17
7 Installation Details
7.1 Wrench torque sheet for
installation
Outside diameter
Torque
Additional tightening
torque
Ф6.35mm
1/4in
1500N.cm(153kgf.cm)
1600N.cm(163kgf.cm)
Ф9.52mm
3/8in
2500N.cm(255kgf.cm)
2600N.cm(265kgf.cm)
Ф12.7mm
1/2in
3500N.cm(357kgf.cm)
3600N.cm(367kgf.cm)
Ф15.9mm
5/8in
4500N.cm(459kgf.cm)
4700N.cm(479kgf.cm)
Ф19mm
3/4in
6500N.cm(663kgf.cm)
6700N.cm(683kgf.cm)
7.2 Connecting the cables
The power cord should be selected according
to the following specifications sheet.
Appliance Amps
AWG Wire Size
10
18
13
16
18
14
25
12
30
10
The cable size and the current of the fuse or
switch are determined by the maximum
current indicated on the nameplate which
located on the side panel of the unit. Please
refer to the nameplate before selecting the
cable, fuse and switch.
7.3 Pipe length and the elevation
Models
Pipe size
Gas
Liquid
BIN414C2V32-I+BIN414C2V32-O
3/8in
(Ф9.52mm)
1/4in
(Ф6.35mm)
BIN520C2V32-I+BIN520C2V32-O
1/2in
(Ф12.7mm)
1/4in
(Ф6.35mm)
BIN625C2V32-IW+BIN625C2V32-O
5/8in
(Ф15.9mm)
3/8in
(Ф9.52mm)
Models
Standard
length
Max.
Elevatio
n
Max.
Length
A
Additional
refrigerant
BIN414C2V32-I+BIN414C2
V32-O
7.5m
(24.6ft)
10m
(32.8ft)
25m
(82.0ft)
15g/m
(0.53oz/3.3ft)
BIN520C2V32-I+BIN520C2
V32-O
7.5m
(24.6ft)
20m
(65.6ft)
30m
(98.4ft)
15g/m
(0.53oz/3.3ft)
BIN625C2V32-IW+BIN625C
2V32-O
7.5m
(24.6ft)
25m
(82.0ft)
50m
(164ft)
30g/m
(1.07oz/3.3ft)
Summary of Contents for BIN312C2V32
Page 7: ...5 2 2 Part names of Indoor Outdoor units ...
Page 14: ...12 6 Wiring Diagram 6 1 Indoor Unit BIN414C2V32 I BIN520C2V32 I ...
Page 15: ...13 BIN625C2V32 IW ...
Page 16: ...14 6 2 Outdoor Unit BIN414C2V32 O BIN520C2V32 O ...
Page 17: ...15 BIN625C2V32 O For BIN414C2V32 O ...
Page 18: ...16 For BIN520C2V32 O For BIN625C2V32 O ...
Page 46: ...44 P U P V ...
Page 47: ...45 P W P N ...