Table 1.
Factory presets list
Adjustable Function
Factory Preset
Changed To
To adjust
press...
CIPD Sensitivity Parameters
Circuit 1 CIPD Sensitivity
30
___________
Setup
Circuit 2 CIPD Sensitivity
30
___________
Setup
Control Algorithm Tuning Parameters (Partial)
(a)
VAV Cooling Control Gains
Proportional (w-VSC / wo-VSC)
(2.0%/F/3.3%/F)
___________
Setup
Reset Time (w-VSC/wo-VSC)
(100 Sec/50 Sec)
___________
Setup
CV Air Economizer Control Gains
Proportional
10.0% F
___________
Setup
Reset Time
DISABLE
___________
Setup
Rate Time
0 Sec
___________
Setup
Bias
0 deg F
___________
Setup
SZVAV Cooling Control Gains
Proportional
6.0% F
___________
Setup
Reset Time
1200 Sec
___________
Setup
Rate Time
0 Sec
___________
Setup
Bias
0 deg F
___________
Setup
Zone Control Modulating Heat Gains
Proportional
10.0% F
___________
Setup
Reset Time
DISABLE
___________
Setup
Rate Time
0 Sec
___________
Setup
Bias
0 deg F
___________
Setup
SZVAV Heating Control Gains
Proportional
8.0% F
___________
Setup
Reset Time
1200 Sec
___________
Setup
Rate Time
0 Sec
___________
Setup
Bias
0 deg F
___________
Setup
(a) Field replacement of control modules requires proper human interface setup to insure unit performance.