background image

28

 RT-SVX50C-EN

Troubleshooting

Standard Troubleshooting

Failures

Cooling Failure

1.

Cooling and heating set point (slide pot) on the 
thermostat has failed. 

2. CC1 or CC2 24 VAC control circuit has opened. Check 

CC1 & CC2 coils, and any of the controls below that 
apply to the unit (HPC1, HPC2, LPC1, LPC2, DLT1, DLT2, 
Frostat™).

Simultaneous Heat and Cool Failure

Emergency Stop is activated.

Low Leak Economizer 
(LLE) Troubleshooting

1.

The economizer controller provides alarm messages 
that display on the 2-line LCD. If one or more alarms are 
present and there has been no keypad activity for at 
least 5 minutes, the Alarms menu displays and cycles 
through the active alarms.

Note:

You can also navigate to the Alarms menu at any 
time.

2. Once the alarm has been identified and the cause has 

been removed (e.g. replaced faulty sensor), the alarm 
can be cleared from the display.

Note:

If an alarm still exists after you clear it, it re-displays 
within 5 seconds.

To Clear an Alarm

Once the alarm has been identified and the cause has been 
removed (e.g. replaced faulty sensor), the alarm can be 
cleared from the display.

1.

Navigate to the desired alarm.

2. Press .

3. “ERASE?” is displayed.

4. Press .

5. “ALARM ERASED” is displayed.

6. Press 

 (Menu Up) to complete the action and return 

to the previous menu.

Note:

If an alarm still exists after you clear it, it re-displays 
within 5 seconds.

Low Leak Economizer Fault Codes

Low Leak Economizer Alarms:

CO2 Sensor Error

SYS Alarm

Actuator Undervoltage

Actuator Overvoltage

Actuator Stalled

The FDD system shall detect the following faults:

Air temperature sensor failure/fault

Not economizing when it should 

Economizing when it should not

Damper not modulating 

Excess outdoor air

The JADE controller is a certified FDD product (HJW10) by 
California Title 24, Part 6. The FDD system is required for 
meeting California Energy Commission's Title 24 
regulations. 

Table 7, p. 29

 shows the various tests that can 

be performed (rows) and the five faults that are defined by 
FDD (columns). The 'x' means that the test has to be 
conducted to see if it is causing the fault to occur.

WARNING

Hazardous Service Procedures!

The maintenance and troubleshooting procedures 
recommended in this section of the manual could result 
in exposure to electrical, mechanical or other potential 
safety hazards. Always refer to the safety warnings 
provided throughout this manual concerning these 
procedures. Unless specified otherwise, disconnect all 
electrical power including remote disconnect and 
discharge all energy storing devices such as capacitors 
before servicing. Follow proper lockout/tagout 
procedures to ensure the power can not be 
inadvertently energized. When necessary to work with 
live electrical components, have a qualified licensed 
electrician or other individual who has been trained in 
handling live electrical components perform these 
tasks. Failure to follow all of the recommended safety 
warnings provided, could result in death or serious 
injury.

Summary of Contents for EAC180A

Page 1: ...ining Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...icates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could r...

Page 3: ...without written permission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Tradema...

Page 4: ...1 Unit Disconnect FIYUDC 21 Pre Start 22 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 22 Electromechanical Controls Test Procedure 22 Start Up 23 Standard Economizer Start Up 23 LLE Cont...

Page 5: ...rometric Relief1 4 E A C 1 8 0 A 3 E G A 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 J Low Leak Economizer Dry Bulb w o Barometric Relief4 L Low Leak Economizer Reference Enthalpy w o Barometric Relief4 N Low L...

Page 6: ...temporary heat is provided in the building Isolate all side panel service entrances and base pan openings e g conduit holes S A and R A openings and flue openings from the ambient air until the unit i...

Page 7: ...ed whenever the position of the economizer dampers meets or exceed the power exhaust setpoint when the indoor fan is on The setpoint panel is located in the return air section and is factory set at 25...

Page 8: ...ied status is to use the G input fan is running Connect the G input to the OCC SENSOR wire at customer connections The controller will then operate in the occupied mode every time the indoor fan is ru...

Page 9: ...nimum distances necessary to assure adequate serviceability cataloged unit capacity and peak operating efficiency Providing less than the recommended clearances may result in condenser coil starvation...

Page 10: ...Dimensional Data 10 RT SVX50C EN Figure 2 Cooling with optional electrical heat units overview Figure 3 Cooling with optional electrical units front side views 15 25 tons standard efficiency...

Page 11: ...al Data RT SVX50C EN 11 Figure 4 Cooling with optional electrical heat units plan view 15 25 tons standard efficiency Figure 5 Foundation units back view horizontal configuration 15 25 tons standard e...

Page 12: ...ndard efficiency Figure 7 Downflow duct connections field fabricated 15 25 tons standard efficiency 9 1 25 4 MM CURB FLANGE LONG SIDES SHORT SIDES Notes Duct flanges mount 7 7 16 down inside the curb...

Page 13: ...re 8 Downflow unit clearance 15 25 tons standard efficiency Figure 9 Barometric relief and economizer 15 25 tons standard efficiency MOTORIZED DAMPER BAROMETRIC RELIEF IS FOR USE WITH A DOWNFLOW ECONO...

Page 14: ...Dimensional Data 14 RT SVX50C EN Figure 10 Manual damper 15 25 tons standard efficiency...

Page 15: ...438 357 416 54 37 25 EAC300A 2208 1888 664 457 345 422 53 35 a Weights are approximate Horizontal and downflow unit and corner weights may vary slightly b Weights do not include additional factory or...

Page 16: ...s gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges General Unit Requirements The checklist listed below is a summary of the steps required to su...

Page 17: ...provided in the unit This is a slip fit joint no threads and can be sealed using PVC Cement or other suitable adhesive A condensate trap must be installed at the unit due to the drain connection bein...

Page 18: ...on selected would be a factory mounted nonfused disconnect switch UDC Provide proper grounding for the unit in accordance with local and national codes Control Power Transformer The 24 volt control po...

Page 19: ...llows Voltage Imbalance AV Average Voltage V1 V2 V3 Line Voltage Readings VD Line Voltage reading that deviates the farthest from the average voltage Example If the voltage readings of the supply powe...

Page 20: ...to position Close the main power disconnect switch and the unit mounted disconnect switch if applicable Checklist Use the following checklist in conjunction with the general checklist General Unit Req...

Page 21: ...y found on the unit nameplate and the N E C 4 Route low voltage class II control wiring through hole in base of unit but not through high voltage conduit Feedcontrolwiringthroughbushingprovided on sid...

Page 22: ...using the setpoint potentiometer located on the Economizer Control ECA if applicable Electromechanical Controls Test Procedure See unit schematic for correct wire numbers Fan Test and Minimum Ventila...

Page 23: ...after powered If OA sensor or Sylk Bus device sensor or actuator is disconnected during the set up mode the JADE will not alarm that failure The MA sensor is a system critical sensor if the MA sensor...

Page 24: ...er disconnect switch to the Off position or proceed to the next component start up procedure Remove electro mechanical test mode connections Final System Set Up After completing all of the pre start a...

Page 25: ...s number represents the force in pounds required to give the needed deflection 6 Compare the force scale reading Step 5 with the appropriate force value listed in Table 5 p 25 If the force reading is...

Page 26: ...data on an operator s maintenance log like the one shown in Table 6 p 27 If the operating pressures indicate a refrigerant shortage measure the system superheat For guidelines refer to Compressor Sta...

Page 27: ...zzle and the microchannel coil is 1 3 Final Process For future reference you may find it helpful to record the unit data requested below in the blanks provided 1 Complete Unit Model Number ___________...

Page 28: ...lt Codes Low Leak Economizer Alarms CO2 Sensor Error SYS Alarm Actuator Undervoltage Actuator Overvoltage Actuator Stalled The FDD system shall detect the following faults Air temperature sensor failu...

Page 29: ...hen the condensate overflow switch is closed a drain pan overflow condition is indicated and it will shut unit operations down Unit Economizer Control ECA Verify Economizer Status by Economizer Actuat...

Page 30: ...08 575 2313 2239 EAC180 300 EAD180 300 60Hz Cooling only Electric Heat Control Box Connection 208 230 380 a 2313 2230 EAC180 300 EAD180 300 60Hz Cooling only Electric Heat 460 575 2313 2234 EAC180 300...

Page 31: ...ervice GW 602 4800 This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a residential application Commercial use is any application where the end p...

Page 32: ...ifications without notice We are committed to using environmentally conscious print practices that reduce waste 2015 Trane All rights reserved RT SVX50C EN 23 Nov 2015 Supersedes RT SVX50B EN 30 Dec 2...

Reviews: