INIM Electronics ID100 Quick Start Manual Download Page 3

“OR”

; the detector signals alarm status when smoke in the protected environment exceeds the pro-

grammed threshold (programmed as described for the ID100 model) or when the temperature within

the protected environment exceeds the programmed threshold (programmed as described for the

ID200 model). This operating mode, characterized by medium-high sensitivity, allows detection of

fires which generate a substantial amount of smoke but low heat emission (slow burning fires) as

well as fires which generate high temperatures and low smoke emission (chemical products).

“AND”;

the detector signals alarm status when the smoke and temperature in the protected envi-

ronment exceed the programmed thresholds simultaneously (programmed as described for theID100

model and ID200 model respectively). This operating mode, characterized by a low sensitivity,

lowers the false alarm rate and is useful in applications where either the smoke or heat values in the

protected environment may increase without the risk of fire.

Note

Given the limited response, consider the conditions in the protected environment carefully
before selecting this operating mode.

“SMOKE”

; the detector assumes the characteristics of the ID100 model

“HEAT”

; the detector assumes the characteristics of the ID200 model

LED

The bicolour LED (360° viewing) indicates the detector status.

Green blinking at 30-second intervals: detector in standby status (i.e. operating properly).

Green blinking at 5-second intervals: detector in fault status. Further details regarding the cause of the

fault (high contamination level in the smoke chamber, detector component fault, etc.) can be obtained

through the EDRV2000 driver.

Red LED On solid: detector in alarm status.

“R” terminal

The detectors have an output (terminal “R”), for the connection of an alarm repeater LED. This LED will
activate when the detector it refers to triggers an alarm.

Description of the parts

A

Detector

B

Detector notch

C

Thermal probe

D

Red/green LED

E

Optical chamber

F

Technical specifications/serial-number sticker

G

Removable serial-number stickers

H

Cover removing hooks

I

Optical chambre removing hooks

J

Base

K

Base notch 1

L

Base notch 2

M

“+” terminal

N

“-” terminal

O

“R” terminal

P

Short-circuit reed

Q

Screw locations

Installation

Note

For information regarding device placement, coverage and method of installation, refer to the
established standard regulations and codes relating to Automatic fire-detection systems.
Iris series detectors are compliant with EN54-7: Smoke detectors – Point detectors using the
scattered light principle, light transmission or ionization (ID100 and ID300 models only) and
EN54-5: Heat detectors – point detectors (forID200 and ID300 models only),.

The detectors are supplied with protective covers which help to protect them against minor damage and
dust contamination which may occur during the installation phase. The covers should not be removed
until the system is ready to start up.
The detectors can be used with one of the following compatible mounting bases:

EB0010

; standard base

An example of installation using standard bases is shown opposite.

EB0020

; relay base

Appropriate when the detector is to be connected to an intrusion control panel or to a control panel
using 4 wires.

Note

The two removable serial-number stickers should be taken off and one should be attached to
the mounting base and the other to the installation layout.

Once the base is located properly in its placement, place the detector unit onto the base and, with mini-
mum force, turn it clockwise until the detector notch

[B]

aligns with the base notch

[K]

(in order to attach

the detector to the base); turn it still further until notch

[B]

aligns with the second base notch

[L]

(in order

to allow the base to engage with the detector contacts).

Using the EDRV2000 driver

The EDRV2000 driver allows you to change the operating parameters of the detectors, check the con-
tamination level of the smoke chambers and also obtain accurate diagnostic data. It can operate through
the USB port of a computer furnished with the relative software programme, or can function auto-
nomously by way of the battery housed inside.
Each detector is capable of retaining memory (smoke and/or temperature depending on the model) of
the 5 minutes prior to an alarm. Therefore, if an alarm occurs, it will be possible to obtain information
regarding the onset of the fire by simply connecting the EDRV2000 driver to the detection line.

For further information and details regarding use of the EDRV2000 driver, refer to the respective hand-
book.

Testing and maintenance

After installation and during periodic maintenance inspections, you must carry out the following ope-
rations on each detector:

Check the LED

; if the LED blinks at 5 second intervals, the detector is in fault status. This may be due

to dust contamination. If after cleaning, this condition persists, remove the faulty detector and replace it
with a new one. The EDRV2000 driver will assist you in finding the cause of faults.

Optical smoke detector test

; smoke detectors should be tested immediately after installation and perio-

dically during maintenance inspections in accordance with the established standard regulations and
codes in force. To test smoke detectors, use an approved test aerosol strictly in accordance with the
accompanying instructions.
Ensure that the smoke inlet ports to the smoke detection chamber are not blocked. Check the con-
tamination level of the smoke detection chamber via the EDRV2000. If the contamination level is high,
detach the detector from its mounting base and open the chamber then, using a small, soft-bristle brush
or hand-held vacuum cleaner remove all dust particles from inside and around the smoke detection
chamber.
Free the protection mesh from all contaminants.

Heat detector test

; using a suitable device (e.g. hairdryer), create heat in the vicinity of the detector,

then work through the steps described in the device instruction sheet. During each periodic maintenance
inspection, ensure that the heat element is intact and that is not obstructed by dust or paint. If it is, using a
small, soft-bristle brush or hand-held vacuum cleaner remove all contaminants.

Technical specifications

Model

ID100

ID200

ID300

Power supply

from 10 to 30 V

Current draw in standby

90µA

70µA

90µA

Current draw in alarm

Max 40mA

Current draw by the “R” output
(internally limited)

Max 14mA

Dimensions (DxH, standard base
included)

110 x 46 mm

110 x 54 mm

Weight

160g, standard base included

91g, without base

Environmental conditions

Temperature

from -5 to +40 °C

Relative humidity

95 % without condensation

CE mark

0051

INIM Electronics s.r.l.

Via Dei Lavoratori 10 - Fraz. Centobuchi

63076 Monteprandone (AP) - Italy

10

0051-CPR-1875

EN 54-7:2000 + A1:2002 + A2:2006

ID100

Conventional optical smoke detector for fire detection

and fire alarm systems installed in buildings

Essential characteristics

Performance

Nominal activation con-

dition/sensitivity, response delay

(response time) and performance

under fire conditions

PASS

Operational reliability

PASS

Tolerance to supply voltage

PASS

Durability of

operational

reliability:

Temperature resistance

PASS

Vibration resistance

PASS

Humidity resistance

PASS

Corrosion resistance

PASS

Electrical stability

PASS

0051

INIM Electronics s.r.l.

Via Dei Lavoratori 10 - Fraz. Centobuchi

63076 Monteprandone (AP) - Italy

10

0051-CPR-1874

EN 54-5:2000 + A1:2002

ID200

Conventional class P heat detector for fire detection

and fire alarm systems installed in buildings

Essential characteristics

Performance

Nominal activation con-

dition/sensitivity, response delay

(response time) and performance

under fire conditions

PASS

Operational reliability

PASS

Tolerance to supply voltage

PASS

Durability of

operational

reliability:

Temperature resistance

PASS

Vibration resistance

PASS

Humidity resistance

PASS

Corrosion resistance

PASS

Electrical stability

PASS

Detector class (EN54-5): A1R or B

0051

INIM Electronics s.r.l.

Via Dei Lavoratori 10 - Fraz. Centobuchi

63076 Monteprandone (AP) - Italy

10

0051-CPR-1873

EN 54-5:2000 + A1:2002

EN 54-7:2000 + A1:2002 + A2:2006

ID300

Conventional multicriteria optical smoke and class P

heat detector for fire detection and fire alarm systems

installed in buildings

Essential characteristics

Performance

Nominal activation con-

dition/sensitivity, response delay

(response time) and performance

under fire conditions

PASS

Operational reliability

PASS

Tolerance to supply voltage

PASS

Durability of

operational

reliability:

Temperature resistance

PASS

Vibration resistance

PASS

Humidity resistance

PASS

Corrosion resistance

PASS

Electrical stability

PASS

Detector class (EN54-5): A1R or B

Documents for the users

Declarationsof Performance, Declarationsof Conformity
and Certificatesconcerning to Inim ElectronicsS.r.l. pro-
ductsmaybe downloaded free of charge from the web
addresswww.inim.biz, getting accessto Extended
Accessand then selecting "Certifications"or requested to
the [email protected] requested byordi-
narymailto the addressshown in thismanual.

Manualsmaybe downloaded free of charge from the
web addresswww.inim.biz, getting accessto Extended
Accessand then selecting "Manuals".

Warnings and limitations

Iris series detectors must be used exclusively with

fully compliant, compatible controlpanels. Detectors

may not provide timely warning of fire if coverage is

limited by large obstructions (pillars, large machinery,

etc.). When installing or working on a fire detection

system, always refer to and comply with the esta-

blished standard regulations and codes. Appro-

priate fire-risk assessment should be undertaken to

determine the type of detectors required and their

placements.

Manufacturer's details

Manufacturer:

Inim ElectronicsS.r.l.

Production plant:

Centobuchi, via DeiLavoratori10

63076 Monteprandone (AP), Italy

Tel:

+39 0735 705007

Fax:

+39 0735 734912

e-mail:

[email protected]

Web:

www.inim.biz

The personsauthorized bythe manufacturer to repair
or replace the partsof thissystem, hold authorization to
workon Inim Electronicsbrand devicesonly.

About this manual

Manual code:

DCMIIN1PID

Revision:

250

Copyright:

the information contained in thisdocument

isthe sole propertyof Inim ElectronicsS.r.l. No part may
be copied without written authorization from Inim Elec-
tronicsS.r.l.. Allrightsreserved.

WEEE

lnformative notice regarding the disposal of electrical and electronic equipment (applicable in
countries with differentiated waste collection systems)

The crossed-out bin symbolon the equipment or on itspackaging indicatesthat the product must be disposed
of correctlyat the end of itsworking life and should never be disposed of together with generalhousehold
waste. The user, therefore, must take the equipment that hasreached the end of itsworking life to the appro-

priate civicamenitiessite designated to the differentiated collection of electricaland electronicwaste. Asan alternative to
the autonomous-management of electricaland electronicwaste, you can hand over the equipment you wish to dispose
of to a dealer when purchasing new equipment of the same type. You are also entitled to conveyfor disposalsmallelec-
tronic-waste productswith dimensionsof lessthan 25cm to the premisesof electronicretailoutletswith salesareasof at
least 400m2, free of charge and without anyobligation to buy. Appropriate differentiated waste collection for the sub-
sequent recycling of the discarded equipment, itstreatment and itsenvironmentallycompatible disposalhelpsto avoid
possible negative effectson the environment and on health and favoursthe re-use and/or recycling of the materialsit is
made of.

ES

Descripción general

Los detectores de la serie Iris son capaces de detectar la presencia de algunos productos de combustión
y por lo tanto la generación de puntos de incendio.
Los parámetros de funcionamiento de los detectores pueden ser modificados y adecuados a las con-
diciones ambientales a través del dispositivo EDRV2000 entregado por Inim Electronics. A través de
este dispositivo es posible programar los detectores así como valorar la contaminación y el fun-
cionamiento. Para mayores detalles ver el apartado “

Uso del driver EDRV2000

”.

El detector, que en condiciones de stand-by posee una baja absorción, 80µA, en caso de alarma
aumenta la corriente absorbida hasta un máximo de 40mA, indicando de este modo el peligro a la cen-
tral de control.
Inim Electronics pone a disposición tres modelos de detectores convencionales de la serie Iris que pue-
den reconocerse a través de la etiqueta de datos de la matrícula que se encuentra situada sobre la parte
trasera. Esta etiqueta lleva un número de serie unívoco que identifica al dispositivo.

Modelos

ID100

Detector óptico dotado de una cámara de prueba basada en el efecto de la difusión de la luz (efecto Tyn-
dall). Para garantizar la eficacia no deben existir obstáculos en la entrada de aire en el interior de la
cámara de prueba y el detector no debe ser expuesto directamente a corrientes de aire.

Manuale d'istruzioni/ Instruction manual/ Manualde instrucciones/ Notice d’instructions

Inim ElectronicsS.r.l. © 2020

DCMIIN1PID-250-20200618

Summary of Contents for ID100

Page 1: ...i da scarsa emissione di fumo o di ottenere un rivelatore con una maggiore immunità ai falsi allarmi Funzionamento Modalità Le modalità di funzionamento impostabili per mezzo del programmatore EDRV2000 sono PLUS pre impostata il rivelatore segnala una condizione di allarme nel caso in cui venga supe rato il valore di soglia di fumo impostabile come descritto per il modello ID100 o nel caso in cui ...

Page 2: ... risposta e prestazioni in condizioni di incendio PASS Affidabilità di funzionamento PASS Tolleranza al voltaggio di ali mentazione PASS Durabilità dell affidabilità di fun zionamento Resistenza termica PASS Resistenza alle vibra zioni PASS Resistenza all umidità PASS Resistenza alla cor rosione PASS Stabilità elettrica PASS Classe del rivelatore EN54 5 A1R o B Documentazione per gli utenti Dichia...

Page 3: ...x 46 mm 110 x 54 mm Weight 160g standard base included 91g without base Environmental conditions Temperature from 5 to 40 C Relative humidity 95 without condensation CE mark 0051 INIM Electronics s r l Via Dei Lavoratori 10 Fraz Centobuchi 63076 Monteprandone AP Italy 10 0051 CPR 1875 EN 54 7 2000 A1 2002 A2 2006 ID100 Conventional optical smoke detector for fire detection and fire alarm systems i...

Page 4: ...ctor Uso del driver EDRV2000 El driver EDRV2000 permite modificar los parámetros de funcionamiento de los detectores valorar el estado de contaminación y realizar un diagnóstico detallado El driver puede ser utilizado conectado a una puerta USB de un PC sobre el que se encuentra en ejecución el software suministrado con el apa rato o de manera autónoma gracias a la batería que se encuentra conteni...

Page 5: ...rt toutes les 5 secondes détecteur en panne plus de détails sur la cause de la panne contamination excessive de la chambre optique panne du détecteur etc peuvent être obtenus à travers l appareil EDRV2000 Voyant rouge allumé fixe détecteur en alarme Terminal R Les détecteurs sont dotés d une sortie le terminal R pour la connexion d un voyant de répétition d alarme Ce voyant est activé quand le dét...

Page 6: ...foyerd incendie éléments au plafonds etc Faire référence à la norme locale applicable pourl installation correcte et l entretien du système une évaluation précise du risque d incendie doit être faite avant de choisirle type de détecteuret son positionnement Données du constructeur Constructeur Inim ElectronicsS r l Site de production Centobuchi via DeiLavoratori10 63076 Monteprandone AP Italy Tel ...

Reviews: