Revision History

Added Factory Preset List (

Table 1, p. 9

).

Introduction

The purpose of this service bulletin is to provide 
information for verification of correct values for certain 
factory-preset tuning parameters.

The action described in this bulletin is not being 
taken to address a safety concern.

Affected Units

All Intellipak™ units.

Discussion

Rooftop units with Intellipak controls (S-HF 20 through 75 
Tons and S-HG 90 through 130 Tons units) contain 
parameters - adjustable through the human interface 
module - that ‘tune’ the control loops.

Values for these parameters are downloaded at the 
factory. If the values are wrong, poor temperature or 
pressure control can result. In particular, the following 
symptoms have been observed:

Even with a call for cooling, the economizer seems 
stuck at some position between minimum and 100%.

With a call for cooling, compressors are not operating.

On a VAV unit, the supply air temperature is offset 6 to 
10ºF above setpoint.

Some units with serial numbers between J93K and J94D 
have one or more incorrect preset values for these 
parameters.

Corrective Action

1.

Press the SETUP key on the Human Interface module. 
Using the NEXT or PREVIOUS key, scroll to this 
display:

2. Press the ENTER key. Then, as you press the NEXT key 

repeatedly, you will see a series of displays that show 
the values of Control Algorithm Tuning Parameters.

3.

Figure 1

 represents the entire list of displays, showing 

the correct factory-preset values. Any particular unit 
will contain only a portion of this list of displays.

WARNING

Personal Protective Equipment (PPE) 
Required!

Failure to wear proper PPE for the job being undertaken 
could result in death or serious injury. Technicians, in 
order to protect themselves from potential electrical, 
mechanical, and chemical hazards, MUST follow 
precautions in this manual and on the tags, stickers, 
and labels, as well as the instructions below:

Before installing/servicing this unit, technicians 
MUST put on all PPE required for the work being 
undertaken (Examples; cut resistant gloves/sleeves, 
butyl gloves, safety glasses, hard hat/bump cap, fall 
protection, electrical PPE and arc flash clothing). 
ALWAYS refer to appropriate Material Safety Data 
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA 
guidelines for proper PPE.

When working with or around hazardous chemicals, 
ALWAYS refer to the appropriate MSDS/SDS and 
OSHA/GHS (Global Harmonized System of 
Classification and Labelling of Chemicals) guidelines 
for information on allowable personal exposure 
levels, proper respiratory protection and handling 
instructions.

If there is a risk of energized electrical contact, arc, or 
flash, technicians MUST put on all PPE in accordance 
with OSHA, NFPA 70E, or other country-specific 
requirements for arc flash protection, PRIOR to 
servicing the unit. NEVER PERFORM ANY 
SWITCHING, DISCONNECTING, OR VOLTAGE 
TESTING WITHOUT PROPER ELECTRICAL PPE AND 
ARC FLASH CLOTHING. ENSURE ELECTRICAL 
METERS AND EQUIPMENT ARE PROPERLY RATED 
FOR INTENDED VOLTAGE.

WARNING

Proper Field Wiring and Grounding 
Required!

All field wiring MUST be performed by qualified 
personnel. Improperly installed and grounded field 
wiring poses FIRE and ELECTROCUTION hazards. To 
avoid these hazards, you MUST follow requirements for 
field wiring installation and grounding as described in 
NEC and your local/state electrical codes. Failure to 
follow code could result in death or serious injury.

Control Algorithm Tuning Parameters

Press Enter to View or Adjust

Summary of Contents for Trane Intellipak

Page 1: ...and labels that are attached to the equipment Control Algorithm Tuning Parameters Intellipak Rooftop Units General Service Bulletin ATTENTION Warnings Cautions and Notices appear at appropriate sectio...

Page 2: ...plays showing the correct factory preset values Any particular unit will contain only a portion of this list of displays WARNING Personal Protective Equipment PPE Required Failure to wear proper PPE f...

Page 3: ...een shown only for units with Dehumidification Installed SA Reheat Control Gains Proportional XX X F Reset Time XXX Sec Range 0 2 20 0 Range 5 600 Default 3 3 Default 50 Note XXX Sec field becomes DIS...

Page 4: ...Default 1800 Note XXX Sec field becomes DISABLE if 3600 seconds Screen shown only for CV units Zone Control Occupied Cooling Gains Proport Bias XXX Max Cy Rate X X CPH Range 0 400 Range 1 5 6 0 Defaul...

Page 5: ...for the number of configured heat stages If heat stages are not configured it will place 30 F in the field as a default until heat stages are configured This will happen once at power up if needed an...

Page 6: ...pply Air Temp High Limit XX X F Range 80 140 Default 120 Screen shown only for VAV units Supply Air Pressure Gain Proportional XX X IWC Reset Time XXX Sec Range 0 2 20 0 Range 1 60 Default 3 3 Default...

Page 7: ...0 Default 17 s Default 80 Note XXXXs field becomes DISABLE and Prop and Feedforward items are not shown if Reset Time 1000 s on Ipak 1 units only Screen shown only for RT or RT AH units with DX Coolin...

Page 8: ...hen Temp Above Setpoint Disable is displayed when the value is incremented above 255 A selection of Disable disables wheel shutoff changes to screen below and allows continuous wheel operation when co...

Page 9: ...et Time w VSC wo VSC 100 Sec 50 Sec ___________ Setup CV Air Economizer Control Gains Proportional 10 0 F ___________ Setup Reset Time DISABLE ___________ Setup Rate Time 0 Sec ___________ Setup Bias...