires of outdoor unit 

    and the terminal Nos. are the same to the 

    indoor s respectively.

5. Wrap those cables not connected with 

     terminals with insulation tapes, so that 

     they will not touch any electrical components. 

     Secure the cable onto the control board 

     with the cord clamp.

    

NOTE:

Terminal block of indoor unit

Electronic box

cover

Front Panel

1. Remove the electrical control board cover

     from the outdoor unit by loosening the screw.

2. Connect the connective  cables to the terminals 

    as identified with their respective matched 

    numbers on the terminal block of indoor and 

    outdoor units.

3. Secure the cable onto the control board with the 

    cord clamp.

4. To prevent the ingress of water, form a loop of the 

    connective cable as illustrated in the installation 

    diagram of indoor and outdoor units.

5. Insulate unused cords (conductors) with PVC-tape. 

    Process them so they do not touch any electrical or  

    metal parts.

Cover

Screw

Fig.26

ELECTRICAL  WORK

To outdoor unit

To outdoor unit

Cord clamp

L1  L2    S

L1  L2    S

or

To outdoor unit

To outdoor unit

Cord clamp

L    N      S

L    N    S

or

Model A

Model B

15

Troubleshooting

For more details visit www.MrCool.com

12

Electric safety regulations for the initial Installation

1. If there is serious safety problem about the power supply, the technicians should refuse to install the air 

    conditioner and explain to the client until the problem is solved. 

2. Power voltage should be in the range of 90%~110% of rated voltage.

3. The creepage protector and main power switch with a 1.5 times capacity of Max. Current of the unit 

    should be installed in power circuit.

4. Ensure the air conditioner is grounded well.

5. According to the attached Electrical Connection Diagram located on the panel of the outdoor unit to 

    connect the wire.

6. All wiring must comply with local and national electrical codes and be installed by qualified and skilled 

    electricians.   

7. An individual branch circuit and single receptacle used only for this air conditioner must be available. 

    See the following table for suggested wire sizes and fuse specifications:

Electrical work

ELECTRICAL  WORK

After the confirmation of the above conditions, prepare the wiring as follows:

1) Never fail to have an individual power circuit specifically for the air conditioner. As for

the method of wiring, be guided by the circuit diagram posted on the inside of control

cover.

2) The screw which fasten the wiring in the casing of electrical fittings are liable to come

loose from vibrations to which the unit is subjected during the course of

transportation. Check them and make sure that they are all tightly fastened. (If they

are loose, it could cause burn-out of the wires.)

3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated

voltage marked on the name plate.

6) Confirm that the cable thickness is as specified in the power source specification.

7) Always install an leakage circuit breaker in a wet or moist area.

8) The following would be caused by voltage drop.

 

A) 

Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the

normal function of the overload.

d

e

x

if

 

e

h

t

 

n

d

e

t

a

r

o

p

r

o

c

n

e

b

 l

l

a

h

s

 

y

l

p

p

u

s

 

r

e

w

o

p

 

a

 

m

o

r

n

o

it

c

e

n

n

o

c

s

i

d

 

r

o

s

n

a

e

m

 

e

h

)

9

wiring and have an air gap contact separation of at least 3mm in each active(phase)
conductors.

CAUTION

CAUTION

CAUTION

CAUTION

NOTE

: The cable size and the current of the fuse or switch are determined by the maximum 

current indicated on the nameplate which located on the side panel of the unit. Please refer to the

nameplate before selecting the cable, fuse and switch.

  

         Appliance Amps

                      

AWG Wire Size

                    

10

13

18

25

18

16

14

12

30

10

Suggest Minimum Wire Size 

(

AWG:

American Wire Gage)

:

14

Troubleshooting

For more details visit www.MrCool.com

Test running:

Perform  test operation after completing gas leak check at the flare nut connections and 

electrical safety check.

    Check that all tubing and wiring have been properly connected.

    Check that the gas and liquid side service valves are fully open.

1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.

2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions

     works well. 

3. When the am

b

ient temperature is too low(lower than 63 °F), the unit cannot be controlled by 

     the remote controller to run at cooling mode, manual operation can be taken. Manual 

     operation is used

 

when the remote controller is disable

d

 or maintenance 

is 

necessary.

     Hold the panel sides and lift the panel up to an angle until it remains fixed

     with a clicking sound.

     Press the Manual control button to select the AUTO or COOL, the unit will

     operate under Forced AUTO or COOL mode(see User Manual for details).

4.  The test operation should last 30 minutes.

Manual control 

button

AUTO/COOL

TEST  RUNNING

Fig.27

Fig.28

14

Model A

Model B

To indoor unit

To indoor unit To power supply

To power supply

L1   L2    S    L1   L2

L1   L2    S    L1   L2

Terminal block of outdoor unit

To indoor unit

To power supply

1(L) 2(N)  S    L     N

13

For more details visit www.MrCool.com

ELECTRICAL  WORK

12

Connection at the condesnser 

slides over the spade.

Condenser Connection

Air Handler Connection

Use screw to connect

to ground.

Air handler preconnected 

at factory, no connection 

needed.

Grounding Wire

For more details visit www.MrCool.com

11

Coupling size (last 2 part numbers)

Pound-force foot(1bf-ft)

Newton meter(N-m)

Kilogram-force meter(kgf-m)

18 - 20

30 - 35

45 - 50

60 - 65

24.4 - 27.1

40.6 - 47.4

61.0 - 67.7

81.3 - 88.1

2.4 - 2.7

4.1 - 4.8

6.2 - 6.9

8.2 - 8.9

-06(9.5mm/3/8 dash size)

-08(12.7mm/1/2 dash size)

-12(19.1mm/3/8 dash size)

-16(25.4mm/1 dash size)

After

 

completing

 

steps

 

1-

 

4,

 

check

 

that

 

all

 

the 

connections

 

are

 

sealed

 

correctly

 

using

 

leak

 

detection

 

spray

 

or

 

soap

 

suds.

 

If

 

any

 

bubbles

 

form,

the

 

system has

 

a

 

leak

 

and

 

the

 

screw

 

connectors

 

must

 

be

 

retightened

 

using

 

an

 

open-ended

 

wrench.

5.

 

Now

 

remove

 

the

 

cover

 

on

 

the

 

top

 

valve

 

using

 

a

   19

 

mm

 

open-ended

 

wrench.

 

Open

 

the

 

valve

 

by

 

    

turning

 

it

 

counter-clockwise

 

as

 

far

 

as

 

it

 

will

 

go

 

    

using

 

a

 

5

 

mm

 

Allen

 

key.

 

The

 

valve

 

is

 

now

 

open.

 

If

 

    

the

 

valve

 

is

 

not

 

opened

 

fully,

 

the

 

system

 

may 

    malfunction

 

and

 

suffer

 

damage.

 

Screw

 

the

 

cover

 

    

back

 

on

 

to

 

the

 

top

 

valve

 

and

 

tighten

 

it

 

well

 

to

 

    

ensure

 

that

 

it

 

is

 

properly

 

sealed. See Fig.24.

6.

 

Now

 

remove

 

the

 

cover

 

on

 

the

 

bottom

 

valve

 

using

 

    

a

 

19

 

mm

 

open-ended

 

wrench.

 

Open

 

the

 

valve by

 

    

turning

 

it

 

counter-clockwise

 

as

 

far

 

as

 

it

 

will

 

go

 

    

using

 

a

 

5

 

mm

 

Allen

 

key.

 

The

 

valve

 

is

 

now

 

open. 

    If

 

the

 

valve

  

is

 

not

 

opened

 

fully,

 

the

 

system

 

may

 

    

malfunction

 

and

 

suffer

 

damage.

 

Screw

 

the

 

cover

 

    

back

 

on

 

to

 

the

 

bottom valve

 

and

 

tighten

 

it

 

well

 

to

 

    

ensure

 

that

 

it

 

is

 

properly

 

sealed. See Fig.25.

Important!

 The conical ring on the valve has an 

important sealing function together with the sealing

seat in the caps. Ensure that you do not damage the

cone and that you keep the cap free of dirt and dust.

7.

 

After

 

completing

 

steps

 

1-

 

6,

 

check

 

that

 

all

 

the

 

    

connections

 

are

 

sealed

 

correctly

 

using

 

leak

 

    

detection

 

spray

 

or

 

soap

 

suds.

 

If

 

any

 

bubbles

 

form,

 

    

the

 

system

 

has

 

a

 

leak

 

and

 

the

 

screw

 

connectors

 

    

must

 

be

 

retightened

 

using

 

an

 

open-

 

ended

 

spanner.

8.

 

Start

 

the

 

equipment

 

so

 

that

 

the

 

operating

 

     

pressures

  

build

 

up

 

inside

 

it.

 

Check

 

all

 

the

 

     

connectors

 

again

 

for

 

signs

 

of

 

leaks

    a)

 

during

 

cooling

 

mode

 

     

b)

 

in

 

heating

 

mode.

    If

 

any

 

bubbles

 

form,

 

the

 

system

 

has

 

a

 

leak

 

and

 

the

    

screw

 

connectors

 

must

 

be

 

retightened

 

using

 

an

 

    

open-ended

 

wrench.

 

 

 

 

 

 

Fig.25

Fig.24

Electric safety regulations for the initial Installation

1. If there is serious safety problem about the power supply, the technicians should refuse to install the air 

    conditioner and explain to the client until the problem is solved. 

2. Power voltage should be in the range of 90%~110% of rated voltage.

3. The creepage protector and main power switch with a 1.5 times capacity of Max. Current of the unit 

    should be installed in power circuit.

4. Ensure the air conditioner is grounded well.

5. According to the attached Electrical Connection Diagram located on the panel of the outdoor unit to 

    connect the wire.

6. All wiring must comply with local and national electrical codes and be installed by qualified and skilled 

    electricians.   

7. An individual branch circuit and single receptacle used only for this air conditioner must be available. 

    See the following table for suggested wire sizes and fuse specifications:

Electrical work

REFRIGERANT  PIPE  CONNECTION

For more details visit www.MrCool.com

10

1. First remove the water tray on the outdoor unit

    as shown in Fig.20.

2. Do not remove the plastic seals from the outdoor

    unit and the appropriate refrigerant pipes until

    immediately before you connect them, Fig.21.

3. Align the refrigerant pipes correctly so they

    line up with the valves and are not stressed. 

    Place the screw connector on the refrigerant line

    just on to the thread on the outdoor unit and 

    tighten the first few threads by hand, Fig.22.

    

NOTE:

 The refrigerant pipes must be connected

    to the valves on the outdoor unit with as little 

    stress as possible.

IMPORTANT:

 Before you continue, it is essential

that you read the following instructions carefully.

4. Now tighten the bottom screw connector first

    and then the top screw connector using the 

    open-ended wrench.  Hold the points marked 

    

A

using a 22mm/0.87in open-ended wrench

     and turn the nuts only at the points marked 

B

    using a  24mm/0.95in open-ended wrench, see 

    Fig.23.

    Ensure that the screw connectors do not skew 

    as you tighten them and work quickly. See the

    next page for the proper torque.

IMPORTANT: Since the coupling works with 
tapping rings, it may leak if you undo and 
reconnect the pipes. This will void the 
warranty.

    

CAUT ION:

 For your safety, always wear goggles

and work gloves when connecting the pipes.

Fig.20

4. Connecting the refrigerant pipe to outdoor unit

 

 

 

 

 

 

 

A

B

A B

Fig.21

Fig.22

Fig.23

NOTE:

 To distinguish the connectors to be connected 

to the indoor unit and outdoor unit, the connectors 

of the refrigerant pipe ha

ve

 been labelled 

A

,

B

,

C

and 

D

. Ensure the marks on the 

connector are the same to the indoor s and outdoor s 

respectively during connection.

,

,

REFRIGERANT  PIPE  CONNECTION

For more details visit www.MrCool.com

9

Select the location for installation(follow the previous

notes on selecting the installation place).

If the outdoor unit is higher than the indoor unit, 

make sure that a curve is made in the refrigerant

pipe which is lower than the bottom edge of the

indoor unit. See Fig.16.

In the case that the installation place is exposed to 

strong wind such as a seaside, make sure the fan 

operating properly by putting the unit lengthwise 

along the wall or using a dust or shield plates, Fig.17.

If need suspending installation, the installation  

bracket should accord with technique requirement 

in the installation bracket diagram. The installation 

wall should be solid brick, concrete or the same 

intensity construction, or actions to reinforce, 

damping supporting should be taken. The connection 

between bracket  and  wall, bracket and the air 

conditioner should be firm, stable and reliable.

Be sure there is no obstacle which can block radiating air.

Strong

  wind

Fig.17

Outdoor unit installation 

1. Outdoor installation precaution

2. Settlement of outdoor unit

Anchor the outdoor unit with a bolt and nut

φ

10 or 

φ

8

tightly and horizontally on a concrete or rigid mount.

 

Outdoor unit

Refrigerant pipe

Indoor unit

Curve

Fig.16

Fig.18

Fig.19

Drain joint installation 

Seal

Drain joint

Base pan hole of

outdoor unit

Seal

Drain pipe

(A)

(B)

For the drain joint with the seal(Fig.19 (A)), first fit  the 

seal onto the drain  joint, then insert  the  drain  joint  

into the base pan hole of outdoor unit, rotate  90 to 

securely  assemble them. To install drain joint as 

shown in Fig.19 (B), insert  the  drain  joint  

into the base pan hole of outdoor unit until it remains 

fixed  with a clicking sound. Connecting the drain 

joint with an extension drain hose (Locally 

purchased), in case of the water draining off the 

outdoor unit during the heating mode.

NOTE: 

The drain joint is slightly different according

to the outdoor unit

 specifications

.

Outdoor unit dimension

          mm/in(WxHxD)

A(mm/in)

B(mm/in)

530(20.87)

290(11.42)

624(24.57)

560(22.05)

366(14.41)

335(13.19)

549(21.61)

458(18.03)

276(10.87)

276(10.87)

Mounting dimensions

780(30.71)x540(21.26)x250(9.84)

760(29.92)x590(23.23)x285(11.22)

660(25.98)x242(9.52)x540(21.26)

990(38.98)x965(37.99)x345(13.58)

840(33.07)x700(27.56)x320(12.6)

A

W

B

D

Air inlet 

Air outlet

Air inlet 

1. First remove the water tray on the outdoor unit

    as shown in Fig.20.

2. Do not remove the plastic seals from the outdoor

    unit and the appropriate refrigerant pipes until

    immediately before you connect them, Fig.21.

3. Align the refrigerant pipes correctly so they

    line up with the valves and are not stressed. 

    Place the screw connector on the refrigerant line

    just on to the thread on the outdoor unit and 

    tighten the first few threads by hand, Fig.22.

    

    to the valves on the outdoor unit with as little 

    stress as possible.

IMPORTANT:

that you read the following instructions carefully.

4. Now tighten the bottom screw connector first

    and then the top screw connector using the 

    open-ended spanner. 

    

     and turn the nuts only at the points marked 

    using a  24mm/0.95in open-ended spanner, see 

    Fig.23.

    Ensure that the screw connectors do not skew 

    as you tighten them and work quickly. See the

    next page for the proper torque.

IMPORTANT: Since the coupling works with 
tapping rings, it may leak if you undo and 
reconnect the pipes. This will void the 
war

    

CAUT

and work gloves when connecting the pipes.

4. Connecting the refrigerant pipe to outdoor unit

NOTE:

to the indoor unit and outdoor unit, the connectors 

of the refrigerant pipe ha

connector are the same to the indoor s and outdoor s 

respectively during connection.

INSTALLATION  INSTRUCTIONS

523(20.59) 340(13.39)

820(32.28)x595(23.43)x330(12.99)

For more details visit www.MrCool.com

8

INSTALLATION  INSTRUCTIONS

Do not allow the piping to let out from the back of 

the indoor unit.

Be careful not to let the drain hose slack.

Heat insulate both of the auxiliary piping.

Be sure that the drain hose is located at the 

lowest side of the bundle. Locating at the upper 

side can cause drain pan to overflow inside the 

unit.

Never intercross nor intertwist the power wire 

with any other wiring.

Run the drain hose sloped downward to drain 

out the condensed water smoothly.

Note: Route the package of pipes/hoses in the 

direction of (rear)right or (rear)left. See Fig.13 .

5. Bundle the tubing, connecting cable with tape 

    securely, evenly as shown in Fig.14.

   Because the condensed water from rear of the 

   indoor unit is gathered in ponding box and is 

   piped out of room. Do not put anything else in 

   the box.

CAUTION:

Indoor unit

Connective

pipe

Pipe room

Ponding box

Wrapping belt

Connective

cable

Drain hose

Fig.14

.

.

.

. .

.

.

.

.

.

.

.

.

.

.

.

.

...

..

.

.

.

.

.

.

.

. .

.

Rear-right piping

Rear-left piping

Fig.13

Fig.15

5. Indoor unit installation

1. Feed the package of pipes/hoses through the hole

    in the wall.

2. Hook the indoor unit onto the upper portion of the 

    installation plate.(Engage the two hooks of the rear

    top of the indoor unit with the upper edge of the 

    installation plate.)  Ensure  that the hooks are 

    properly seated on the installation plate by moving 

    it left and right.

3. The female half can easily be made by lifting the 

    indoor unit with a cushioning material between the 

    indoor unit and the wall. Get it out after finish piping.

4. Press the lower left and right sides of the unit 

    against the installation plate until the hooks engage 

    into their slots.

One side drainage structure is standard. Both sides 

drainage structure is optional and can only be 

customized from factory.For both sides drainage 

structure, it can be choosen for right, left or both 

sides drainage connection. If choosing both sides 

drainage connection, another proper drain hose is 

needed as there is only one drain hose offered by 

factory. If choosing one side drainage connection, 

make sure the drain hole on the other side is well 

plugged. For 9k/12k models, if choosing right side 

drainage connection, please choosing right-hand 

or right-back piping.The connection of the drain 

hose is supposed to be done by qualified installer in 

case of water leakage.

For more details visit www.MrCool.com

7

INSTALLATION  INSTRUCTIONS

   Remember

 

that

 

if

 

they

 

are

 

tightened

 

with

 

too

 

    

little torque

 

they

 

will

 

leak

 

but

 

if

 

they

 

are

 

tightened

 

   

with too

 

much

 

torque,

 

the

 

screw

 

connections

 

may

   suffer

 

damage.

 

If

 

you

 

should

 

not

 

be

 

confident

 

   

about

 

connecting

 

the

 

refrigerant

 

line

 

connectors

 

   

yourself,

 

it

 

is

 

imperative

 

that

 

you

 

contact

 

your

 

   

customer

 

service

 

team

 

or

 

a

 

refrigeration

 

contractor.

Important! The EQ valves are only designed for 

one-time installation. Their seal can not be 

guaranteed if they are installed on more than one 

occasion. This will also void the warranty.

4.3 Connecting the refrigerant pipes to indoor

       unit

1. Do not remove the plastic seals from the indoor

    equipment and the appropriate refrigerant pipe

    until immediately before you connect them.

2. Align the refrigerant pipes correctly, make sure

    the dimensions of the connecting refrigerant pipe 

    are the same. Place the screw connector on the 

    refrigerant pipes just on to the thread on the 

    indoor equipment and tighten the first few threads

    by hand. See Fig.9.

IMPORTANT: Before you continue, it is essential

that you read the following instructions carefully.

3. Hold the points marked  A  using a 22mm/0.87in open-

    ended wrench and turn the nuts only at the points

    marked  B  using a 24mm/0.95in open-ended wrench.

    See Fig.10a & 10b.

4. Ensure that the screw connectors do not skew as

    you tighten them and work quickly.

IMPORTANT: Since the coupling works with tapping

rings, it may leak if you undo and reconnect the 

pipes. This will also void the warranty.

5. After finishing the connection, first wrap up the quick

    connectors with the sound deadening pads(packed with

     accessories) solidly and tightly as shown in Fig.11,

    then use the tape to wrap the refrigerant pipe and 

    connecting cable together. See Fig.12.

NOTE: 

For aesthetic reasons, the quick connector parts 

are recommended to be placed outside of room.

   

   

Fig.9

Fig.10a

Fig.10b

Fig.12

Fig.11

A

B

,,

,,

,,

,,

Note: Route the package of pipes/hoses in the 

direction of (rear)right or (rear)left. See Fig.13 .

5. Bundle the tubing, connecting cable with tape 

    securely, evenly as shown in Fig.14.

   Because the condensed water from rear of the 

   indoor unit is gathered in ponding box and is 

   piped out of room. Do not put anything else in 

   the box.

CAUTION:

5. Indoor unit installation

1. Feed the package of pipes/hoses through the hole

    in the wall.

2. Hook the indoor unit onto the upper portion of the 

    installation plate.(Engage the two hooks of the rear

    top of the indoor unit with the upper edge of the 

    installation plate.)  Ensure  that the hooks are 

    properly seated on the installation plate by moving 

    it left and right.

3. The female half can easily be made by lifting the 

    indoor unit with a cushioning material between the 

    indoor unit and the wall. Get it out after finish piping.

4. Press the lower left and right sides of the unit 

    against the installation plate until the hooks engage 

    into their slots.

Do

 

not

 

smoke

 

during

 

the

 

installation

 

work.

The

 

equipment

 

must

 

never

 

be

 

operated

 

without

 

the

 

refrigerant

 

lines

 

connected,

 

otherwise

 

the

 

equipment

 

will

 

be

 

damaged

 

immediately.

The

 

screw

 

connections

 

may

 

only

 

be

 

tightened

 

using

 

the

 

appropriate

 

open-ended

 

wrench.

 

One side drainage structure is standard. Both sides 

drainage structure is optional and can only be 

customized from factory.For both sides drainage 

structure, it can be choosen for right, left or both 

sides drainage connection. If choosing both sides 

drainage connection, another proper drain hose is 

needed as there is only one drain hose offered by 

factory. If choosing one side drainage connection, 

make sure the drain hole on the other side is well 

plugged. For 9k/12k models, if choosing right side 

drainage connection, please choosing right-hand 

or right-back piping.The connection of the drain 

hose is supposed to be done by qualified installer in 

case of water leakage.

For more details visit www.MrCool.com

6

2. Drilling

  

1. Determine hole positions according to 

    the diagram detailed in Fig.5. Drill 

    one (1) hole (

φ

90mm/3.54in) slanting 

    slightly to outdoor side.

2. Always use wall hole conduit when 

    drilling metal grid, metal plate or the like.

Wall

Indoor

Outdoor

5-

7m

m

/0

.2

-0

.2

8i

n

INSTALLATION  INSTRUCTIONS

3. Drainage Installation

1. Run the drain hose sloping downward. Do not 

    install the drain hose as illustrated in Fig.7.

2. When connecting extension drain hose, insulate 

    the connecting part of extension drain hose with 

    a shield pipe, do not let the drain hose slack.

D

Fig.7

Fig.6

Do not form a rise

Do not put the hose

end into water or any

container

4. Connecting the refrigerant pipes

4.1

  

Tools needed

-You

 

will

 

require

 

the

 

following

 

tools

 

to

 

carry

 

out

 

this

 

installation

 

work

 

correctly:

1x

 

open-ended

 

wrench,

 

19

 

mm/0.75in

1x

 

open-ended

 

wrench,

 

22

 

mm/0.87in

1x

 

open-ended

 

wrench,

 

24

 

mm/0.95in

1x

 

Allen

 

key,

 

5

 

mm/0.2in

1x

 

Philips

 

screwdriver

1x

 

leak

 

detection

 

spray

 

or

 

alternatively

 

soap

 

suds

(water/detergent mix)

Follow

 

the

 

detailed

 

instructions

 

for

 

connecting

 

the

 

refrigerant

 

pipes

 

to

 

the indoor unit and 

outdoor unit.

 

We

 

can

 

only

 

provide

 

a

 

warranty

 

if

 

the

 

lines

 

are

 

installed

 

correctly

 

as

 

described

 

in

 

the

 

instructions.

 

Do

 

not

 

remove

 

the

 

sealing

 

caps

 

and

 

stoppers

 

until

 

immediately

 

before

 

you

 

install

 

the

 

lines.

 

To

 

prevent

 

leaks,

 

ensure

 

that

 

the

 

quick-release

 

screw

 

connections

 

are

 

absolutely

 

free

 

of

 

dirt.

 

Moisture

 

or

 

foreign

 

bodies

 

will

 

adversely

 

affect

the

 

function

 

of

 

the

 

quick-release

 

connectors,

 

leading

 

to

 

a

 

risk

 

of

 

refrigerant

 

loss

 

(not

 

covered

 

by

 

the

 

warranty).

Only

 

install

 

refrigerant

 

lines

 

outdoors

 

in

 

dry

 

weather.

The

 

refrigerant

 

lines

 

must

 

not

 

be

 

installed

 

and

 

then

 

plastered

 

over.

Please

 

make

 

sure

 

that

 

refrigerant

 

is

 

never

 

allowed

 

to

 

enter

 

the

 

environment.

Improper

 

handling

 

of

 

refrigerant

 

may

 

be

 

harmful

 

to

 

health.

 

Always

 

wear

 

work

 

gloves

 

and

 

goggles

 

when

 

handling

 

refrigerant.

4.2 

Important

 information

Refrigerant pipe

Connectors(both ends):

Fig.8

NOTE:

 To distinguish the connectors 

to be connected to the indoor unit and

outdoor unit, the connectors of the 

refrigerant pipe has been labelled 

A

,

B

,

C

and 

D

. Ensure the 

marks on the connectors are the same

to the indoor s and outdoor s respectively

during connection.

,

,

90/3.54in

refrigerant pipe 

 or more to wall

18000Btu/h models(A:905/35.63, B:275/10.83, C:80/3.15,  D:100/3.94)

Right rear side

refrigerant pipe 

90/3.54

For more details visit www.MrCool.com

5

2. Drilling

  

1. Determine hole positions according to 

    the diagram detailed in Fig.5. Drill 

    one (1) hole (

    slightly to outdoor side.

2. Always use wall hole conduit when 

    drilling metal grid, metal plate or the like.

INSTALLATION  INSTRUCTIONS

3. Drainage Installation

1. Run the drain hose sloping downward. Do not 

    install the drain hose as illustrated in Fig.7.

2. When connecting extension drain hose, insulate 

    the connecting part of extension drain hose with 

    a shield pipe, do not let the drain hose slack.

4. Connecting the refrigerant pipes

4.1

-You

 

installation

1x

1x

1x

1x

1x

1x

(water/detergent mix)

4.2 

Indoor unit installation

Fig.4

Fig.5

Note:
  

1.  Fitting the Installation Plate

1. Fit the installation plate horizontally

    on structural parts of the wall with 

    spaces around the installation plate.

2. If the wall is made of brick, concrete or

    the like, drill five o r eight 5mm/0.197in 

    diameter holes in the wall. Insert Clip 

    anchor  for appropriate mounting screws.

3. Fit the installation plate o n the wall with 

    eight or five type A screws.

Correct orientation 

of Installation Plate

Fit the Installation Plate and drill 

holes in the wall according to the 

wall structure and corresponding 

mounting points on the installation 

plate.

(

Dimensions are in mm & in unless 

otherwise stated)

Right rear side

refrigerant pipe 

hole 

φ

90/3.54in

Right rear side

refrigerant pipe 

hole 

φ

90/3.54

Left rear side 

refrigerant

pipe hole

 

φ

90/3.54in

Left rear side 

refrigerant

pipe hole

 

φ

90/3.54in

Left rear side 

refrigerant

pipe hole

 

φ

90/3.54in

Left rear side 

refrigerant

pipe hole

 

φ

90/3.54in

Indoor unit outline

Indoor unit outline

150mm/5.91in or more to ceiling

150mm/5.91in or more to ceiling

150mm/5.91in or more to ceiling

150mm/5.91in or more to ceiling

120mm/4.72in

 or more to wall

120mm/4.72in

 or more to wall

120mm/4.72in

 or more to wall

120mm/4.72in

 or more to wall

120mm/4.72in

 or more to wall

120mm/4.72in

 or more to wall

120mm/4.72in

 or more to wall

36

.5

4

1

9000Btu/h models(A:680/26.77, B:255/10.04, C:170/6.69,  D:92/3.62)

12000Btu/h models(A:770/30.31, B:255/10.04, C:170/6.69,  D:95/3.74)

18000Btu/h models(A:905/35.63, B:275/10.83, C:80/3.15,  D:100/3.94)

22000Btu/h models

>30000Btu/h models

A

A

C

C

D

D

B

B

Right rear side

refrigerant pipe 

hole 

φ

90/3.54

Installation plate

Indoor unit outline

1030/40.55

1450/57.09

21.5/0.85

293/11.54

163/6.42

315/12.4

340/13.39

55

55

/2

.1

7

55

/2

.1

7

55

/2

.1

7

55

/2

.1

7

71.

2/

55

25

/0

.9

8

35/1.38

For more details visit www.MrCool.com

4

INSTALLATION  INSTRUCTIONS

The indoor unit should be installed on the wall at a height of 2.3m/7.55ft or more from the floor.

The indoor unit should be installed allowing a minimum clearance of 15cm/5.9in from the ceiling.

Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.

If the outdoor unit is installed on roof structures or external walls, this may  result in excessive

Accessories

Note:

 Except the above parts provided, the other parts  needed during  installation  you 

must purchase.

Fig.3

Use a stud finder to locate studs to prevent 

unnecessary damage to the wall. 

Two of the A, B and C directions should be 

free from obstructions.

This illustration is for explanation purposes 

only.

Copper lines must be insulated independently.

CAUTION

Mounting  screw  B
ST2.9x10-C-H

Remote  controller

holder

7

8

Remote Controller

6

Quick connecting 

refrigerant pipe

Self-tapping Screw B ST2.9X10

Remote controller

Installation Plate

Name of Accessories

Self-tapping Screw  A ST3.9X25

Seal

(For cooling & heating models only)

Drain Joint

(For cooling & heating models only)

Clip Anchor

Number

Remote controller holder

9

10

11

1
2
3
4
5
6
7
8

1

1(depending on models)

2

1

5-8(depending on models)
5-8(depending on models)

1
1
1
2
1

Quick connecting refrigerant pipe and wire

Optional 

parts

>12cm/4.72in

Air Filter

>12cm/4.72in

>15cm/5.9in 

1

2

3

>2.3m/7.54ft

Air freshening filter(used to install on Air filter)

Sound deadening pads(used to wrap up the

quick connectors)

ON/OFF

MODE

FAN

TEMP

SHORT

   CUT

TIMER ON

TIMER OFF

SLEEP  

SWING  DIRECT

LED  

TURBO 

C

B

A

60cm above

60cm above

30cm above

200cm above

Air Outlet

30cm above

QTY

3

INSTALLATION  INSTRUCTIONS

Selecting installation place

Read completely, then follow step by step.

Indoor unit:

Do not expose the indoor unit to heat or steam.

Select a place where there are no obstacles 

in front or around the unit.

Make sure that condensation drainage can 

be conveniently routed away.

Do not install near a doorway.

Ensure that the space on the left and right 

of the unit is more than 12cm/4.72in.  

Use a stud finder to locate studs to prevent unnecessary damage to the wall. 

The indoor unit should be installed on the wall at a height of 2.3m/7.55ft or more from the floor.

The indoor unit should be installed allowing a minimum clearance of 15cm/5.9in from the ceiling.

Any variations in pipe length will/may require adjustment to refrigerant charge.

There should not be any direct sunlight. Otherwise, the sun will fade the plastic  cabinet and 

affect its appearance. If unavoidable, sunlight prevention should be taken into consideration.

Outdoor unit:

If an awning is built over the outdoor unit to 

prevent direct sunlight or rain exposure, 

make sure that heat radiation from the 

condenser is not restricted.

Ensure that the clearance around the back 

of the unit is more than 30cm/11.81in and left 

side is more than 30cm/11.81in. The front of the 

unit should have more than 200cm/78.74in of 

clearance and the connection side (right side) 

should have more than 60cm/23.62in of clearance.

Do not place animals and plants in the path of the air inlet or outlet.

Take the air conditioner weight into account and select a place where noise and vibration 

will not be an issue.

Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.

If the outdoor unit is installed on a roof structure, make sure unit is level. 

Ensure the roof structure and anchoring method are adequate for the unit location.

Consult local codes regarding rooftop mounting.

If the outdoor unit is installed on roof structures or external walls, this may  result in excessive

noise and vibration, and may also be classed as a non serviceable installation.

Rooftop installation:

Fig.2

Level gauge

Screwdriver

Electric drill,Hole core drill (

φ

90mm/3.54in)

Tools needed for installation:

Hexagonal wrench (4mm/0.157in)

Gas-leak detector (or a soapy spray)

User manual

Thermometer (no required, but recommended)

Multimeter (no required, but recommended)

Measuring tape

Gloves for saftey (especially connecting line set)

Saftey goggles (especially connecting line set)

More than 2.3m/7.55ft

(from the floor)

More than 15cm/5.9in

(to the ceiling)

More than 

12cm/4.72in

More than 

12cm/4.72in

Fig.1

More than30cm/11.81in

More than 

60cm/23.62in

More than

30cm/11.81in

More than 200cm/78.74in

>12cm/4.72in

For more details visit www.MrCool.com

2

Warning  .....................................................................................................................................2

Caution ......................................................................................................................................2

Refrigerant pipe connection ......................................................................................................10

Electrical work .................. .......................................................................................................12

.14

WARNING

      Read the follow

ing

 SAFETY PRECAUTIONS carefully before installation.

      

      Incorrect installation due to ignoring of the instruction will cause harm or damage, and the

      seriousness is classified by the following indications.

Installation must be performed in accordance with the requirement of NEC and CEC by 

      authorized personnel only.

This symbol indicates the possibility of death or serious injury.

The items to be followed are classified by the symbols:

Symbol will background white denotes item that is PROHIBITED from doing.

CAUTION

This symbol indicates the possibility of injury or damage to property.

WARNING

1)  Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water

     leakage, electrical shock or fire.

2)  Install  strictly according to installation instructions. If installation is defective, it will cause water

     leakage, electrical shock or fire.

3) Use only included accessories in this package for installation.

4)  Install at a strong and firm location which is able to withstand the set s weight. If the strength is not enough

     or installation is not properly done, the set will drop and cause injury.

,

5)  For electrical work, follow the local national wiring standard, regulation and these installation instructions. An 

     independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found

     in electrical work, it will cause electrical shock fire.
6)  Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on

     the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7)  Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover 

     is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
8)  When carrying out piping connection, take care not to let air substances other than the specified 

     refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure 

     in the refrigeration cycle, explosion and injury.
9)  Do not modify the length of the power supply cord or use of extension cord, and do not share the 

     single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.

CAUTION

1)  This equipment must be grounded and installed with leakage current breaker. It may cause electrical

     shock if grounding is not perfect.
2)  Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and 

     accumulates at surrounding of the unit, it may cause fire.
3)  Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water 

      may enter the room and damage the furniture.

SAFETY  PRECAUTIONS

For more details visit www.MrCool.com

1

CONTENTS

   

   Contact an authorized service technician for repair or maintenance of this unit.

   Contact the authorized installer for installation of this unit.

   This appliance is not intended for use by persons(including children) with reduced 

   physical, sensory or mental capabilities, or lack of experience and knowledge, unless 

   they have been given supervision or instruction concerning use of the appliance by a 

   person responsible for their safety. 

   Young children should be supervised to ensure that they do not play with the

    air  conditioner.

   If the power cord is to be replaced, replacement work shall be performed by

   authorized personnel only.

   Installation work must be performed in accordance with the national wiring

   standards by authorized personnel only. 

CAUTION

SAFETY  PRECAUTIONS

Warning  .....................................................................................................................................2

Caution ......................................................................................................................................2

INSTALLATION  INSTRUCTIONS

Selecting installation place ........................................................................................................3

Accessories  ...............................................................................................................................4

Indoor  unit  installation ...............................................................................................................8

Outdoor  unit  installation ............................................................................................................9

REFRIGERANT  PIPE  CONNECTION

Refrigerant pipe connection ......................................................................................................10

ELECTRICAL  WORK

Electrical work

 

...........................................................................................................................12

TROUBLESHOOTING

T

roubleshooting

 .........................................................................................................................14

      Read the follow

      

      Incorrect installation due to ignoring of the instruction will cause harm or damage, and the

      seri ousness is classified by the following indications.

      authorized personnel only.

The items to be followed are classified by the symbols:

1)  Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water

     leakage, electrical shock fire.

2)  Install according to this installation instructions strictly

     leakage, electrical shock fire.

3) Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall, 

     water  leakage, electrical shock fire.

4)  Install at a strong and firm location which is able to withstand the set s weight. If the strength is not enough

     or installation is not properly done, the set will drop and cause injury

5)  For electrical work, follow the local national wiring standard, regulation and this installation instructions. 

     independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found

     in electrical work, it will cause electrical shock fire.
6)  Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on

     the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7)  Wiring routing must be properly arranged so that control board cover is fixed properly

     is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
8)  When carrying out piping connection, take care not to let air substances other than the specified 

     refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity

     in the refrigeration cycle, explosion and injury.
9)  Do not modify the length of the power supply cord or use of extension cord, and do not share the 

     single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.

1)  This equipment must be earthed and installed with earth leakage current breaker. It may cause electrical

     shock if grounding is not perfect.
2)  Do not install the unit at place where leakage of flammable gas may occur

     accumulates at surrounding of the unit, it may cause fire.
3)  Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water 

      may enter the room and damage the furniture.

Test Running .....................................................................................................................................13

Please read this manual carefully before installation and keep it for future reference.

ROOM AIR CONDITIONER HEAT PUMP

  Inspect all packaged components thoroughly.

may

N

W

z

z

INVERTER SPLIT  TYPE

Installation Manual

®

DIY Series

For more details visit www.MrCool.com

• 

Please read this installation manual

  completely before installing the product.

• 

Inspect all packaged componets thoroughly.

• 

If the power cord is damaged, replacement

  work may be preformed by authorized

  personnel only.

• 

Installation work must be performed in

  accordance with National Wiring Standards

  by authorized personnel only.

• 

Contact an authorized service technician for

  repair, maintenance or installation of this unit.

©2015 Innovair Corporation.  All Rights Reserved.

www.innovair.com

Summary of Contents for BIN519C2V31

Page 1: ...NATURE INVERTER INSTALLATION MANUAL INVERTER MINI SPLIT SYSTEM 2015 Innovair Corporation All Rights Reserved www innovair com PIN413C2V31 BIN519C2V31 PIN624C2V321 ...

Page 2: ...s unit This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Young children should be supervised to ensure that they do not play with the air conditioner If the power c...

Page 3: ...utlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock fire 6 Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal If connection or fixing is not perfect it will cause heat up or fire at the connection 7 Wiring routing must be properly arranged so that contr...

Page 4: ...orque they will leak but if they are tightened with too much torque the screw connections may suffer damage If you should not be confident about connecting the refrigerant line connectors yourself it is imperative that you contact your customer service team or a refrigeration contractor Important The EQ valves are only designed for one time installation Their seal can not be guaranteed if they are...

Page 5: ...ilter used to install on Air filter 1 depending on models 11 Sound deadening pads used to wrap up the 2 quick connectors Note Except the above parts provided the other parts needed during installation you must purchase Fig 3 c CAUTION Use a stud finder to locate studs to prevent unnecessary damage to the wall Two of the A Band C directions should be free from obstructions This illustration is for ...

Page 6: ...ar side refrigerantpipe hole I 90 3 54in 9000Btu h models A 680 26 77 B 255 10 04 C 170 6 69 D 92 3 62 12000Btu h models A 770 30 31 B 255 10 04 C 170 6 69 D 95 3 74 Indoor unit outline 150mm 5 91in or more to ceilin b c 20mm 4 72in Dimensions are in mm in unless otherwise stated 120mm 4 72in I I or more to wall 1 I I or more to wall I 120mm 4 72in I or more to wall I Left rear side refrigerant Pi...

Page 7: ...stalled correctly as described in the instructions Do not remove the sealing caps and stoppers until immedi ately before you install the lines To prevent leaks ensure that the quick release screw connections are absolutely free of dirt Moisture or foreign bodies will adversely affect the function of the quick release connectors leading to a risk of refrigerant loss not covered by the warranty Only...

Page 8: ...m 2 Align the refrigerant pipes correctly make sure the dimensions of the connecting refrigerant pipe are the same Place the screw connector on the refrigerant pipes just on to the thread on the indoor equipment and tighten the first few threads by hand See Fig 9 IMPORTANT Before you continue it is essential that you read the following instructions carefully 3 Hold the points marked A using a 22mm...

Page 9: ... the indoor unit Be careful not to let the drain hose slack Heat insulate both of the auxiliary piping Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan to overflow inside the unit Never intercross nor intertwist the power wire with any other wiring Run the drain hose sloped downward to drain out the condensed water smoothly 5 In...

Page 10: ... unit with a bolt and nut l 10 or l 8 tightly and horizontally on a concrete or rigid mount Outdoor unit dimension Mounting dimensions mm in WxHxD A mm in B mm in 760 29 92 x590 23 23 x285 11 22 530 20 87 290 11 42 820 32 28 x595 23 43 x330 12 99 523 20 59 340 13 39 780 30 71 x540 21 26 x250 9 84 549 21 61 276 10 87 660 25 98 x242 9 52 x540 21 26 458 18 03 276 10 87 840 33 07 x700 27 56 x320 12 6 ...

Page 11: ...w connector on the refrigerant line just on to the thread on the outdoor unit and tighten the first few threads by hand Fig 22 NOTE The refrigerant pipes must be connected to the valves on the outdoor unit with as little stress as possible IMPORTANT Before you continue it is essential I that you read the following instructions carefully 4 Now tighten the bottom screw connector first and then the t...

Page 12: ...o using a 5 mm Allen key The valve is now open If the valve is not opened fully the system may malfunction and suffer damage Screw the cover back on to the bottom valve and tighten it well to ensure that it is properly sealed See Fig 25 Important The conical ring on the valve has an Newton meter N m Kilogram force meter kgf m 24 4 27 1 2 4 2 7 40 6 47 4 4 1 4 8 61 0 67 7 6 2 6 9 81 3 88 1 8 2 8 9 ...

Page 13: ...Connection at the condesnser slides over the spade Air Handler Connection Air handler preconnected at factory no connection needed Grounding Wire Use screw to connect to ground 2015 Innovair Corporation All Rights Reserved www innovair com ...

Page 14: ...TIONS Remember that if they are tightened with too little torque they will leak but if they are tightened with too much torque the screw connections may suffer damage If you should not be confident about connecting the refrigerant line connectors yourself it is imperative that you contact your customer service team or a refrigeration contractor Important The EQ valves are only designed for one tim...

Page 15: ...ir gap contact separationof at Ieast 3mm ineach active phase conductors Electricalwork Electric safety regulations for the initial Installation 1 If there is serious safety problem about the power supply the technicians should refuse to install the air conditioner and explain to the client until the problem is solved 2 Power voltage should be in the range of 90 11 0 of ratedvoltage 3 The creepage ...

Page 16: ...trical components Secure the cable onto the control board with the cord clamp Connect the cable to the outdoor unit 1 Remove the electricalcontrolboardcover from the outdoorunitby loosening the screw 2 Connect the connective cables to the terminals as identifiedwith their respective matched numbers on the terminalblock of indoor and outdoorunits 3 Secure the cable onto the controlboardwiththe cord...

Page 17: ...Innovair Corporation 11490 NW 39th Street Miami FL 33178 www innovair com 2015 Innovair Corporation All Rights Reserved www innovair com ...

Reviews: