46
TK 61694-18-IM-EN
Recommended Refrigerant Charge by Model
IIm
mp
po
orrtta
an
ntt:: Failure to add the proper amount of refrigerant will result in decreased system performance. Refer to the
Thermo King Vehicle Powered Truck Installation Standards and Procedures Guide for information on proper
system charging procedures.
Model
Recommended Refrigerant Charge (lb.)
E-200 20
E-200 MAX 50
E-200 MAX 50 Spectrum
1.3kg (2.8lb) (including 1.5m (60") hoses supplied as standard) R134a
1.3kg (2.8lb) (including 1.5(60") hoses supplied as standard) R452A/
R404A
1.6kg (3.5lb) (including 6m(237") hoses supplied as standard) R452A/
R404A
Important:
1.
For each additional meter (39") of hose extension, 80g
(0.17lb) of refrigerant
MUST
be added
2.
It is a good idea to utilise the WINTRAC tool to set
compressor speed at an intermediate level (for example -
60Hz) during refrigeration charge. If the unit is charged
with the compressor at full speed, overcurrent protection
may trip.
Summary of Contents for THERMO KING E-200 Series
Page 29: ...TK 61694 18 IM EN 29 H Ho ol ld do ov ve er r B Ba at tt te er ry y O Op pt ti io on n ...
Page 33: ...TK 61694 18 IM EN 33 S St ta ar rt t S St to op p F Fu un nc ct ti io on na al li it ty y ...
Page 37: ...TK 61694 18 IM EN 37 I In nc cr re ea as se ed d I Id dl le e S Sp pe ee ed d S Se et tu up p ...
Page 49: ...TK 61694 18 IM EN 49 N No ot te es s ...
Page 50: ...50 TK 61694 18 IM EN N No ot te es s ...