3. IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital
tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
N
U
V
V
W
W
(+)Red
4: Indoor AC Fan Motor
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
RPG13B
RPG15A
RPG20B
RPG28H
RPG45B
Black -
Red
530
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
75
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
381
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
183.6
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
112
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
118.5
Ω±8%
(20
℃/68℉
)
(Brand: Broad
Ocean)
White -
Black
315
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
150
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
267
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
206
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
82
Ω±8%
(20
℃/68℉
)
(Brand:
Welling)
78.5
Ω±8%
(20
℃/68℉
)
(Brand: Broad
Ocean)
Summary of Contents for BIN312C2V32
Page 7: ...5 2 2 Part names of Indoor Outdoor units ...
Page 14: ...12 6 Wiring Diagram 6 1 Indoor Unit BIN414C2V32 I BIN520C2V32 I ...
Page 15: ...13 BIN625C2V32 IW ...
Page 16: ...14 6 2 Outdoor Unit BIN414C2V32 O BIN520C2V32 O ...
Page 17: ...15 BIN625C2V32 O For BIN414C2V32 O ...
Page 18: ...16 For BIN520C2V32 O For BIN625C2V32 O ...
Page 46: ...44 P U P V ...
Page 47: ...45 P W P N ...