For more details visit www.MrCool.com
The design and specifications are subject to change without prior notice.
. Consult with the sales agency or manufacturer for details.
CS260I-BP11D(QF)
202000192602
20130319
P
Please read this manual carefully before installation and keep it for future reference.
ROOM AIR CONDITIONER
INVERTER SPLIT TYPE
®
DIY Series
For more details visit www.MrCool.com
13
Test running
Perform test operation after completing gas leak check at the flare nut connections and
electrical safety check.
Check that all tubing and wiring have been properly connected.
Check that the gas and liquid side service valves are fully open.
1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.
2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions
works well.
3. When the am
the remote controller to run at cooling mode, manual operation can be taken. Manual
operation is used
Hold the panel sides and lift the panel up to an angle until it remains fixed
with a clicking sound.
Press the Manual control button to select the AUTO or COOL, the unit will
operate under Forced AUTO or COOL mode(see User Manual for details).
4. The test operation should last about 30 minutes.
Connect the cable to the indoor unit
Connect the cable to the outdoor unit
,
Before performing any electrical
work, turn off the power to the system.
1. The inside and outside connecting cable
can be connected without removing the
front grille.
2. The indoor power cord type is H05VV-F
or H05V2V2-F, the outdoor power cord
and interconnected cord type is H07RN-F.
3. Lift the indoor unit panel up, remove the
electrical box cover by loosening the screw.
4. Ensure the color of wires of outdoor unit
and the terminal Nos. are the same to the
indoor s respectively.
5. Wrap those cables not connected with
terminals with insulation tapes, so that
they will not touch any electrical components.
Secure the cable onto the control board
with the cord clamp.
NOTE:
Terminal block of indoor unit
Electronic box
cover
Front Panel
1. Remove the electrical control board cover
from the outdoor unit by loosening the screw.
2. Connect the connective cables to the terminals
as identified with their respective matched
numbers on the terminal block of indoor and
outdoor units.
3. Secure the cable onto the control board with the
cord clamp.
4. To prevent the ingress of water, form a loop of the
connective cable as illustrated in the installation
diagram of indoor and outdoor units.
5. Insulate unused cords (conductors) with PVC-tape.
Process them so they do not touch any electrical or
metal parts.
Cover
Screw
Fig.26
ELECTRICAL WORK
To outdoor unit
To outdoor unit
Cord clamp
L1 L2 S
L1 L2 S
or
To outdoor unit
To outdoor unit
Cord clamp
L N S
L N S
or
Model A
Model B
15
Troubleshooting
For more details visit www.MrCool.com
12
Electric safety regulations for the initial Installation
1. If there is serious safety problem about the power supply, the technicians should refuse to install the air
conditioner and explain to the client until the problem is solved.
2. Power voltage should be in the range of 90%~110% of rated voltage.
3. The creepage protector and main power switch with a 1.5 times capacity of Max. Current of the unit
should be installed in power circuit.
4. Ensure the air conditioner is grounded well.
5. According to the attached Electrical Connection Diagram located on the panel of the outdoor unit to
connect the wire.
6. All wiring must comply with local and national electrical codes and be installed by qualified and skilled
electricians.
7. An individual branch circuit and single receptacle used only for this air conditioner must be available.
See the following table for suggested wire sizes and fuse specifications:
Electrical work
ELECTRICAL WORK
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for
the method of wiring, be guided by the circuit diagram posted on the inside of control
cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come
loose from vibrations to which the unit is subjected during the course of
transportation. Check them and make sure that they are all tightly fastened. (If they
are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated
voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
7) Always install an leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
A)
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the
normal function of the overload.
d
e
x
if
e
h
t
n
i
d
e
t
a
r
o
p
r
o
c
n
i
e
b
l
l
a
h
s
y
l
p
p
u
s
r
e
w
o
p
a
m
o
r
f
n
o
it
c
e
n
n
o
c
s
i
d
r
o
f
s
n
a
e
m
e
h
T
)
9
wiring and have an air gap contact separation of at least 3mm in each active(phase)
conductors.
CAUTION
CAUTION
CAUTION
CAUTION
NOTE
: The cable size and the current of the fuse or switch are determined by the maximum
current indicated on the nameplate which located on the side panel of the unit. Please refer to the
nameplate before selecting the cable, fuse and switch.
Appliance Amps
AWG Wire Size
10
13
18
25
18
16
14
12
30
10
Suggest Minimum Wire Size
(
AWG:
American Wire Gage)
:
14
Troubleshooting
Test running:
Perform test operation after completing gas leak check at the flare nut connections and
electrical safety check.
Check that all tubing and wiring have been properly connected.
Check that the gas and liquid side service valves are fully open.
1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.
2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions
works well.
3. When the am
b
ient temperature is too low(lower than 63 °F), the unit cannot be controlled by
the remote controller to run at cooling mode, manual operation can be taken. Manual
operation is used
when the remote controller is disable
d
or maintenance
is
necessary.
Hold the panel sides and lift the panel up to an angle until it remains fixed
with a clicking sound.
Press the Manual control button to select the AUTO or COOL, the unit will
operate under Forced AUTO or COOL mode(see User Manual for details).
4. The test operation should last 30 minutes.
Manual control
button
AUTO/COOL
TEST RUNNING
Fig.27
Fig.28
14
Model A
Model B
To indoor unit
To indoor unit To power supply
To power supply
L1 L2 S L1 L2
L1 L2 S L1 L2
Terminal block of outdoor unit
To indoor unit
To power supply
1(L) 2(N) S L N
13
Eletrical Specifications
DIY-12
DIY-18
DIY-24
DIY-32
Power Supply
Min. Circuit Amps
Max Fuse
System
115/60/1
208-230/60/1
208-230/60/1
208-230/60/1
20.0A
4.0A
15.0A
16.0A
30.0A
20.0A
25.0A
25.0A
For more details visit www.MrCool.com
ELECTRICAL WORK
12
Connection at the condesnser
slides over the spade.
Condenser Connection
Air Handler Connection
Use screw to connect
to ground.
Air handler preconnected
at factory, no connection
needed.
Grounding Wire
For more details visit www.MrCool.com
11
Coupling size (last 2 part numbers)
Pound-force foot(1bf-ft)
Newton meter(N-m)
Kilogram-force meter(kgf-m)
18 - 20
30 - 35
45 - 50
60 - 65
24.4 - 27.1
40.6 - 47.4
61.0 - 67.7
81.3 - 88.1
2.4 - 2.7
4.1 - 4.8
6.2 - 6.9
8.2 - 8.9
-06(9.5mm/3/8 dash size)
-08(12.7mm/1/2 dash size)
-12(19.1mm/3/8 dash size)
-16(25.4mm/1 dash size)
After
completing
steps
1-
4,
check
that
all
the
connections
are
sealed
correctly
using
leak
detection
spray
or
soap
suds.
If
any
bubbles
form,
the
system has
a
leak
and
the
screw
connectors
must
be
retightened
using
an
open-ended
wrench.
5.
Now
remove
the
cover
on
the
top
valve
using
a
19
mm
open-ended
wrench.
Open
the
valve
by
turning
it
counter-clockwise
as
far
as
it
will
go
using
a
5
mm
Allen
key.
The
valve
is
now
open.
If
the
valve
is
not
opened
fully,
the
system
may
malfunction
and
suffer
damage.
Screw
the
cover
back
on
to
the
top
valve
and
tighten
it
well
to
ensure
that
it
is
properly
sealed. See Fig.24.
6.
Now
remove
the
cover
on
the
bottom
valve
using
a
19
mm
open-ended
wrench.
Open
the
valve by
turning
it
counter-clockwise
as
far
as
it
will
go
using
a
5
mm
Allen
key.
The
valve
is
now
open.
If
the
valve
is
not
opened
fully,
the
system
may
malfunction
and
suffer
damage.
Screw
the
cover
back
on
to
the
bottom valve
and
tighten
it
well
to
ensure
that
it
is
properly
sealed. See Fig.25.
Important!
The conical ring on the valve has an
important sealing function together with the sealing
seat in the caps. Ensure that you do not damage the
cone and that you keep the cap free of dirt and dust.
7.
After
completing
steps
1-
6,
check
that
all
the
connections
are
sealed
correctly
using
leak
detection
spray
or
soap
suds.
If
any
bubbles
form,
the
system
has
a
leak
and
the
screw
connectors
must
be
retightened
using
an
open-
ended
spanner.
8.
Start
the
equipment
so
that
the
operating
pressures
build
up
inside
it.
Check
all
the
connectors
again
for
signs
of
leaks
a)
during
cooling
mode
b)
in
heating
mode.
If
any
bubbles
form,
the
system
has
a
leak
and
the
screw
connectors
must
be
retightened
using
an
open-ended
wrench.
Fig.25
Fig.24
Electric safety regulations for the initial Installation
1. If there is serious safety problem about the power supply, the technicians should refuse to install the air
conditioner and explain to the client until the problem is solved.
2. Power voltage should be in the range of 90%~110% of rated voltage.
3. The creepage protector and main power switch with a 1.5 times capacity of Max. Current of the unit
should be installed in power circuit.
4. Ensure the air conditioner is grounded well.
5. According to the attached Electrical Connection Diagram located on the panel of the outdoor unit to
connect the wire.
6. All wiring must comply with local and national electrical codes and be installed by qualified and skilled
electricians.
7. An individual branch circuit and single receptacle used only for this air conditioner must be available.
See the following table for suggested wire sizes and fuse specifications:
Electrical work
REFRIGERANT PIPE CONNECTION
For more details visit www.MrCool.com
10
1. First remove the water tray on the outdoor unit
as shown in Fig.20.
2. Do not remove the plastic seals from the outdoor
unit and the appropriate refrigerant pipes until
immediately before you connect them, Fig.21.
3. Align the refrigerant pipes correctly so they
line up with the valves and are not stressed.
Place the screw connector on the refrigerant line
just on to the thread on the outdoor unit and
tighten the first few threads by hand, Fig.22.
NOTE:
The refrigerant pipes must be connected
to the valves on the outdoor unit with as little
stress as possible.
IMPORTANT:
Before you continue, it is essential
that you read the following instructions carefully.
4. Now tighten the bottom screw connector first
and then the top screw connector using the
open-ended wrench. Hold the points marked
“
A
”
using a 22mm/0.87in open-ended wrench
and turn the nuts only at the points marked
“
B
”
using a 24mm/0.95in open-ended wrench, see
Fig.23.
Ensure that the screw connectors do not skew
as you tighten them and work quickly. See the
next page for the proper torque.
IMPORTANT: Since the coupling works with
tapping rings, it may leak if you undo and
reconnect the pipes. This will void the
warranty.
CAUT ION:
For your safety, always wear goggles
and work gloves when connecting the pipes.
Fig.20
4. Connecting the refrigerant pipe to outdoor unit
A
B
A B
Fig.21
Fig.22
Fig.23
NOTE:
To distinguish the connectors to be connected
to the indoor unit and outdoor unit, the connectors
of the refrigerant pipe ha
ve
been labelled
“
A
”
,
“
B
”
,
“
C
”
and
“
D
”
. Ensure the marks on the
connector are the same to the indoor s and outdoor s
respectively during connection.
,
,
REFRIGERANT PIPE CONNECTION
For more details visit www.MrCool.com
9
Select the location for installation(follow the previous
notes on selecting the installation place).
If the outdoor unit is higher than the indoor unit,
make sure that a curve is made in the refrigerant
pipe which is lower than the bottom edge of the
indoor unit. See Fig.16.
In the case that the installation place is exposed to
strong wind such as a seaside, make sure the fan
operating properly by putting the unit lengthwise
along the wall or using a dust or shield plates, Fig.17.
If need suspending installation, the installation
bracket should accord with technique requirement
in the installation bracket diagram. The installation
wall should be solid brick, concrete or the same
intensity construction, or actions to reinforce,
damping supporting should be taken. The connection
between bracket and wall, bracket and the air
conditioner should be firm, stable and reliable.
Be sure there is no obstacle which can block radiating air.
Strong
wind
Fig.17
Outdoor unit installation
1. Outdoor installation precaution
2. Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut
φ
10 or
φ
8
tightly and horizontally on a concrete or rigid mount.
Outdoor unit
Refrigerant pipe
Indoor unit
Curve
Fig.16
Fig.18
Fig.19
Drain joint installation
Seal
Drain joint
Base pan hole of
outdoor unit
Seal
Drain pipe
(A)
(B)
For the drain joint with the seal(Fig.19 (A)), first fit the
seal onto the drain joint, then insert the drain joint
。
into the base pan hole of outdoor unit, rotate 90 to
securely assemble them. To install drain joint as
shown in Fig.19 (B), insert the drain joint
into the base pan hole of outdoor unit until it remains
fixed with a clicking sound. Connecting the drain
joint with an extension drain hose (Locally
purchased), in case of the water draining off the
outdoor unit during the heating mode.
NOTE:
The drain joint is slightly different according
to the outdoor unit
specifications
.
Outdoor unit dimension
mm/in(WxHxD)
A(mm/in)
B(mm/in)
530(20.87)
290(11.42)
624(24.57)
560(22.05)
366(14.41)
335(13.19)
549(21.61)
458(18.03)
276(10.87)
276(10.87)
Mounting dimensions
780(30.71)x540(21.26)x250(9.84)
760(29.92)x590(23.23)x285(11.22)
660(25.98)x242(9.52)x540(21.26)
990(38.98)x965(37.99)x345(13.58)
840(33.07)x700(27.56)x320(12.6)
A
W
B
D
Air inlet
Air outlet
Air inlet
1. First remove the water tray on the outdoor unit
as shown in Fig.20.
2. Do not remove the plastic seals from the outdoor
unit and the appropriate refrigerant pipes until
immediately before you connect them, Fig.21.
3. Align the refrigerant pipes correctly so they
line up with the valves and are not stressed.
Place the screw connector on the refrigerant line
just on to the thread on the outdoor unit and
tighten the first few threads by hand, Fig.22.
to the valves on the outdoor unit with as little
stress as possible.
IMPORTANT:
that you read the following instructions carefully.
4. Now tighten the bottom screw connector first
and then the top screw connector using the
open-ended spanner.
and turn the nuts only at the points marked
using a 24mm/0.95in open-ended spanner, see
Fig.23.
Ensure that the screw connectors do not skew
as you tighten them and work quickly. See the
next page for the proper torque.
IMPORTANT: Since the coupling works with
tapping rings, it may leak if you undo and
reconnect the pipes. This will void the
war
CAUT
and work gloves when connecting the pipes.
4. Connecting the refrigerant pipe to outdoor unit
NOTE:
to the indoor unit and outdoor unit, the connectors
of the refrigerant pipe ha
“
connector are the same to the indoor s and outdoor s
respectively during connection.
INSTALLATION INSTRUCTIONS
523(20.59) 340(13.39)
820(32.28)x595(23.43)x330(12.99)
For more details visit www.MrCool.com
8
INSTALLATION INSTRUCTIONS
Do not allow the piping to let out from the back of
the indoor unit.
Be careful not to let the drain hose slack.
Heat insulate both of the auxiliary piping.
Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
Never intercross nor intertwist the power wire
with any other wiring.
Run the drain hose sloped downward to drain
out the condensed water smoothly.
Note: Route the package of pipes/hoses in the
direction of (rear)right or (rear)left. See Fig.13 .
5. Bundle the tubing, connecting cable with tape
securely, evenly as shown in Fig.14.
Because the condensed water from rear of the
indoor unit is gathered in ponding box and is
piped out of room. Do not put anything else in
the box.
CAUTION:
Indoor unit
Connective
pipe
Pipe room
Ponding box
Wrapping belt
Connective
cable
Drain hose
Fig.14
.
.
.
. .
.
.
.
.
.
.
.
.
.
.
.
.
...
..
.
.
.
.
.
.
.
. .
.
Rear-right piping
Rear-left piping
Fig.13
Fig.15
5. Indoor unit installation
1. Feed the package of pipes/hoses through the hole
in the wall.
2. Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the
installation plate.) Ensure that the hooks are
properly seated on the installation plate by moving
it left and right.
3. The female half can easily be made by lifting the
indoor unit with a cushioning material between the
indoor unit and the wall. Get it out after finish piping.
4. Press the lower left and right sides of the unit
against the installation plate until the hooks engage
into their slots.
One side drainage structure is standard. Both sides
drainage structure is optional and can only be
customized from factory.For both sides drainage
structure, it can be choosen for right, left or both
sides drainage connection. If choosing both sides
drainage connection, another proper drain hose is
needed as there is only one drain hose offered by
factory. If choosing one side drainage connection,
make sure the drain hole on the other side is well
plugged. For 9k/12k models, if choosing right side
drainage connection, please choosing right-hand
or right-back piping.The connection of the drain
hose is supposed to be done by qualified installer in
case of water leakage.
For more details visit www.MrCool.com
7
INSTALLATION INSTRUCTIONS
Remember
that
if
they
are
tightened
with
too
little torque
they
will
leak
but
if
they
are
tightened
with too
much
torque,
the
screw
connections
may
suffer
damage.
If
you
should
not
be
confident
about
connecting
the
refrigerant
line
connectors
yourself,
it
is
imperative
that
you
contact
your
customer
service
team
or
a
refrigeration
contractor.
Important! The EQ valves are only designed for
one-time installation. Their seal can not be
guaranteed if they are installed on more than one
occasion. This will also void the warranty.
4.3 Connecting the refrigerant pipes to indoor
unit
1. Do not remove the plastic seals from the indoor
equipment and the appropriate refrigerant pipe
until immediately before you connect them.
2. Align the refrigerant pipes correctly, make sure
the dimensions of the connecting refrigerant pipe
are the same. Place the screw connector on the
refrigerant pipes just on to the thread on the
indoor equipment and tighten the first few threads
by hand. See Fig.9.
IMPORTANT: Before you continue, it is essential
that you read the following instructions carefully.
3. Hold the points marked A using a 22mm/0.87in open-
ended wrench and turn the nuts only at the points
marked B using a 24mm/0.95in open-ended wrench.
See Fig.10a & 10b.
4. Ensure that the screw connectors do not skew as
you tighten them and work quickly.
IMPORTANT: Since the coupling works with tapping
rings, it may leak if you undo and reconnect the
pipes. This will also void the warranty.
5. After finishing the connection, first wrap up the quick
connectors with the sound deadening pads(packed with
accessories) solidly and tightly as shown in Fig.11,
then use the tape to wrap the refrigerant pipe and
connecting cable together. See Fig.12.
NOTE:
For aesthetic reasons, the quick connector parts
are recommended to be placed outside of room.
Fig.9
Fig.10a
Fig.10b
Fig.12
Fig.11
A
B
,,
,,
,,
,,
Note: Route the package of pipes/hoses in the
direction of (rear)right or (rear)left. See Fig.13 .
5. Bundle the tubing, connecting cable with tape
securely, evenly as shown in Fig.14.
Because the condensed water from rear of the
indoor unit is gathered in ponding box and is
piped out of room. Do not put anything else in
the box.
CAUTION:
5. Indoor unit installation
1. Feed the package of pipes/hoses through the hole
in the wall.
2. Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the
installation plate.) Ensure that the hooks are
properly seated on the installation plate by moving
it left and right.
3. The female half can easily be made by lifting the
indoor unit with a cushioning material between the
indoor unit and the wall. Get it out after finish piping.
4. Press the lower left and right sides of the unit
against the installation plate until the hooks engage
into their slots.
Do
not
smoke
during
the
installation
work.
The
equipment
must
never
be
operated
without
the
refrigerant
lines
connected,
otherwise
the
equipment
will
be
damaged
immediately.
The
screw
connections
may
only
be
tightened
using
the
appropriate
open-ended
wrench.
One side drainage structure is standard. Both sides
drainage structure is optional and can only be
customized from factory.For both sides drainage
structure, it can be choosen for right, left or both
sides drainage connection. If choosing both sides
drainage connection, another proper drain hose is
needed as there is only one drain hose offered by
factory. If choosing one side drainage connection,
make sure the drain hole on the other side is well
plugged. For 9k/12k models, if choosing right side
drainage connection, please choosing right-hand
or right-back piping.The connection of the drain
hose is supposed to be done by qualified installer in
case of water leakage.
For more details visit www.MrCool.com
6
2. Drilling
1. Determine hole positions according to
the diagram detailed in Fig.5. Drill
one (1) hole (
φ
90mm/3.54in) slanting
slightly to outdoor side.
2. Always use wall hole conduit when
drilling metal grid, metal plate or the like.
Wall
Indoor
Outdoor
5-
7m
m
/0
.2
-0
.2
8i
n
INSTALLATION INSTRUCTIONS
3. Drainage Installation
1. Run the drain hose sloping downward. Do not
install the drain hose as illustrated in Fig.7.
2. When connecting extension drain hose, insulate
the connecting part of extension drain hose with
a shield pipe, do not let the drain hose slack.
D
Fig.7
Fig.6
Do not form a rise
Do not put the hose
end into water or any
container
4. Connecting the refrigerant pipes
4.1
Tools needed
-You
will
require
the
following
tools
to
carry
out
this
installation
work
correctly:
1x
open-ended
wrench,
19
mm/0.75in
1x
open-ended
wrench,
22
mm/0.87in
1x
open-ended
wrench,
24
mm/0.95in
1x
Allen
key,
5
mm/0.2in
1x
Philips
screwdriver
1x
leak
detection
spray
or
alternatively
soap
suds
(water/detergent mix)
Follow
the
detailed
instructions
for
connecting
the
refrigerant
pipes
to
the indoor unit and
outdoor unit.
We
can
only
provide
a
warranty
if
the
lines
are
installed
correctly
as
described
in
the
instructions.
Do
not
remove
the
sealing
caps
and
stoppers
until
immediately
before
you
install
the
lines.
To
prevent
leaks,
ensure
that
the
quick-release
screw
connections
are
absolutely
free
of
dirt.
Moisture
or
foreign
bodies
will
adversely
affect
the
function
of
the
quick-release
connectors,
leading
to
a
risk
of
refrigerant
loss
(not
covered
by
the
warranty).
Only
install
refrigerant
lines
outdoors
in
dry
weather.
The
refrigerant
lines
must
not
be
installed
and
then
plastered
over.
Please
make
sure
that
refrigerant
is
never
allowed
to
enter
the
environment.
Improper
handling
of
refrigerant
may
be
harmful
to
health.
Always
wear
work
gloves
and
goggles
when
handling
refrigerant.
4.2
Important
information
Refrigerant pipe
Connectors(both ends):
Fig.8
NOTE:
To distinguish the connectors
to be connected to the indoor unit and
outdoor unit, the connectors of the
refrigerant pipe has been labelled
“
A
”
,
“
B
”
,
“
C
”
and
“
D
”
. Ensure the
marks on the connectors are the same
to the indoor s and outdoor s respectively
during connection.
,
,
90/3.54in
refrigerant pipe
or more to wall
18000Btu/h models(A:905/35.63, B:275/10.83, C:80/3.15, D:100/3.94)
Right rear side
refrigerant pipe
90/3.54
For more details visit www.MrCool.com
5
2. Drilling
1. Determine hole positions according to
the diagram detailed in Fig.5. Drill
one (1) hole (
slightly to outdoor side.
2. Always use wall hole conduit when
drilling metal grid, metal plate or the like.
INSTALLATION INSTRUCTIONS
3. Drainage Installation
1. Run the drain hose sloping downward. Do not
install the drain hose as illustrated in Fig.7.
2. When connecting extension drain hose, insulate
the connecting part of extension drain hose with
a shield pipe, do not let the drain hose slack.
4. Connecting the refrigerant pipes
4.1
-You
installation
1x
1x
1x
1x
1x
1x
(water/detergent mix)
4.2
Indoor unit installation
Fig.4
Fig.5
Note:
1. Fitting the Installation Plate
1. Fit the installation plate horizontally
on structural parts of the wall with
spaces around the installation plate.
2. If the wall is made of brick, concrete or
the like, drill five o r eight 5mm/0.197in
diameter holes in the wall. Insert Clip
anchor for appropriate mounting screws.
3. Fit the installation plate o n the wall with
eight or five type A screws.
Correct orientation
of Installation Plate
Fit the Installation Plate and drill
holes in the wall according to the
wall structure and corresponding
mounting points on the installation
plate.
(
Dimensions are in mm & in unless
otherwise stated)
Right rear side
refrigerant pipe
hole
φ
90/3.54in
Right rear side
refrigerant pipe
hole
φ
90/3.54
Left rear side
refrigerant
pipe hole
φ
90/3.54in
Left rear side
refrigerant
pipe hole
φ
90/3.54in
Left rear side
refrigerant
pipe hole
φ
90/3.54in
Left rear side
refrigerant
pipe hole
φ
90/3.54in
Indoor unit outline
Indoor unit outline
150mm/5.91in or more to ceiling
150mm/5.91in or more to ceiling
150mm/5.91in or more to ceiling
150mm/5.91in or more to ceiling
120mm/4.72in
or more to wall
120mm/4.72in
or more to wall
120mm/4.72in
or more to wall
120mm/4.72in
or more to wall
120mm/4.72in
or more to wall
120mm/4.72in
or more to wall
120mm/4.72in
or more to wall
36
.5
4
1
9000Btu/h models(A:680/26.77, B:255/10.04, C:170/6.69, D:92/3.62)
12000Btu/h models(A:770/30.31, B:255/10.04, C:170/6.69, D:95/3.74)
18000Btu/h models(A:905/35.63, B:275/10.83, C:80/3.15, D:100/3.94)
22000Btu/h models
>30000Btu/h models
A
A
C
C
D
D
B
B
Right rear side
refrigerant pipe
hole
φ
90/3.54
Installation plate
Indoor unit outline
1030/40.55
1450/57.09
21.5/0.85
293/11.54
163/6.42
315/12.4
340/13.39
55
55
/2
.1
7
55
/2
.1
7
55
/2
.1
7
55
/2
.1
7
71.
2/
55
25
/0
.9
8
35/1.38
For more details visit www.MrCool.com
4
INSTALLATION INSTRUCTIONS
The indoor unit should be installed on the wall at a height of 2.3m/7.55ft or more from the floor.
The indoor unit should be installed allowing a minimum clearance of 15cm/5.9in from the ceiling.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
If the outdoor unit is installed on roof structures or external walls, this may result in excessive
Accessories
Note:
Except the above parts provided, the other parts needed during installation you
must purchase.
Fig.3
Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
Two of the A, B and C directions should be
free from obstructions.
This illustration is for explanation purposes
only.
Copper lines must be insulated independently.
CAUTION
Mounting screw B
ST2.9x10-C-H
Remote controller
holder
7
8
Remote Controller
6
Quick connecting
refrigerant pipe
Self-tapping Screw B ST2.9X10
Remote controller
Installation Plate
Name of Accessories
Self-tapping Screw A ST3.9X25
Seal
(For cooling & heating models only)
Drain Joint
(For cooling & heating models only)
Clip Anchor
Number
Remote controller holder
9
10
11
1
2
3
4
5
6
7
8
1
1(depending on models)
2
1
5-8(depending on models)
5-8(depending on models)
1
1
1
2
1
Quick connecting refrigerant pipe and wire
Optional
parts
>12cm/4.72in
Air Filter
>12cm/4.72in
>15cm/5.9in
1
2
3
>2.3m/7.54ft
Air freshening filter(used to install on Air filter)
Sound deadening pads(used to wrap up the
quick connectors)
ON/OFF
MODE
FAN
TEMP
SHORT
CUT
TIMER ON
TIMER OFF
SLEEP
SWING DIRECT
LED
TURBO
C
B
A
60cm above
60cm above
30cm above
200cm above
Air Outlet
30cm above
QTY
For more details visit www.MrCool.com
3
INSTALLATION INSTRUCTIONS
Selecting installation place
Read completely, then follow step by step.
Indoor unit:
Do not expose the indoor unit to heat or steam.
Select a place where there are no obstacles
in front or around the unit.
Make sure that condensation drainage can
be conveniently routed away.
Do not install near a doorway.
Ensure that the space on the left and right
of the unit is more than 12cm/4.72in.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
The indoor unit should be installed on the wall at a height of 2.3m/7.55ft or more from the floor.
The indoor unit should be installed allowing a minimum clearance of 15cm/5.9in from the ceiling.
Any variations in pipe length will/may require adjustment to refrigerant charge.
There should not be any direct sunlight. Otherwise, the sun will fade the plastic cabinet and
affect its appearance. If unavoidable, sunlight prevention should be taken into consideration.
Outdoor unit:
If an awning is built over the outdoor unit to
prevent direct sunlight or rain exposure,
make sure that heat radiation from the
condenser is not restricted.
Ensure that the clearance around the back
of the unit is more than 30cm/11.81in and left
side is more than 30cm/11.81in. The front of the
unit should have more than 200cm/78.74in of
clearance and the connection side (right side)
should have more than 60cm/23.62in of clearance.
Do not place animals and plants in the path of the air inlet or outlet.
Take the air conditioner weight into account and select a place where noise and vibration
will not be an issue.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
If the outdoor unit is installed on a roof structure, make sure unit is level.
Ensure the roof structure and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
If the outdoor unit is installed on roof structures or external walls, this may result in excessive
noise and vibration, and may also be classed as a non serviceable installation.
Rooftop installation:
Fig.2
Level gauge
Screwdriver
Electric drill,Hole core drill (
φ
90mm/3.54in)
Tools needed for installation:
Hexagonal wrench (4mm/0.157in)
Gas-leak detector (or a soapy spray)
User manual
Thermometer (no required, but recommended)
Multimeter (no required, but recommended)
Measuring tape
Gloves for saftey (especially connecting line set)
Saftey goggles (especially connecting line set)
More than 2.3m/7.55ft
(from the floor)
More than 15cm/5.9in
(to the ceiling)
More than
12cm/4.72in
More than
12cm/4.72in
Fig.1
More than30cm/11.81in
More than
60cm/23.62in
More than
30cm/11.81in
More than 200cm/78.74in
>12cm/4.72in
For more details visit www.MrCool.com
2
Warning .....................................................................................................................................2
Caution ......................................................................................................................................2
Refrigerant pipe connection ......................................................................................................10
Electrical work .................. .......................................................................................................12
.14
WARNING
Read the follow
ing
SAFETY PRECAUTIONS carefully before installation.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seriousness is classified by the following indications.
Installation must be performed in accordance with the requirement of NEC and CEC by
authorized personnel only.
This symbol indicates the possibility of death or serious injury.
The items to be followed are classified by the symbols:
Symbol will background white denotes item that is PROHIBITED from doing.
CAUTION
This symbol indicates the possibility of injury or damage to property.
WARNING
1) Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water
leakage, electrical shock or fire.
2) Install strictly according to installation instructions. If installation is defective, it will cause water
leakage, electrical shock or fire.
3) Use only included accessories in this package for installation.
4) Install at a strong and firm location which is able to withstand the set s weight. If the strength is not enough
or installation is not properly done, the set will drop and cause injury.
,
5) For electrical work, follow the local national wiring standard, regulation and these installation instructions. An
independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found
in electrical work, it will cause electrical shock fire.
6) Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on
the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7) Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover
is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
8) When carrying out piping connection, take care not to let air substances other than the specified
refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure
in the refrigeration cycle, explosion and injury.
9) Do not modify the length of the power supply cord or use of extension cord, and do not share the
single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
CAUTION
1) This equipment must be grounded and installed with leakage current breaker. It may cause electrical
shock if grounding is not perfect.
2) Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and
accumulates at surrounding of the unit, it may cause fire.
3) Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water
may enter the room and damage the furniture.
SAFETY PRECAUTIONS
For more details visit www.MrCool.com
1
CONTENTS
Contact an authorized service technician for repair or maintenance of this unit.
Contact the authorized installer for installation of this unit.
This appliance is not intended for use by persons(including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety.
Young children should be supervised to ensure that they do not play with the
air conditioner.
If the power cord is to be replaced, replacement work shall be performed by
authorized personnel only.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
CAUTION
SAFETY PRECAUTIONS
Warning .....................................................................................................................................2
Caution ......................................................................................................................................2
INSTALLATION INSTRUCTIONS
Selecting installation place ........................................................................................................3
Accessories ...............................................................................................................................4
Indoor unit installation ...............................................................................................................8
Outdoor unit installation ............................................................................................................9
REFRIGERANT PIPE CONNECTION
Refrigerant pipe connection ......................................................................................................10
ELECTRICAL WORK
Electrical work
...........................................................................................................................12
TROUBLESHOOTING
T
roubleshooting
.........................................................................................................................14
Read the follow
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seri ousness is classified by the following indications.
authorized personnel only.
The items to be followed are classified by the symbols:
1) Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water
leakage, electrical shock fire.
2) Install according to this installation instructions strictly
leakage, electrical shock fire.
3) Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall,
water leakage, electrical shock fire.
4) Install at a strong and firm location which is able to withstand the set s weight. If the strength is not enough
or installation is not properly done, the set will drop and cause injury
5) For electrical work, follow the local national wiring standard, regulation and this installation instructions.
independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found
in electrical work, it will cause electrical shock fire.
6) Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on
the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7) Wiring routing must be properly arranged so that control board cover is fixed properly
is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
8) When carrying out piping connection, take care not to let air substances other than the specified
refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity
in the refrigeration cycle, explosion and injury.
9) Do not modify the length of the power supply cord or use of extension cord, and do not share the
single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
1) This equipment must be earthed and installed with earth leakage current breaker. It may cause electrical
shock if grounding is not perfect.
2) Do not install the unit at place where leakage of flammable gas may occur
accumulates at surrounding of the unit, it may cause fire.
3) Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water
may enter the room and damage the furniture.
Test Running .....................................................................................................................................13
Please read this manual carefully before installation and keep it for future reference.
ROOM AIR CONDITIONER HEAT PUMP
Inspect all packaged components thoroughly.
may
N
W
z
z
INVERTER SPLIT TYPE
Installation Manual
®
DIY Series
For more details visit www.MrCool.com
•
Please read this installation manual
completely before installing the product.
•
Inspect all packaged componets thoroughly.
•
If the power cord is damaged, replacement
work may be preformed by authorized
personnel only.
•
Installation work must be performed in
accordance with National Wiring Standards
by authorized personnel only.
•
Contact an authorized service technician for
repair, maintenance or installation of this unit.
©2015 Innovair Corporation. All Rights Reserved.
www.innovair.com