Unpacking the unit 

The serial number of the equipment is its unique identifier.  This number must be referenced in any communication 

with Ingeteam Energy S.A. 

Never stack more than 20 TL units or more than 10 units with their transformers on a Europallet. In the case of units 

with transformers, the transformers are to be laid on the first two layers and half the third:

Transport damage

If the equipment has been damaged during transport: 
1) do not proceed with the installation 
2) notify the distributor immediately within 5 days of receipt. 
If ultimately the unit has to be returned to the manufacturer, you must use the same original packaging. 

Recycling the Packaging 

All the packaging can be delivered to a non-hazardous waste management company. 
In any event, each part of the packaging may be recycled as follows: 
Plastic (polystyrene, bag and bubble wrap):  Yellow municipal container (plastic and bottles). 
Cardboard:  Municipal blue container (paper and cardboard). 

3.3 Handling

Correct handling of the units is vitally important in order to:

- Prevent damage to the packaging which enables them to be kept in optimum condition from 

shipping until they are unpacked.

- Avoid knocks and/or falls which may harm their mechanical characteristics, e.g. cause incorrect 

closure of doors, loss of IP rating, etc.

- Avoid, as far as possible, vibrations which may cause subsequent malfunction.

If you observe any anomaly, please contact INGETEAM immediately.

Installation Manual

 

INGECON

® 

SUN LITE

AAY2000IKI01

AAY2000IKI01

Rev. _B

Date: March 2011

Page   18      

18      

      

La copia, circulación o uso de este documento o de su contenido requiere un permiso por escrito. Su in-

cumplimiento será denunciado por daños y perjuicios. Todos los derechos están reservados, incluyendo 

aquellos que resulten de derechos de patentes o registro del diseño.

La correspondencia del contenido del documento con el hardware ha sido comprobada. Sin embargo, 

pueden existir discrepancias. No se asume ninguna responsabilidad por la concordancia total. La infor-

mación que contiene este documento es revisada regularmente y es posible que se produzcan cambios 

en siguientes ediciones.

El presente documento es susceptible de ser cambiado.

The copy, distribution or use of this document or of its content requires written authorisation. Any 

breach thereof will be reported for damages. All rights reserved including those of patent rights or 

design registration.

The conformity of the document content with the hardware described has been checked. However, 

discrepancies may exist. Liability will not be assumed for total concordance. The information contained 

in this document is regularly revised and it is possible that there may be changes in subsequent 

editions.Other functions may be available which are not covered by this document. 

This document may be changed.

Manual de instalación

 

INGECON

® 

SUN LITE

AAY2000IKH01

AAY2000IKH01

Rev. _B

Fecha: Marzo 2011

Page   2      

TL inverters

Transformers 

Inverters

Summary of Contents for Ingecon Sun 2.5

Page 1: ...Ingeteam Energy S A 03 2011 INGECON SUN LITE Ingecon Sun Lite Installation Manual Rev _B AAY2000I KI 01...

Page 2: ...o registro del dise o La correspondencia del contenido del documento con el hardware ha sido comprobada Sin embargo pueden existir discrepancias No se asume ninguna responsabilidad por la concordancia...

Page 3: ...n Manual INGECON SUN LITE AAY2000IKI01 AAY2000IKI01 Rev _B Date March 2011 Page 3 DOCUMENTACI N RELACIONADA CAT LOGOS MANUALES Manual de Usuario Ingecon Sun LITE AAY2000IKE01 Manual de Instalaci n Ing...

Page 4: ...not imply lack of voltage inside Only qualified personnel may open them following the instructions in this manual CAUTION There is a risk of electric shock even after disconnecting the network and PV...

Page 5: ...Italy DIN VDE 0105 100 and DIN VDE 1000 10 in Germany UTE C15 400 in France CAUTION Compliance with the safety instructions set out in this manual or in the suggested legislation does not imply exempt...

Page 6: ...011 Page 6 La copia circulaci n o uso de este documento o de su contenido requiere un permiso por escrito Su in cumplimiento ser denunciado por da os y perjuicios Todos los derechos est n reservados i...

Page 7: ...unit is operating Disconnect and check for absence of voltage first PERSONAL PROTECTION EQUIPMENT PPE CAUTION The standard personal protective equipment is Safety goggles for mechanical hazards Safet...

Page 8: ...5 Inspection control and handling tasks 25 4 5 1 Inspection tasks 25 4 5 2 Control tasks 25 4 5 3 Handling tasks 26 Installation Manual INGECON SUN LITE AAY2000IKI01 AAY2000IKI01 Rev _B Date March 20...

Page 9: ...reventive maintenance 40 7 1 Maintenance tasks 40 8 Troubleshooting 42 8 1 LED indications 42 8 1 1 Green LED 42 8 1 1 1 1 second flashing 42 8 1 1 2 3 second flashing 42 8 1 1 3 Steady light 42 8 1 2...

Page 10: ...R SINGLE PHASE family which has its own manual 00000 Paneles Solares Fotovoltaicos Inversor Fotovoltaico Contador Protecciones Red de Distribuci n El ctrica 00000 Paneles Solares Fotovoltaicos Inverso...

Page 11: ...th the standard VDE 0126 1 1 Automatic disconnection for generating installations connected in parallel with the low voltage grid Compliance with this standard must be requested on ordering the unit 1...

Page 12: ...ent temperature must not exceed 40 C 2 System description Installation Manual INGECON SUN LITE AAY2000IKI01 AAY2000IKI01 Rev _B Date March 2011 Page La copia circulaci n o uso de este documento o de s...

Page 13: ...it and 20 cm below and at the sides must be left free of obstacles Only in this way will the unit s cooling system be able to operate correctly The cooling system designed for the unit varies from one...

Page 14: ...s derechos est n reservados incluyendo aquellos que resulten de derechos de patentes o registro del dise o La correspondencia del contenido del documento con el hardware ha sido comprobada Sin embargo...

Page 15: ...three upper drilled holes and where the bottom hole will be It also shows the approximate vertical distance to the level of the top edge of the inverter which will subsequently be attached to the tran...

Page 16: ...ndencia del contenido del documento con el hardware ha sido comprobada Sin embargo pueden existir discrepancias No se asume ninguna responsabilidad por la concordancia total La infor maci n que contie...

Page 17: ...which transformer corresponds to each unit by means of the serial number shown on the shipping label 3 Operating conservation and transport conditions CONTENTS PACKING WEIGHT kg HEIGHT WIDTH LENGTH m...

Page 18: ...may cause subsequent malfunction If you observe any anomaly please contact INGETEAM immediately Installation Manual INGECON SUN LITE AAY2000IKI01 AAY2000IKI01 Rev _B Date March 2011 Page La copia circ...

Page 19: ...respect to the forks 2 Try to locate it as close as possible to the connection between the forks and the chassis 3 Ensure that the forks are perfectly level to avoid overturning the unit 4 In any case...

Page 20: ...ment will inform the authorised manager via this Section of the location of components to be decontaminated The elements within the unit that must be handled individually are 1 Electrolytic condensers...

Page 21: ...CAT LOGOS MANUALES Manual de Usuario Ingecon Sun LITE AAY2000IKE01 Manual de Instalaci n Ingecon Sun LITE AAY2000IKH01 Manual de Instalaci n de los Accesorios de Comunicaci n AAX2002IKH01 Ingecon Sun...

Page 22: ...on to comply with the legislation applicable to electrical work The fact that the various compartment housings are open in no way implies the ab sence of voltage Only qualified personnel following the...

Page 23: ...erhead electricity lines must be interrupted in the case of storms INGETEAM accepts no liability for any damages caused by improper use of the equip ment Any work carried out on any equipment which im...

Page 24: ...ety standards Inform the worker of the risk Comply with that laid down in the legislation applicable to the installation in which the unit is lo cated both that for the type of installation and the co...

Page 25: ...andling tasks on this unit are defined below 4 5 1 Inspection tasks Opening system The cover is opened and closed using a system requiring tools to remove it fasteners IT IS STRICTLY FORBIDDEN TO GAIN...

Page 26: ...rch 2011 Page La copia circulaci n o uso de este documento o de su contenido requiere un permiso por escrito Su in cumplimiento ser denunciado por da os y perjuicios Todos los derechos est n reservado...

Page 27: ...inlets and outlets to obstruct proper ventilation of the unit 5 2 Fixing the unit to the wall INGECON SUN LITE units have a system for anchoring to the wall TL units A fixing plate is supplied attach...

Page 28: ...ito Su in cumplimiento ser denunciado por da os y perjuicios Todos los derechos est n reservados incluyendo aquellos que resulten de derechos de patentes o registro del dise o La correspondencia del c...

Page 29: ...be made between a nut and bolt or the use of a padlock Check that the transformer is secured well The following drawings show the steps to take Installation Manual INGECON SUN LITE AAY2000IKI01 AAY20...

Page 30: ...servados incluyendo aquellos que resulten de derechos de patentes o registro del dise o La correspondencia del contenido del documento con el hardware ha sido comprobada Sin embargo pueden existir dis...

Page 31: ...cables This entrance can be used for access to the DC connection by cable access to the insulation fault contact access for other accessories 1 PG20 and 6 PG 12 for INGECON SUN 2 5 TL INGECON SUN 2 5...

Page 32: ...a circulaci n o uso de este documento o de su contenido requiere un permiso por escrito Su in cumplimiento ser denunciado por da os y perjuicios Todos los derechos est n reservados incluyendo aquellos...

Page 33: ...L 6TL PV panels Inverter Electricity company panel Thermomagnetic circuit breaker kWh meter TL UNIT PHYSICAL CONNECTION DIAGRAM grid Ingecon Sun 2 5TL 3TL 3 3TL 3 68TL 4 6TL 5TL 6TL PV panels Inverter...

Page 34: ...nd to the electricity grid The inverter s metal parts unit ground are electrically connected to the ground pin in the grid connection quick connector To ensure the safety of personnel this terminal mu...

Page 35: ...un Maximum inverter current Rated current for the gL type fuse Rated current for the type B MCB 2 5 TL 13 20 20 3 TL 17 25 25 3 3 TL 17 25 25 3 68 TL 17 25 25 3 8 TL 18 8 25 25 4 6 TL 24 4 32 32 5 TL...

Page 36: ...ter even under the most adverse conditions e g an ambient temperature of 10 C In the case of damage due to the DC voltage exceeding 550 Vdc Ingeteam Energy S A accepts no liability for such damage CAU...

Page 37: ...he side or rear of the inverter these can reach high temperatures Installation work requiring opening the unit should be done in a dry environment so that no moisture left inside could condense and da...

Page 38: ...sufficient length so that they do not pull on the internal electrical connection terminals Make sure that the unused knock outs have not been opened Firmly tighten the cable glands to guarantee seali...

Page 39: ...sealing check has been carried out proceed to connect power to the unit while keeping it switched off following the guidelines in the instruction manual for the unit installed The tasks outlined for...

Page 40: ...If moisture exists dry before making electrical connections Check the correct fixing of the housing components to their corresponding anchoring points Installation Manual INGECON SUN LITE AAY2000IKI0...

Page 41: ...ard handling display reading and access to the unit s various in ternal components Installation Manual INGECON SUN LITE AAY2000IKI01 AAY2000IKI01 Rev _B Date March 2011 Page DOCUMENTACI N RELACIONADA...

Page 42: ...ions cable if the communications installation is fixed or because the inverter is resetting in which case the flashing will be momentary If the flashing is not accompanied by this message on the displ...

Page 43: ...fault current or differential current protection has tripped An insulation fault can pose a hazard to personnel The repair of an insulation fault must be carried out by qualified personnel Procedure...

Page 44: ...again and press OK Installation Manual INGECON SUN LITE AAY2000IKI01 AAY2000IKI01 Rev _B Date March 2011 Page La copia circulaci n o uso de este documento o de su contenido requiere un permiso por es...

Page 45: ...e LEDs Green LED 1 second flashing Start up process 3 second flashing Standby due to low irradiance On Inverter connected to the grid Orange LED 0 5 second flashing The external fan is not working cor...

Page 46: ...ge date Start Stop Reset partial data Change inverter number 12 00 12 04 10 MONITORING Pout 5000 W Vac 229 V Iac 21 83 A Fac 49 89 Hz PhiCos 0 998 12 00 12 04 10 MAIN MENU Monitoring Configuration Lan...

Page 47: ...be requested from Ingeteam s customer services SN Serial Number Screen 4 TotE Total energy in kWh delivered by the inverter to the grid from the date it was manufactured Recording the serial number of...

Page 48: ...tion changes are described below 9 5 1 Country Normative Press OK on the COUNTRY NORMATIVE option from the CONFIGURATION submenu 12 00 12 04 10 CONFIGURATION GRID VOLTAGE GROUNDING OTHER ADJUSTMENTS C...

Page 49: ...V1 2004 for changes to configuration for ITALY Two labels will be included together with the unit documentation to stick under the ratings plate in these cases The illustration shows where these are...

Page 50: ...al INGECON SUN LITE AAY2000IKI01 AAY2000IKI01 Rev _B Date March 2011 Page La copia circulaci n o uso de este documento o de su contenido requiere un permiso por escrito Su in cumplimiento ser denuncia...

Page 51: ...ption to change the upper and lower voltage and frequency protection limits Shown as an example is the screen for changing the upper frequency limit Press OK The value for the maximum frequency limit...

Page 52: ...ISH Continue Confirm OK Installation Manual INGECON SUN LITE AAY2000IKI01 AAY2000IKI01 Rev _B Date March 2011 Page La copia circulaci n o uso de este documento o de su contenido requiere un permiso po...

Page 53: ...ER 12 00 12 04 10 MAIN MENU Change date Reset partial data Change inverter number Start Stop 12 00 09 01 09 Change to Stop OK Cancel ESC ON OFF 9 8 Start Stop The operation of the inverter can be stop...

Page 54: ...en the AUTOTEST is complete The AUTOTEST process can be interrupted at any time by selecting the STOP AUTOTEST option which appears in place of START AUTOTEST while it is being carried out Once an aut...

Page 55: ...T LOGOS MANUALES Manual de Usuario Ingecon Sun LITE AAY2000IKE01 Manual de Instalaci n Ingecon Sun LITE AAY2000IKH01 Manual de Instalaci n de los Accesorios de Comunicaci n AAX2002IKH01 Ingecon Sun Ca...

Page 56: ...Ingeteam Energy S A www ingeteam com Avda Ciudad de la Innovaci n 13 31621 Sarriguren Navarra SPAIN Tel 34 948 288 000 Fax 34 948 288 001 http www ingeteam com...

Reviews: