4. Referring to 

Figure 1

, if a value other than the factory 

preset is shown, place the cursor beneath that value 
and press the + and - keys to adjust it to the factory 
preset value. Then press the ENTER key to set the 
change. The display will prompt you to enter a 
password.

The password is “+ + - +”. After entering the password, 
press the ENTER key again. It won’t be necessary to 
enter the password again for the next 15 minutes.

Important:

The factory-preset values have been chosen 
to provide stable but responsive control 
loops. These values 

MUST NOT

 be further 

adjusted from the factory presets.

Figure 1.

Control algorithm tuning parameter setup 
submenu screens

Screen always shown 

  Control Algorithm Tuning Parameters 

 

  Press ENTER to Review or Adjust 

 

 

Screen shown only for units with Dehumidification Installed 

  SA Reheat Control Gains 

 

  Proportional XX.X %/F  Reset Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 0.2-20.0 

 

Range 5-600 

 

 

Default 3.3 

 

Default 50 

 

Note: “XXX Sec” field becomes “DISABLE” if > 3600 seconds 

Screen shown only for VAV or SZVAV units 

  VAV Cooling Control Gains 

 

  Proportional XX.X %/F  Reset Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 0.2-20.0 

 

Range 5-600 

 

 

Default 3.3 

 

Default 50 

 

Note: “XXX Sec” field becomes “DISABLE” if > 3600 seconds 

 

Screen shown only for IntelliPak II VAV or SZVAV units with Electric heat installed 

  VAV Heating Control Gains 

 

  Proportional XX.X %/F  Reset Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 0.2-20.0 

 

Range 5-600 

 

 

Default 3.3 

 

Default 50 

 

Note: “XXX Sec” field becomes “DISABLE” if > 3600 seconds 

 

Screen shown only for units with Air Economizer installed 

Range 0.2-20.0 

 

Default 2.0 

 

                                 ┌─┴─┐

 

  Econ SA Cntl Gain:  Proportional XX.X %/F 

 

  Reset Time 

XXX  Sec 

Rate Time  XXX Sec 

 

             └─┬─┘                └─┬─┘

 

 

Range 5-600 

 

Range 0-100 

 

 

Default 75 

 

Default 0 

 

NOTE: Referred to as “VAV Occ Econ Ctrl Gains” in IPC documentation 

Summary of Contents for Trane Intellipak

Page 1: ...and labels that are attached to the equipment Control Algorithm Tuning Parameters Intellipak Rooftop Units General Service Bulletin ATTENTION Warnings Cautions and Notices appear at appropriate sectio...

Page 2: ...plays showing the correct factory preset values Any particular unit will contain only a portion of this list of displays WARNING Personal Protective Equipment PPE Required Failure to wear proper PPE f...

Page 3: ...een shown only for units with Dehumidification Installed SA Reheat Control Gains Proportional XX X F Reset Time XXX Sec Range 0 2 20 0 Range 5 600 Default 3 3 Default 50 Note XXX Sec field becomes DIS...

Page 4: ...Default 1800 Note XXX Sec field becomes DISABLE if 3600 seconds Screen shown only for CV units Zone Control Occupied Cooling Gains Proport Bias XXX Max Cy Rate X X CPH Range 0 400 Range 1 5 6 0 Defaul...

Page 5: ...for the number of configured heat stages If heat stages are not configured it will place 30 F in the field as a default until heat stages are configured This will happen once at power up if needed an...

Page 6: ...pply Air Temp High Limit XX X F Range 80 140 Default 120 Screen shown only for VAV units Supply Air Pressure Gain Proportional XX X IWC Reset Time XXX Sec Range 0 2 20 0 Range 1 60 Default 3 3 Default...

Page 7: ...0 Default 17 s Default 80 Note XXXXs field becomes DISABLE and Prop and Feedforward items are not shown if Reset Time 1000 s on Ipak 1 units only Screen shown only for RT or RT AH units with DX Coolin...

Page 8: ...hen Temp Above Setpoint Disable is displayed when the value is incremented above 255 A selection of Disable disables wheel shutoff changes to screen below and allows continuous wheel operation when co...

Page 9: ...et Time w VSC wo VSC 100 Sec 50 Sec ___________ Setup CV Air Economizer Control Gains Proportional 10 0 F ___________ Setup Reset Time DISABLE ___________ Setup Rate Time 0 Sec ___________ Setup Bias...

Page 10: ...rease industrial productivity and efficiency We are a 13 billion global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Inge...

Reviews: