Installation manual
Installation
27
To close the control panel, work carefully through the previously mentioned steps in reverse
order.
1. Exit maintenance mode.
2. Replace the frontplate screws.
Via keypad
3. Exit the Installer menu.
Note
On exiting the Installer menu with the control panel still open, the system panel will not generate an
“Open-panel” event.
Such an event will be generated if the control panel is opened 15 seconds after closing the open/
dislodgement tamper microswitch (
Table 2-5: Sol control panels - internal, C1
).
4-1-5
Connecting to a PC
In order to program the control panel via PC, it is necessary to have the Sol/STUDIO software
(refer to the programming manual) and a connection with the Sol control panel.
It is possible to set up a connection with the PC in the following ways:
• insert the cable with the micro USB terminal in the appropriate port (
Table 2-5: Sol control
panels - internal, Z
)
• insert the LAN cable in the appropriate port, if you have a Sol-LAN/S Ethernet module
(
Table 2-16: LAN modules - description of parts, A
)
• access the WiFI network,if you have a Sol-WIFI/S board
For details regarding the connection, refer to the Sol/STUDIO software manual.
4-2
Installing peripherals
4-2-1
Connecting to the I-BUS line
Any peripheral readers and transceivers of the Sol system (not integrated in the control panel)
must be connected to control panel via the I-BUS.
The connection between the control panel and its peripherals is achieved through a 4 wire (or
more) cable. The cable specifications depend on the length of the BUS (from the panel
terminals to the most distant point), Baud rate and the load current draw.
The connection to the control panel is done using terminals “
+ D S -
” on the motherboard
(
Table 2-5: Sol control panels - internal, L
).
The shield must be connected to the “
-
” terminal at the control panel end only, and must run
along the BUS without being connected to ground at any other point.
The maximum operative distance of the I-BUS line depends on the distribution of the
peripherals on the line and the current draw. The BUS potentiality can be improved by means
of the use of an IB-200 BUS isolator, the characteristics of this are best explained in the
respective manual.
Table 4-2: I-BUS connection
A
Control panel
B
Device
C
Shield
$
³6´
³'´
³´
&
³´
%
%