![Ingersoll-Rand Trane Intellipak General Service Bulletin Download Page 6](http://html1.mh-extra.com/html/ingersoll-rand/trane-intellipak/trane-intellipak_general-service-bulletin_2059244006.webp)
6
RT-SVB98B-EN
Screen shown only for units with Modulating Gas or Hydronic Heat installed
Zone Control Modulating Heat
When CV
SZVAV Heating Control Gains
When SZVAV
┌──────────────────┴────────────────────┐
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
Proport Bias XXX °F Rate Time
XXX Sec
└─┬─┘ └─┬─┘
Range 0-40
Range 0-100
Default 0
Default 0
Screen shown only for units with Modulating Gas or Hydronic Heat installed
Zone Control Modulating Heat
Supply Air Temp High Limit
XX.X °F
└─┬─┘
Range
80-140
Default
120
Screen shown only for VAV units
Supply Air Pressure Gain
Proportional XX.X %/IWC Reset Time XXX Sec
└─┬─┘ └─┬─┘
Range 0.2-20.0
Range 1-60
Default 3.3
Default 5
Screen shown only for IntelliPak II units with Return Fan VFD installed
Return Plenum Pressure Gain
Proportional XX.X %/F Reset Time XX Sec
└──┬──┘ └─┬─┘
Range 0.2-20.0
Range 1.0-60.0
Default 3.3
Default 5.0
Link
Screen shown only for units with VCM installed
Range 20-2000
Default 100
┌─┴─┐
Min OA Flow Gain: Proportion XXXXX %/CFM
Reset Time
XXX Sec
Rate Time XXX Sec
└─┬─┘ └─┬─┘
Range 0-600
Range 0-100
Default 10
Default 0