Make a visual inspection to ensure that
the bars connecting the AC
lead-in maintain their safety distances and also their electrical properties.
Check
that there is no moisture in the cabinet interior.
If moisture is detected, it is essential to dry it up before making the electrical
connections.
Check
that the cabinet components are correctly secured to their corres-
ponding anchors.
Check
that the equipment is correctly ventilated. To do so:
Check
the condition of the air outlet fans and clean and replace if neces-
sary.
Clean the ventilation grids.
Check
the condition of the front ventilation grid filters.
To do so, dismount the air intake grid, the filter is inside it.
- Unscrew the four screws securing the grid and which are accessed from
the inside face of the door.
- Dismount the grid.
- Remove the filter from inside the grid