Table 1.

Factory presets list

Adjustable Function

Factory Preset

Changed To

To adjust

press...

CIPD Sensitivity Parameters

Circuit 1 CIPD Sensitivity

30

___________

Setup

Circuit 2 CIPD Sensitivity

30

___________

Setup

Control Algorithm Tuning Parameters (Partial)

(a)

VAV Cooling Control Gains

              Proportional (w-VSC / wo-VSC)

(2.0%/F/3.3%/F)

___________

Setup

              Reset Time (w-VSC/wo-VSC)

(100 Sec/50 Sec)

___________

Setup

CV Air Economizer Control Gains

Proportional

10.0% F

___________

Setup

Reset Time

DISABLE

___________

Setup

Rate Time

0 Sec

___________

Setup

Bias

0 deg F

___________

Setup

SZVAV Cooling Control Gains

Proportional

6.0% F

___________

Setup

Reset Time

1200 Sec

___________

Setup

Rate Time

0 Sec

___________

Setup

Bias

0 deg F

___________

Setup

Zone Control Modulating Heat Gains

Proportional

10.0% F

___________

Setup

Reset Time

DISABLE

___________

Setup

Rate Time

0 Sec

___________

Setup

Bias

0 deg F

___________

Setup

SZVAV Heating Control Gains

Proportional

8.0% F

___________

Setup

Reset Time

1200 Sec

___________

Setup

Rate Time

0 Sec

___________

Setup

Bias

0 deg F

___________

Setup

(a) Field replacement of control modules requires proper human interface setup to insure unit performance.

Summary of Contents for Trane Intellipak

Page 1: ...and labels that are attached to the equipment Control Algorithm Tuning Parameters Intellipak Rooftop Units General Service Bulletin ATTENTION Warnings Cautions and Notices appear at appropriate sectio...

Page 2: ...plays showing the correct factory preset values Any particular unit will contain only a portion of this list of displays WARNING Personal Protective Equipment PPE Required Failure to wear proper PPE f...

Page 3: ...een shown only for units with Dehumidification Installed SA Reheat Control Gains Proportional XX X F Reset Time XXX Sec Range 0 2 20 0 Range 5 600 Default 3 3 Default 50 Note XXX Sec field becomes DIS...

Page 4: ...Default 1800 Note XXX Sec field becomes DISABLE if 3600 seconds Screen shown only for CV units Zone Control Occupied Cooling Gains Proport Bias XXX Max Cy Rate X X CPH Range 0 400 Range 1 5 6 0 Defaul...

Page 5: ...for the number of configured heat stages If heat stages are not configured it will place 30 F in the field as a default until heat stages are configured This will happen once at power up if needed an...

Page 6: ...pply Air Temp High Limit XX X F Range 80 140 Default 120 Screen shown only for VAV units Supply Air Pressure Gain Proportional XX X IWC Reset Time XXX Sec Range 0 2 20 0 Range 1 60 Default 3 3 Default...

Page 7: ...0 Default 17 s Default 80 Note XXXXs field becomes DISABLE and Prop and Feedforward items are not shown if Reset Time 1000 s on Ipak 1 units only Screen shown only for RT or RT AH units with DX Coolin...

Page 8: ...hen Temp Above Setpoint Disable is displayed when the value is incremented above 255 A selection of Disable disables wheel shutoff changes to screen below and allows continuous wheel operation when co...

Page 9: ...et Time w VSC wo VSC 100 Sec 50 Sec ___________ Setup CV Air Economizer Control Gains Proportional 10 0 F ___________ Setup Reset Time DISABLE ___________ Setup Rate Time 0 Sec ___________ Setup Bias...

Page 10: ...rease industrial productivity and efficiency We are a 13 billion global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Inge...

Reviews: