Wiring requirements
The correct wiring of the equipment to any PV installation will be done
respecting the mandatory minimum section types of wire. We provide the
minimum size standarized types of wire. Wider wires can be used whenever the
wires would be compatible with the terminals, would have enough space to go
through the conduit.
AC Terminals Ingecon Sun 15U 208. Use 194ºF (90ºC) wire, either 8/AWG
copper or 6/AWG aluminium:
- Copper wires:
Minimun 8/AWG 0.012 in² (8.35 mm²)
- Aluminium wires:
Minimun 6/AWG 0.02 in² (13.3 mm²)
The wiring have to comply with the provisions of the National Electrical Code
ANSI/NEPA70, Canadian Electrical Code CEC and other Local or State Codes.
AC Terminals Ingecon Sun 15U 480. Use 12/AWG 194ºF (90ºC) wire:
- Copper wires:
Minimun 12/AWG 0.012in² (8.35 mm²)
- Aluminium wires:
Minimun 12/AWG 0.02in² (13.3 mm²)
The wiring have to comply with the provisions of the National Electrical Code
ANSI/NEPA70, Canadian Electrical Code CEC and other Local or State Codes.
DC Terminals Ingecon Sun 15U 208 and Ingecon Sun 15U 480.Use 194ºF
(90ºC) wire, either 8/AWG copper or 6/AWG aluminium:
- Copper wires:
Minimun 8/AWG 0.012in² (8.35 mm²)
- Aluminium wires:
Minimun 6/AWG 0.02in² (13.3 mm²)
The wiring have to comply with the provisions of the National Electrical Code
ANSI/NEPA70, Canadian Electrical Code CEC and other Local or State Codes.
DC Terminals Ingecon Sun 15U 208 and Ingecon Sun 15U 480 with multi input.
Use 194ºF (90ºC) wire, either 10/AWG copper or 10/AWG aluminium:
- Copper wires:
Minimun 11/AWG 0.006in² (4.14 mm²)
- Aluminium wires:
Minimun 11/AWG 0.006in² (4.14 mm²)
Multi input connectors admit a maximun current of A.
The wiring have to comply with the provisions of the National Electrical Code
ANSI/NEPA70, Canadian Electrical Code CEC and other Local or State Codes.
AC Terminals Ingecon Sun 25U 208. Use 194ºF (90ºC) wire, either 6/AWG
copper or 4/AWG aluminium:
- Copper wires:
Minimun 6 AWG 0.02in² (13.3 mm²)
- Aluminium wires:
Minimun 4/AWG 0.032in² (21.2 mm²)
The wiring have to comply with the provisions of the National Electrical Code
ANSI/NEPA70, Canadian Electrical Code CEC and other Local or State Codes.