background image

6

RT-SVX50C-EN

General Information

Unit Inspection

As soon as the unit arrives at the job site:

Verify that the nameplate data matches the data on the 
sales order and bill of lading (including electrical data).

Verify that the power supply complies with the unit 
nameplate specifications.

Visually inspect the exterior of the unit, including the 
roof, for signs of shipping damage.

Visually inspect the internal components for shipping 
damage as soon as possible after delivery and before 
it is stored. Do not walk on the sheet metal base pans.

If concealed damage is discovered, notify the carrier’s 
terminal of damage immediately by phone and by 
mail. Concealed damage must be reported within 15 
days.

Request an immediate joint inspection of the 
damage by the carrier and the consignee.

Do not remove damaged material from the 
receiving location.

Take photos of the damage, if possible. The owner 
must provide reasonable evidence that the damage 
did not occur after delivery.

Notify the appropriate sales representative before 
installing or repairing a damaged unit.

Precautionary Measures

Avoid breathing fiberglass dust.

Use a NIOSH approved dust/mist respirator.

Avoid contact with the skin or eyes. Wear long-sleeved, 
loose-fitting clothing, gloves, and eye protection.

Wash clothes separately from other clothing: rinse 
washer thoroughly.

Operations such as sawing, blowing, tear-out, and 
spraying may generate fiber concentrations requiring 

additional respiratory protection. Use the appropriate 
NIOSH approved respiration in these situations.

First Aid Measures

Eye Contact - Flush eyes with water to remove dust. If 
symptoms persist, seek medical attention.

Skin Contact - Wash affected areas gently with soap 
and warm water after handling.

Storage

Take precautions to prevent condensate from forming 
inside the unit’s electrical compartments and motors if:

The unit is stored before it is installed; or,

The unit is set on the roof curb, and temporary heat is 
provided in the building. Isolate all side panel service 
entrances and base pan openings (e.g., conduit holes, 
S/A and R/ A openings, and flue openings) from the 
ambient air until the unit is ready for start-up.

Note:

Do not use the unit’s heater for temporary heat 
without first completing the start-up procedure 
detailed under 

“Start Up,” p. 23

.

The manufacturer will not assume any responsibility for 
equipment damage resulting from condensate 
accumulation on the unit’s electrical and/or mechanical 
components.

Unit Description

Before shipment, each unit is leak tested, dehydrated, 
charged with refrigerant and compressor oil, and run 
tested for proper control operation.

Direct-drive, vertical discharge condenser fans are 
provided with built-in thermal overload protection.

The stages of capacity control for these units are achieved 
by starting the Economizer Control Actuator (ECA).

Economizer Control Actuator 
Electromechanical Control

The ECA monitors the mixed air temperature, return air 
temperature, minimum position setpoint (local or 
remote), power exhaust setpoint, CO

2

 setpoint, CO

2

, and 

ambient dry bulb/ enthalpy sensor or comparative 
humidity (return air humidity against ambient humidity) 
sensors, if selected, to control dampers to an accuracy of 
±5 percent of stroke. The actuator is spring returned to the 
closed position any time that power is lost to the unit. It is 
capable of delivering up to 25 in·lb of torque and is 
powered by 24 Vac.

WARNING

Fiberglass Wool! 

Product contains fiberglass wool. Disturbing the 
insulation in this product during installation, 
maintenance or repair will expose you to airborne 
particles of glass wool fibers and ceramic fibers known 
to the state of California to cause cancer through 
inhalation. You MUST wear all necessary Personal 
Protective Equipment (PPE) including gloves, eye 
protection, a NIOSH approved dust/mist respirator, long 
sleeves and pants when working with products 
containing fiberglass wool. Exposition to glass wool 
fibers without all necessary PPE equipment could result 
in cancer, respiratory, skin or eye irritation, which could 
result in death or serious injury. 

Summary of Contents for EAC180A

Page 1: ...ining Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...icates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could r...

Page 3: ...without written permission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Tradema...

Page 4: ...1 Unit Disconnect FIYUDC 21 Pre Start 22 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 22 Electromechanical Controls Test Procedure 22 Start Up 23 Standard Economizer Start Up 23 LLE Cont...

Page 5: ...rometric Relief1 4 E A C 1 8 0 A 3 E G A 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 J Low Leak Economizer Dry Bulb w o Barometric Relief4 L Low Leak Economizer Reference Enthalpy w o Barometric Relief4 N Low L...

Page 6: ...temporary heat is provided in the building Isolate all side panel service entrances and base pan openings e g conduit holes S A and R A openings and flue openings from the ambient air until the unit i...

Page 7: ...ed whenever the position of the economizer dampers meets or exceed the power exhaust setpoint when the indoor fan is on The setpoint panel is located in the return air section and is factory set at 25...

Page 8: ...ied status is to use the G input fan is running Connect the G input to the OCC SENSOR wire at customer connections The controller will then operate in the occupied mode every time the indoor fan is ru...

Page 9: ...nimum distances necessary to assure adequate serviceability cataloged unit capacity and peak operating efficiency Providing less than the recommended clearances may result in condenser coil starvation...

Page 10: ...Dimensional Data 10 RT SVX50C EN Figure 2 Cooling with optional electrical heat units overview Figure 3 Cooling with optional electrical units front side views 15 25 tons standard efficiency...

Page 11: ...al Data RT SVX50C EN 11 Figure 4 Cooling with optional electrical heat units plan view 15 25 tons standard efficiency Figure 5 Foundation units back view horizontal configuration 15 25 tons standard e...

Page 12: ...ndard efficiency Figure 7 Downflow duct connections field fabricated 15 25 tons standard efficiency 9 1 25 4 MM CURB FLANGE LONG SIDES SHORT SIDES Notes Duct flanges mount 7 7 16 down inside the curb...

Page 13: ...re 8 Downflow unit clearance 15 25 tons standard efficiency Figure 9 Barometric relief and economizer 15 25 tons standard efficiency MOTORIZED DAMPER BAROMETRIC RELIEF IS FOR USE WITH A DOWNFLOW ECONO...

Page 14: ...Dimensional Data 14 RT SVX50C EN Figure 10 Manual damper 15 25 tons standard efficiency...

Page 15: ...438 357 416 54 37 25 EAC300A 2208 1888 664 457 345 422 53 35 a Weights are approximate Horizontal and downflow unit and corner weights may vary slightly b Weights do not include additional factory or...

Page 16: ...s gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges General Unit Requirements The checklist listed below is a summary of the steps required to su...

Page 17: ...provided in the unit This is a slip fit joint no threads and can be sealed using PVC Cement or other suitable adhesive A condensate trap must be installed at the unit due to the drain connection bein...

Page 18: ...on selected would be a factory mounted nonfused disconnect switch UDC Provide proper grounding for the unit in accordance with local and national codes Control Power Transformer The 24 volt control po...

Page 19: ...llows Voltage Imbalance AV Average Voltage V1 V2 V3 Line Voltage Readings VD Line Voltage reading that deviates the farthest from the average voltage Example If the voltage readings of the supply powe...

Page 20: ...to position Close the main power disconnect switch and the unit mounted disconnect switch if applicable Checklist Use the following checklist in conjunction with the general checklist General Unit Req...

Page 21: ...y found on the unit nameplate and the N E C 4 Route low voltage class II control wiring through hole in base of unit but not through high voltage conduit Feedcontrolwiringthroughbushingprovided on sid...

Page 22: ...using the setpoint potentiometer located on the Economizer Control ECA if applicable Electromechanical Controls Test Procedure See unit schematic for correct wire numbers Fan Test and Minimum Ventila...

Page 23: ...after powered If OA sensor or Sylk Bus device sensor or actuator is disconnected during the set up mode the JADE will not alarm that failure The MA sensor is a system critical sensor if the MA sensor...

Page 24: ...er disconnect switch to the Off position or proceed to the next component start up procedure Remove electro mechanical test mode connections Final System Set Up After completing all of the pre start a...

Page 25: ...s number represents the force in pounds required to give the needed deflection 6 Compare the force scale reading Step 5 with the appropriate force value listed in Table 5 p 25 If the force reading is...

Page 26: ...data on an operator s maintenance log like the one shown in Table 6 p 27 If the operating pressures indicate a refrigerant shortage measure the system superheat For guidelines refer to Compressor Sta...

Page 27: ...zzle and the microchannel coil is 1 3 Final Process For future reference you may find it helpful to record the unit data requested below in the blanks provided 1 Complete Unit Model Number ___________...

Page 28: ...lt Codes Low Leak Economizer Alarms CO2 Sensor Error SYS Alarm Actuator Undervoltage Actuator Overvoltage Actuator Stalled The FDD system shall detect the following faults Air temperature sensor failu...

Page 29: ...hen the condensate overflow switch is closed a drain pan overflow condition is indicated and it will shut unit operations down Unit Economizer Control ECA Verify Economizer Status by Economizer Actuat...

Page 30: ...08 575 2313 2239 EAC180 300 EAD180 300 60Hz Cooling only Electric Heat Control Box Connection 208 230 380 a 2313 2230 EAC180 300 EAD180 300 60Hz Cooling only Electric Heat 460 575 2313 2234 EAC180 300...

Page 31: ...ervice GW 602 4800 This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a residential application Commercial use is any application where the end p...

Page 32: ...ifications without notice We are committed to using environmentally conscious print practices that reduce waste 2015 Trane All rights reserved RT SVX50C EN 23 Nov 2015 Supersedes RT SVX50B EN 30 Dec 2...

Reviews: