10.3.2 Indoor / outdoor
unit’s communication diagnosis and solution(E1)
Error Code
E1
Malfunction decision
conditions
Indoor unit does not receive the feedback from outdoor unit during
110
seconds and this condition happens four times continuously.
Supposed causes
●
Wiring mistake
●
Indoor or outdoor PCB faulty
Trouble shooting:
Yes
Yes
Measure Vs, is it moving alternately
with positive value?
(Vs is the voltage between L2 and S
of outdoor unit. Connect the red pin of
multimeter with L2 port, black pin with
S port)
Yes
Power off, then turn on the unit 5 seconds
later(reconnect the power wire).Is the error
still displaying after several minutes?
No
Replace the outdoor main PCB.
Power on. Is the error extinguished?
Check all the wiring with indoor units.
Is the wiring to the indoor main PCB
connected correctly?
Replace the indoor main PCB.
Yes
Replace the outdoor main PCB.
No
Check all the wiring with outdoor
u n i t s . Is the wiring to the outdoor
m a i n PCB connect e d correctly? I s
the reactor connected well?
Power on. Is the error extinguished?
Replace the indoor main PCB.
No
Yes
M e a s u r e t h e r e s i s t a n c e o f t h e
reactor(The one without capacitor).
If it is zero ,follow the below step. If
not, replace a new reactor.
Summary of Contents for BIN312C2V32
Page 7: ...5 2 2 Part names of Indoor Outdoor units ...
Page 14: ...12 6 Wiring Diagram 6 1 Indoor Unit BIN414C2V32 I BIN520C2V32 I ...
Page 15: ...13 BIN625C2V32 IW ...
Page 16: ...14 6 2 Outdoor Unit BIN414C2V32 O BIN520C2V32 O ...
Page 17: ...15 BIN625C2V32 O For BIN414C2V32 O ...
Page 18: ...16 For BIN520C2V32 O For BIN625C2V32 O ...
Page 46: ...44 P U P V ...
Page 47: ...45 P W P N ...